 A.  VENT SYSTEM INSTALLATION

1.  Determine vent terminal location:

a.  Vent length must be between 3’ and 20’ long. 

See paragraph 4.A.3 and Figure 4.1 for air 

intake requirements.

b.  No clearance is required between vent terminal 

and combustible construction.

c.  Vent terminal extends 12” beyond outside wall 

surface and at least 16” beyond inside wall 

surface. See Figure 4.1.

d.  Sidewall vented products are susceptible to 

wind conditions that can effect combustion. To 

minimize the effects of wind, the exhaust and 

air inlet terminations must penetrate the same 

wall or vertical surface. In addition, the length of 

the exhaust and air inlet pipes must be roughly 

equivalent.

e.  Condensation from a sidewall vented appliance 

may cause paint and other surface coatings to 

deteriorate. In addition, soot stains may appear 

on surrounding surfaces if the boiler is not 

properly maintained.

f.  If the boiler is used to heat potable (tap) water, 

the boiler will operate year round. The effects 

of hot gases and odors must be taken into 

consideration during the summer months.

g.  See Figure 4.2 for an illustration of clearances for 

location of exit terminals for direct-vent, sidewall 

venting systems.

h.  The boiler vent system shall terminate at least 3 

feet (0.9 m) above any forced air inlet located 

within 10 feet (3 m). Note: This does not apply 

to the combustion air inlet of a direct-vent 

appliance. 

7

 4. VENTING

VENTING

This boiler is shipped with a Z-Flex Vent Terminal 

carton, and a Z-Flex Venting Components Kit. The 

following components from these two cartons must 

be used in the installation of this boiler:

·

  Z-Flex Oil Vent Terminal

·

  Z-Flex Vent Pipe

·

  Z-Flex Appliance Adapter

·

  Z-Flex Terminal Adapter

·

  Z-Flex Sealant

NOTICE

Figure 4.1: Venting

This Oil-Fired Unit Shall be Connected to a Direct Vent 

System, to Assure Safe Proper Operation of the Unit.

CAUTION

Table 4.1

See Sidewall Venting 

NOTICE

 on inside of front cover of this manual.

Содержание WV-DV Series

Страница 1: ...WV DV Boilers Series Oil Installation Operation Maintenance Manual...

Страница 2: ...inter months as well as shorten the life of the deck materials Refer to Chapter 4 in this manual for specific terminal location requirements Condensate from a side wall vent terminal may also cause pa...

Страница 3: ...ILER 4 3 PIPING CONTROLS 5 A BOILER SUPPLY RETURN 5 B SAFETY RELIEF VALVE 5 C TANKLESS WATER HEATER 5 D INDIRECT FIRED WATER HEATER 6 E CONTROLS 6 4 VENTING 7 A VENT SYSTEM INSTALLATION 7 5 BURNER SET...

Страница 4: ...instructions and make special notice of potential hazards These categories mean in the judgment of PB Heat LLC USING THIS MANUAL USING THIS MANUAL Indicates a hazardous situation which if not avoided...

Страница 5: ...em is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating This boiler is part of a modular or multiple boiler system having...

Страница 6: ...This boiler is suitable for use on combustible flooring provided the boiler is not set on carpet and a metal drip pan is placed under the appliance 4 See clearance information in Section 1 Preinstall...

Страница 7: ...er from condensation Condensation will damage the boiler and will lead to shortened boiler life and maintenance problems 9 If the boiler is to be used in conjunction with a refrigeration system the ch...

Страница 8: ...ure 3 4 PIPING CONTROLS IMPORTANT In accordance with Section 325 f 3 of the Energy Policy and Conservation Act water boilers are equipped with a feature that saves energy by reducing the boiler water...

Страница 9: ...ly maintained f If the boiler is used to heat potable tap water the boiler will operate year round The effects of hot gases and odors must be taken into consideration during the summer months g See Fi...

Страница 10: ...nside 2 Use Z Flex 4 diameter Vent Pipe 3 For air intake use 4 diameter galvanized smoke pipe or 4 diameter flexible corrugated aluminum pipe Maximum equivalent length of galvanized smoke pipe is 40 A...

Страница 11: ...circuit board inside burner cover Post purge duration must be a minimum of one minute Adjust dial so arrow is pointing directly to the right toward mounting screw for AL1009 bracket Check post purge...

Страница 12: ...y require the addition of a backflow preventer or manual fill only with separation from the city water supply d Consider the minimum temperature of potential exposure in the system when deciding on th...

Страница 13: ...65 1 3 3 WV DV 04 115 Hago 85 60 B or Delavan 85 60 W 180 2 5 0 WV DV 04 130 Hago 1 10 60 B or Delavan 1 10 60 W 140 4 5 0 Start up and adjustment recommendations Above Turbulator Pin Air Damper and A...

Страница 14: ...National Electrical Code and Local Requirements Single Pole Switches including those of Safety Controls or Protective Devices shall not be wired in a grounded line 6 ELECTRICAL Do not connect power su...

Страница 15: ...13 ELECTRICAL Figure 6 2 Hydrolevel 3250 Limit Control Riello Burner...

Страница 16: ...es become airborne during service or repair inhalation of these particles may be hazardous to your health Avoid Breathing Fiber Particulates and Dust Suppliers of RCF recommend the following precautio...

Страница 17: ...ust be taken not to damage this material during cleaning 4 Remove any scale or soot from the combustion chamber area by vacuum cleaning or any other available means 5 Replace oil burner and flue colle...

Страница 18: ...NTENANCE 2 Be certain that the boiler and system are refilled before returning to service Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time CA...

Страница 19: ...unusual piping and pickup requirements such as intermittent system operation extensive piping systems etc 4 Heating Capacity and Annual Fuel Utilization Efficiency AFUE ratings are based on U S Gover...

Страница 20: ...ir Parts Repair parts are available from your local PB Heat LLC distributor or from Parts To Your Door at 1 610 916 5380 www partstoyourdoor com Note Remember to include the boiler model number and se...

Страница 21: ...lue Collector Plate Blanket Seal 1 90999 90999 11 Flue Collector Cover Plate 1 50245 50245 12 Rope Seal 2 ft 51209 51209 13 Rear Outlet Cover Plate 1 90563 90563 15 Jacket Assembly 1 90098 90418 Limit...

Страница 22: ...20 NOTES...

Страница 23: ...ation Operation Maintenance Manual TO THE INSTALLER This manual is the property of the owner and must be affixed near the boiler for future reference TO THE OWNER This boiler should be inspected annua...

Отзывы: