Pego ECP 200 Base 2 Скачать руководство пользователя страница 3

                                                                                                                                                             

                                                                                                                                   

Pag. 3

 

200 EXPERT B2/4 

– Parameters Abstract

 

Rev. 02-09

 

Pc 

Compressor protection contact status

 

0 = NO 
1 = NC 

0 = NO 

doC 

Compressor safety time for door switch

: when the door is 

opened the evaporator fans shut down and the compressor 
will continue working for time 

doC

, after which it will shut 

down.

 

0…5 minutes 

tdo 

Compressor restart time after door opening.  

when the 

door is opened and after tdo time, it’s setted back the normal 
functioning giving door open alarm (Ed) 
With tdo=0 the parameter is disabled.

 

0…240 min  

 

0 = disabled 

Fst 

FAN shutdown TEMPERATURE 

The fans will stop if the temperature value read by the 

evaporator 

sensor is higher than this value. 

-45…+45°C +45°C 

Fd 

Fst differential  

0…+10°C 2°C 

LSE 

Minimum value attributable to setpoint. 

-45... HSE °C 

-45°C 

HSE 

Maximum value attributable to setpoint. 

+45... LSE °C 

+45°C 

tA 

NO – NC

 alarm relay switching 

0=  activates when alarm is on  
1=  deactivates when alarm is on 

AU 

Auxiliary/alarm relay control

 

0= alarm 

relay 

1=  manual auxiliary relay 
 

controlled via AUX key 

2=   automatic auxiliary relay 
 

managed by StA temp. 

 

setting with 2°C differential 

3=   relay disabled / TeleNET 
 function 
4=   pump down function (see 
 CHAP 

5.15) 

5=  free voltage contact for 

  condensing unit (AUX relay 

  and compressor relay in 

 parallel) 

6=  Contact for casing element 

  control (AUX relay closed 

 with compressor output 

 inactive). 

7=  relay disabled / Modbus-RTU function 

StA 

Temp. setting for aux. relay 

-45…+45°C 0 

In1 

Man in cold room alarm 

Select input INP1 on the board as 

compressor protection 

alarm 

or as 

man in cold room alarm 

(contact NC). 

0 =   compressor protection 
1 =   man in room alarm 

P1 

Password type of protection 

( active when PA is not equal 0) 

0 =   only display set point 
1=   display set point, AUX, 
 light 

access 

2=   access in programming 
 not 

permitted 

3=   access in second level 
 programming 

not 

 permitted 

PA 

Password 

(see P1 for the type of protection) 

0...999    0 = not active 

reL 

Software release 

indicates software version 

7 (Read only) 

 

TROUBLESHOOTING 

ALARM CODE  

POSSIBLE CAUSE 

SOLUTION 

E0 

Cold room temperature sensor not working properly

 

• 

Check that cold room temperature sensor is 
working properly 

• 

If the problem persists replace the sensor 

E1 

Defrost sensor not working properly 

(In this case defrosts will last time 

d3

• 

Check that defrost sensor is working properly 

• 

If the problems persists replace the sensor 

E2 

Eeprom alarm 

An EEPROM memory alarm has been detected 
(All outputs except the alarm one are deactivated) 

• 

Switch unit off and back on  

E8 

Man in cold room alarm 
 

• 

Reset the alarm input inside the cold room 

Ec 

Compressor protection tripped 

(e.g. thermal protection or max pressure 

switch) 
(All outputs except the alarm one – where applicable – are deactivated) 

• 

Check that compressor is working properly 

• 

Check compressor absorption 

• 

If the problem persists contact the technical 
assistance service 

Ed 

Open door  Alarm. 

When the door is opened and after tdo time, it’s setted 

back the normal functioning giving door open alarm (Ed)

 

• 

Check door switch status  

• 

Check door switch connections 

• 

If the problem persists contact the technical 
assistance service 

Temperature 

shown on display 

is flashing  

 

Minimum or maximum temperature alarm. 

The temperature inside the cold room has exceeded the min. or max. 
temperature alarm setting (see variables 

A1 and A2, user programming 

level

• 

Check that the compressor is working properly. 

• 

Sensor not reading temperature properly or 
compressor start/stop control not working. 

ENGLISH

Содержание ECP 200 Base 2

Страница 1: ...T RS485 TELENET RS485 TELENET RS485 TELENET RS485 TELENET Power Supply 230vac levering 230vac Versorgung 230vac Alimentation 230vac Suministro 230vac Alimentazione 230vac Defrost ontdooi elementen Abtauheizungen résistances de dégivrage resistencias de descongelación Resistenze sbrinamento Fan verdamperventilator Verdampferlüfter ventilateur évaporateur Evaporador ventilador Ventole evaporatore Co...

Страница 2: ...rn 3 seconds Change menu Installer level 3 seconds Return 3 seconds VARIABLES MEANING VALUE DEFAULT r0 Temperature difference compared to main SETPOINT 0 2 10 C 2 C d0 Defrost interval hours 0 24 hours 4 hours d2 End of defrost setpoint Defrost is not executed if the temperature read by the defrost sensor is greater than d2 If the sensor is faulty defrosting is timed 35 45 C 15 C d3 Max defrost du...

Страница 3: ...of protection active when PA is not equal 0 0 only display set point 1 display set point AUX light access 2 access in programming not permitted 3 access in second level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Software release indicates software version 7 Read only TROUBLESHOOTING ALARM CODE POSSIBLE CAUSE SOLUTION E0 Cold room temperature ...

Страница 4: ...level 3 seconden Terugkeer 3 seconden VARIABELEN VERKLARING WAARDE FABR INST r0 Temperatuur differentie vergeleken met het SETPOINT 0 2 10 C 2 C d0 Ontdooi interval Uur 0 24 uur 4 uur d2 Ontdooibeïndigings setpoint Ontdooiing wordt niet uigevoerd als de temperatuurwaarde van de ontdooi sensor gro d2 Als de sensor defect is wordt de ontdooiing op tijd uitgevoerd 35 45 C 15 C d3 Max ontdooitijd minu...

Страница 5: ...f als persoon in ruimte alarm contact NC 0 compressor beveiliging 1 persoon in ruimte alarm 0 P1 Password type beveiliging actief als PA niet gelijk is 0 0 alleen display setpoint 1 display setpoint AUX verlichting toegang 2 toegang tot programmering niet toegestaan 3 toegang tot tweede programmeerniveau is niet toegestaan 3 PA Password zie P1 voor het type beveiliging 0 999 0 niet actief 0 reL So...

Страница 6: ...haltzustand des Türkontaktschalters 0 NO 1 NC 0 F3 Verdampferlüfter bei Verdichter Aus 0 Lüfter Ein 1 Lüfter Aus 1 F4 Verdampferlüfter während der Abtauphase 0 Lüfter Ein 1 Lüfter Aus 1 dE Verdampferfühler vorhanden 0 vorhanden 1 nicht vorhanden 0 d1 Abtauart 0 Elektrisch 1 Heißgas 0 Ad Geräte Adresse für Verbindung mit Telenet Auswerte Software oder Modbus 0 31 wenn AU 3 1 247 wenn AU 7 0 Ald Ver...

Страница 7: ...0 Verdichterschutz 1 Personen im Kühlraum 0 P1 Passwort Schutz nur aktiv wenn PA nicht 0 0 nur Anzeigen keine Änderungen möglich 1 Anzeigen Zugriff auf Beleuchtung und AUX 2 Parameterebenen verriegeln 3 nur Parameterebene 2 verriegeln 3 PA Passwort siehe P1 für Schutzstufe 0 999 0 nicht aktiv 0 reL Software Version Aktuelle Software Störungen Meldungen im Display Mögliche Ursache Event Abhilfen E0...

Страница 8: ...r 3 secondes VARIABLES SIGNIFICATION VALEURS VALEURS PAR DÉFAUT r0 Différentiel de température relatif au POINT DE CONSIGNE principal 0 2 10 C 2 C d0 Intervalle de dégivrage heures 0 24 heures 4 heures d2 Point de consigne de fin de dégivrage Le dégivrage n a pas lieu si la température relevée par la sonde de dégivrage dépasse la valeur d2 en cas de sonde défectueuse le dégivrage a lieu par tempor...

Страница 9: ...a chambre 0 protection compresseur 1 alarme personne dans chambre 0 P1 Mot de passe type de protection actif quand PA différent de 0 0 visualise uniquement point de consigne 1 visualise point de consigne accès aux touches d éclairage et AUX 2 verrouille accès programmation 3 verrouille accès programmation de second niveau 3 PA Mot de passe voir P1 pour le type de protection 0 999 0 fonction désact...

Страница 10: ...gundos VARIABLES SIGNIFICADO VALORES POR DEFECTO r0 Diferencial de temperatura referido al SETPOINT principal 0 2 10 C 2 C d0 Intervalo de descongelación horas 0 24 ore 4 horas d2 Setpoint de fin descongelación La descongelación no se realiza si la temperatura leída por la sonda de descongelación es superior al valor d2 En caso de sonda averiada la descongelación se realiza a tie 35 45 C 15 C d3 M...

Страница 11: ... visualiza sólo el set point 1 visualiza set point acceso a las teclas luz y AUX 2 bloquea el acceso en programación 3 bloquea el acceso en program de segundo nivel 3 PA Contraseña véase P1 para el tipo de protección 0 999 0 función desactivada 0 reL versión software indica la versión software sólo lectura 7 DIAGNÓSTICO CÓDIGO ALARMA POSIBLE CAUSA OPERACIÓN A EFECTUAR E0 Anomalía de funcionamiento...

Страница 12: ...RI DEFAULT r0 Differenziale di temperatura riferito al SETPOINT principale 0 2 10 C 2 C d0 Intervallo di sbrinamento ore 0 24 ore 4 ore d2 Setpoint di fine sbrinamento Lo sbrinamento non è eseguito se la temperatura letta dalla sonda di sbrinamento è superiore al valore d2 In caso di sonda guasta lo sbrinamento è eseguito a tempo 35 45 C 15 C d3 Massima durata sbrinamento minuti 1 240 min 25 min d...

Страница 13: ...one attivo quando PA è diverso da 0 0 visualizza solo il set point 1 visualizza set point accesso ai tasti luce ed AUX 2 blocca accesso in programmazione 3 blocca accesso in program di secondo livello 3 PA Password vedi P1 per il tipo di protezione 0 999 0 funzione disattivata 0 reL release software indica la versione software sola lettura 7 DIAGNOSTICA CODICE ALLARME POSSIBILE CAUSA OPERAZIONE DA...

Страница 14: ...Pag 14 200 EXPERT B2 4 Parameters Abstract Rev 02 09 WHITE PAGE INTENTIONALLY ...

Страница 15: ...Pag 15 200 EXPERT B2 4 Parameters Abstract Rev 02 09 WHITE PAGE INTENTIONALLY ...

Страница 16: ...Pag 16 200 EXPERT B2 4 Parameters Abstract Rev 02 09 PEGO S r l Via Piacentina 6 b 45030 OCCHIOBELLO ROVIGO Tel 0425 762906 Fax 0425 762905 www pego it e mail info pego it Distributore ...

Отзывы: