DESCRIPTION 

The Expert  nano  model  200NANO3CF is an  electronic  regulator 

operating  with  microprocessor  designed  to  control  refrigerated 

counters,  display  windows  and  static  or  ventilated  refrigeration 

units  with  off-cycle  or  electrical  defrosting.  It  is  fitted  with  two 

analogue inputs for NTC or PTC temperature probes, one digital 

input,  three  relays  for  the  control  of  the  compressor,  fans  and 

defrosting function (the defrosting relay can be configured as the 

light command) and buzzer. The regulator can be also configured 

for heat applications. 

 

PRINCIPAL CHARACTERISTICS 

 

Can be configured for hot or cold applications. 

 

Can be configured to read NTC or PTC probes. 

 

Relay  for  controlling  the  compressor,  evaporator  fans  and 

defrosting  elements  (defrost  output  can  be  configured  like  light 

output). 

 

Defrosting can be configured for off-cycle, heating element, heating 

element with temperature control or cycle inversion and frequency 

and duration can be set. End-of- defrosting can be based on time or 

temperature. 

 

Configurable input as evaporator probe or dirty condenser alarm 

probe. 

 

Key operated manual START/STOP defrosting. 

 

Key operated ON/OFF. 

 

Cold  room  light  ON/OFF  switch  with  key  or  by  means  of  door 

switch (if defrost output is configured like cold room light). 

 

Display/adjustment of temperature with decimal point. 

 

Flat front surface for easy cleaning and keys of ample dimensions 

which can be customised with various colours (on request). 

 

3-Digit LED display with sign, decimal point and system status icon.  

Internal buzzer for acoustic signals. 

 

PEGO programming philosophy guaranteeing immediate start-up. 

 

RS485 serial connection with Modbus-RTU or Telenet protocol. 

 

IP65 front protection. Two-fold fastening option: clips / screws. 

 

Voltage and terminal type depending on model 

 

NANO3CF SERIES MODELS 

PEGO CODE 

EXPERT NANO DESCRIPTION 

200NANO3CF01

 

Power 230Vac, 3 relays (8A+8A+16A), digital input, 

cold/hot function, RS485, Buzzer, fixed clamps. 

200NANO3CF02

 

Power 230Vac, 3 relays (8A+8A+16A), digital input, 

cold/hot function, RS485, Buzzer, removable clamps. 

200NANO3CF11

 

Power 12Vac/dc, 3 relays (8A+8A+16A), digital input, 

hot/cold function, RS485, Buzzer, fixed clamps. 

KEY FUNCTIONS 

Key 

FUNCTION 

 

UP KEY 

Increases  values  /  Scrolls  parameters  in  ascending 

order  /  Deactivates  acoustic  alarm  if  present  / 

Acknowledges an alarm. With variable do2=1 if pressed 

for  over  3  sec,  activates/deactivates  room  light  (DO2 

output).  With  manual  activation/  deactivation  of  the 

light a BIP is generated to confirm. 

 

DOWN KEY 

Decreases  values  /  Scrolls  parameters  in  descending 

order  /  If  pressed  for  over  3  sec.  activates  manual 

defrosting (if suitable conditions are present). 

Terminates defrosting if pressed for over 3 sec. during 

the  defrosting  process.  With  manual  activation/ 

deactivation  of  defrosting  a  BIP  is  generated  to 

confirm. 

Stand 

by

 

STAND-BY KEY 

If pressed for over 1 sec. alternates the Stand-By with 

normal mode and vice versa. When mode is alternated 

a  BIP  is  generated  to  confirm.  In  Stand-By  mode  the 

system  stops  and  the  display  signals  OFF  and  the 

temperature alternating. 

 

SET KEY

 

Displays the set point. 

Allows  the  set  point  to  be  entered  when  pressed  in 

combination  with  the  DOWN  or  UP  keys.  Resets  the 

acoustic alarm if present. 

 

STATUS ICON 

ICON 

MEANING 

 

COLD FUNCTION ICON 

(icon activated with mOd=0/2)   

Led OFF = Cold function OFF 

Led ON =  Cold function ON 

Flashing Led = Cold function ON  waiting for C1 delay 

 

HOT FUNCTION ICON 

 (icon activated with mOd=1/3)   

Led OFF = Hot function OFF 

Led ON =  Hot function ON   

 

FAN ICON

   

Led OFF = Fans OFF 

Led ON =  Fans ON   

Flashing Led =  Fans paused after defrosting (see 

parameter F5) 

 

DEFROSTING ICON  

(icon activated with mOd=0/2)   

Led OFF = Defrosting OFF 

Led ON =  Defrosting ON   

Led Flashing = Dripping in progress after defrosting (see 

parameter d7) 

 

DOOR SWITCH / ROOM LIGHT ICON

 

Led OFF = Door switch not activated or not used and 

room light off 

Led ON =  Room light ON  (function active only if 

variable dO2=1) 

Flashing Led = Door switch activated or room light ON 

with alarm E8. 

 

ALARM ICON

 

Led OFF = No alarm present 

Led ON = Indicates temperature alarm intervention 

with remedy (HACCP alarm). 

Flashing Led =  Alarm present 

COMBINED ACTIVATION OF KEYS AND THEIR FUNCTIONS 

FUNCTION / KEY COMBINATION 

SETTINGS PROGRAMMING   /

  (Set + 

 o 

)

 

Press  the  SET  key  to  view  the  current  SETPOINT  value 

(temperature). 
Keeping the SET key down and pressing either the (

) or (

key, the SETPOINT value can be changed. 

Release the SET key to return to view the room temperature; 

the changes made will be automatically saved. 

LEVEL 1 PROGRAMMING /

  (

 + 

)

 

Press the UP and DOWN keys simultaneously for over 3 sec. to 

access  the  Level  1  programming  menu.  When  the  menu  is 

accessed, a BIP is generated to confirm. The system leaves the 

menu after 30 seconds. 

LEVEL 2 PROGRAMMING

/ (

+

+Stand-by)

 

Press  the  UP,  DOWN  and  STAND-BY  keys  simultaneously  for 

over 3 sec. to access the Level 1 programming menu. When the 

menu is accessed, a BIP is generated to confirm and the system 

is placed in Stand-By mode. 

EXIT PROGRAMMING MENUS  /

  (

 + 

)

 

Pressing  the  UP  and  DOWN  buttons  simultaneously  in  any 

programming menu for over 3 sec. causes the system to save 

the settings entered and leave that menu. A BIP is generated to 

confirm. 

 
GENERAL INFORMATION 

PEGO  S.r.l.  does  not  accept  responsibility  for  any  loss  of  data  or 

information, costs of goods or substitute services, damages to objects, 

persons or animals, lost sales or profits, interruption of activities, any 

direct,  indirect,  accidental,  property,  insured,  punitive,  special  or 

consequential  damage  caused  in  any  way,  be  it  contractual,  extra-

contractual or due to negligence or other responsibility resulting from 

the use of the product or its installation. The guarantee automatically 

becomes  invalid  in  the  case  of  poor  functioning  due  to  tampering, 

impact  or  inadequate  installation.  It  is  mandatory  to  observe  all 

instructions in this manual and the operating conditions of the device. 

PEGO S.r.l. does not accept responsibility for any inaccuracies which 

may  be  present  in  this  manual  in  the  case  that  these  are  due  to 

printing  or  transcription  errors  and  reserves  the  right  to  make 

modifications to its products which it deems necessary or appropriate, 

without prejudicing the products essential characteristics. 

 

ELECTRICAL PRESCRIPTIONS 

Avoid using multipolar cables with conductors connected to inductive 

and  power  loads  and  signal  conductors  such  as  probes  and  digital 

inputs. Avoid installing in the same channels power cables and signal 

cables  (probes,  digital  inputs  or  RS485  connections).  Reduce  to  a 

minimum  the  length  of  the  connecting  cables,  avoiding  that  the 

cabling takes on a spiral form which may have inductive effects on the 

electronic  system.  All  conductors  used  in  the  cabling  must  be 

appropriately  sized  in  order  to  support  the  load  which  they  must 

provide. If it is necessary to extend the probes, use conductors with 

appropriate cross-sections and not less than 1 mm². The extension or 

reduction  of  the  probes  may  alter  the  calibration  which  was 

performed in the factory.  Therefore, verify and calibrate by means of 

an external thermometer. 

 
ELECTRICAL CONNECTIONS: 
 
 
 
 
 
 
 
 
 
 
 
 
FASTENING TO PANEL BT MEANS OF TWO BACK CLIPS: 
 
 
 
 
 
 
 
 
 
 
 
 
 
FASTENING TO PANLE BY MEANS OF TWO FRONT SCREW: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

TECHNICAL DATA 

Power voltage 

Model 200NANO3CF01 

Model 200NANO3CF02 

230 V

~

  +10/-15%  50/60Hz   

Model 200NANO3CF11 

12V

~

 +10/-15%  50/60Hz  / 12Vdc +10/-15%  class 2 

Absorbed power  

3 VA  Max 

Environment conditions 

Operating temperature 

   -5T55°C  - humidity < 90% Rel. Hum. Not condensing 

Storage temperature 

   -20T70°C - humidity < 90% Rel. Hum.  Not condensing 

Unsuitable operating 

environments 

Environments with strong vibrations or impacts; aggressive, 

polluted or corrosive atmospheres, exposure to direct solar 

radiation, explosive atmospheres or flammable gas. 

General characteristics 
Display 

3-Digit with sign, decimal point and 9 LED status indicators 

Resolution 

0.1 °C 

Probe precision (electronic) 

± 0.5 °C 

Reading range 

-45T99 °C 

Model 200NANO3CF01 

Model 200NANO3CF11 

Power clamps: fixed, screw for cables with c/section 0.2 to  2.5mm

2

 

Signal clamps:  fixed, screw for cables with c/section  0.2 to  1.5mm

2

 

Model 200NANO3CF02 

Removable, screw clamps for cables with c/section 0.2 to  2.5mm

2

 

Software class: A  /  Parameters saved on non-volatile memory (EEPROM) 
Input characteristics 

Analogue inputs 

2 Inputs for NTC probes (10K Ώ 1%  at 25°C)  or 

2 Inputs for PTC probes (1K Ώ  at 25°C)   

Digital inputs 

1 Input (clean contact) 

Output characteristics 
Compressor relay (DO1) 

N.O.  16(6)A  / 250V

~

 

Heating elements relay 

(DO2) 

N.O.  8(3)A     N.C.  6(3)A  /  250V

~

 

Fan relay (DO3) 

N.O.  8(3)A  /  250V

~

 

Buzzer 

Present 

Dimensional, insulation and mechanical characteristics 

Dimensions 

93x37x65mm  Depth 59mm  

(Depth 69mm with removable clamps) 

Drill hole template 

71x29mm (+0.2/-0.1mm) 

Front protection rating 

IP65 with front board installation 

Installation 

In front of board by means of rear fastening clips or two front 

screws 

Casing 

Plastic PC+ABS UL94 V-0 body, PC transparent front, Key panel PC 

or PC+ABS 

Insulation type 

Class II 

Conformity with EU low voltage directives, electromagnetic compatibility and EC mark 
Conforms to following EU Directives : Directives 2014/30/EU , 2014/35/EU 

Conforms to following harmonised standards:  

EN60730-1:2016, EN60730-2-9:2010, EN61000-6-1:2007,  EN61000-6-3:2007 