Pag. 3
200 EXPERT B2/4
– Parameters Abstract
Rev. 02-09
Pc
Compressor protection contact status
0 = NO
1 = NC
0 = NO
doC
Compressor safety time for door switch
: when the door is
opened the evaporator fans shut down and the compressor
will continue working for time
doC
, after which it will shut
down.
0…5 minutes
0
tdo
Compressor restart time after door opening.
when the
door is opened and after tdo time, it’s setted back the normal
functioning giving door open alarm (Ed)
With tdo=0 the parameter is disabled.
0…240 min
0 = disabled
0
Fst
FAN shutdown TEMPERATURE
The fans will stop if the temperature value read by the
evaporator
sensor is higher than this value.
-45…+45°C +45°C
Fd
Fst differential
0…+10°C 2°C
LSE
Minimum value attributable to setpoint.
-45... HSE °C
-45°C
HSE
Maximum value attributable to setpoint.
+45... LSE °C
+45°C
tA
NO – NC
alarm relay switching
0= activates when alarm is on
1= deactivates when alarm is on
1
AU
Auxiliary/alarm relay control
0= alarm
relay
1= manual auxiliary relay
controlled via AUX key
2= automatic auxiliary relay
managed by StA temp.
setting with 2°C differential
3= relay disabled / TeleNET
function
4= pump down function (see
CHAP
5.15)
5= free voltage contact for
condensing unit (AUX relay
and compressor relay in
parallel)
6= Contact for casing element
control (AUX relay closed
with compressor output
inactive).
7= relay disabled / Modbus-RTU function
0
StA
Temp. setting for aux. relay
-45…+45°C 0
In1
Man in cold room alarm
Select input INP1 on the board as
compressor protection
alarm
or as
man in cold room alarm
(contact NC).
0 = compressor protection
1 = man in room alarm
0
P1
Password type of protection
( active when PA is not equal 0)
0 = only display set point
1= display set point, AUX,
light
access
2= access in programming
not
permitted
3= access in second level
programming
not
permitted
3
PA
Password
(see P1 for the type of protection)
0...999 0 = not active
0
reL
Software release
indicates software version
7 (Read only)
TROUBLESHOOTING
ALARM CODE
POSSIBLE CAUSE
SOLUTION
E0
Cold room temperature sensor not working properly
•
Check that cold room temperature sensor is
working properly
•
If the problem persists replace the sensor
E1
Defrost sensor not working properly
(In this case defrosts will last time
d3
)
•
Check that defrost sensor is working properly
•
If the problems persists replace the sensor
E2
Eeprom alarm
An EEPROM memory alarm has been detected
(All outputs except the alarm one are deactivated)
•
Switch unit off and back on
E8
Man in cold room alarm
•
Reset the alarm input inside the cold room
Ec
Compressor protection tripped
(e.g. thermal protection or max pressure
switch)
(All outputs except the alarm one – where applicable – are deactivated)
•
Check that compressor is working properly
•
Check compressor absorption
•
If the problem persists contact the technical
assistance service
Ed
Open door Alarm.
When the door is opened and after tdo time, it’s setted
back the normal functioning giving door open alarm (Ed)
•
Check door switch status
•
Check door switch connections
•
If the problem persists contact the technical
assistance service
Temperature
shown on display
is flashing
Minimum or maximum temperature alarm.
The temperature inside the cold room has exceeded the min. or max.
temperature alarm setting (see variables
A1 and A2, user programming
level
)
•
Check that the compressor is working properly.
•
Sensor not reading temperature properly or
compressor start/stop control not working.
ENGLISH