PEERLESS Partner PP-120 Скачать руководство пользователя страница 3

2

Installer - Read all instructions in this manual before installing. 

Perform steps in the given order.
User - This manual is for use only by a qualified heating installer 

/ service technician. Have this water heater serviced / inspected 

annually by a qualified service technician.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE 

CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE 

PERSONAL INJURY, OR DEATH.
NOTE: 
If the heater is exposed to the following, do not operate 

until all corrective steps have been made by a qualified serviceman:
 

1. Fire

 

2. Damage

 

3. Water

Failure to follow this information could result in property damage, 

severe personal injury, or death.

A. When Servicing the Water Heating System

To avoid electric shock, disconnect electrical supply before 

performing maintenance.

To avoid severe burns, allow water heater and associated equipment 

to cool before servicing.

B. Heater Water

Do not use petroleum-based cleaning or sealing compounds in a water 

heating system. Gaskets and seals in the system may be damaged. This 

can result in substantial property damage.

Do not use “homemade cures” or “patent medicines”. Damage to the 

water heater, substantial property damage, and/or serious personal 

injury may result.

NOTICE FOR SINGLE-WALL HEAT EXCHANGER MODELS

Per the Uniform Plumbing Code:

Single-wall heat exchangers are permitted if they satisfy all of the 

following requirements:

The heat exchanger medium is potable water or contains only 

substances which are recognized as safe by the US Food and Drug 

Administration (FDA).

The pressure of the heat exchanger medium is maintained less than 

the normal minimum operating pressure of the potable water system 

(steam systems must comply with this statement).

The equipment is permanently labeled to indicate that only additives 

recognized as safe by the FDA shall be used as the heat transfer 

medium.

Other heat exchanger designs may be permitted where approved by 

the AHJ.

UNCRATING THE WATER HEATER - Any claims for damage or 

shortage in shipment must be filed immediately against the 

transportation company by the consignee.

Do not use this water heater for anything other than its intended 

purpose (as described in this manual). Doing so could result in 

property damage and WILL VOID product warranty.

High heat sources (sources generating heat 100

o

F / 37

o

C or 

greater, such as stove pipes, space heaters, etc.) may damage 

plastic components of the water heater as well as plastic vent 

pipe materials. Such damages ARE NOT covered by warranty. It is 

recommended to keep a minimum clearance of 8” from high heat 

sources. Observe heat source manufacturer instructions, as well 

as local, state, provincial, and national codes, laws, regulations 

and ordinances when installing this water heater and related 

components near high heat sources.

C. Freeze Protection

NOTE: Consider piping and installation when determining heater 

location. Place the water heater as close to the boiler as possible, in a 

location not prone to freezing.

Failure of the water heater due to freeze related damage IS NOT 

covered by product warranty.
In water heaters with single wall heat exchangers, the heat transfer 

fluid must be water or nontoxic food grade glycol, FDA rated 

“generally recognized as safe” (GRAS) and having a toxicity rating or 

class of 1, as listed in Clinical Toxicology of Commercial Products, 5th 

edition. Ensure the system is permanently labeled to indicate any 

additives used in the heat transfer fluid.

NEVER use any toxic chemical, including automotive, standard glycol 

antifreeze, or ethylene glycol made for hydronic (non-potable) 

systems. These chemicals can attack gaskets and seals in water 

systems, are poisonous if consumed, and can cause personal injury 

or death.

D. Water Temperature Adjustment

If the water heater is going to have a set temperature above 120

o

F, you 

must use an ASSE 1017 rated mixing valve to avoid severe burns or 

death from scalding temperatures.

Households with small children, disabled, or elderly persons may 

require a 120

o

F or lower temperature setting to prevent severe 

personal injury or death due to scalding.

Part 1 - General Safety Information

This water heater is approved for indoor installation only and is 

not intended for use as a pool heater. Clearance to combustible 

materials: 0” top, bottom, sides, and back. Heater must have room 

for service: 24” front, 6” top, and 0” sides are recommended service 

clearances. (A combustible door or removable panel is acceptable 

front clearance.) This water heater has been approved for closet 

installation and installation on combustible flooring. Do not install 

directly on carpeting. Install the water heater in a location where 

temperature and pressure relief valve discharge or a leak will not 

result in damage to the surrounding area.

NOTE: Obey all local codes. Obtain all applicable permits before 

installing the water heater.
NOTE: Install all system components and piping in such a manner 

that does not reduce the performance of any fire rated assembly.

Содержание Partner PP-120

Страница 1: ...Partner Water Heater Peerless Indirect Fired Installation Operation Maintenance Manual ...

Страница 2: ...may be the AHJ NOTE The manufacturer reserves the right to modify product technical specifications and components without prior notice For the Installer This water heater must be installed by qualified and licensed personnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements Installations Must Comply With Local sta...

Страница 3: ...nents of the water heater as well as plastic vent pipe materials Such damages ARE NOT covered by warranty It is recommended to keep a minimum clearance of 8 from high heat sources Observe heat source manufacturer instructions as well as local state provincial and national codes laws regulations and ordinances when installing this water heater and related components near high heat sources C Freeze ...

Страница 4: ...alized to the piping system as possible Also locate the water heater and domestic water piping where it will not be exposed to freezing temperatures All piping should be insulated Additionally place the water heater so that the drain controls and inlets outlets are easily accessible NOTE To save on heating costs and improve energy efficiency keep the distance between the boiler and water heater to...

Страница 5: ...ity Continuous Flow Example PP 40 314 75 X 45 280 25 MODEL HEAT EXCHANGER SURFACE VOLUME PRESS DROP FT TEST PRESS WORK PRESS 180O BOILER WATER FIRST HOUR RATINGS GAL 200O BOILER WATER FIRST HOUR RATINGS GAL 180O F BOILER BTU SIZE 200O F BOILER BTU SIZE RECOMMENDED FLOW RATE 140O F 115O F 140O F 115O F PP 30 LB 15 SQ FT 1 5 GAL 6 0 300 PSI 150 PSI 169 234 189 257 114 000 131 000 8 PP 40 20 SQ FT 2 ...

Страница 6: ...0 111 133 150 B COLD START 40 60 83 99 112 A B WARM START 60 90 126 150 169 PP 45 A COLD START 53 80 111 133 150 159 186 187 B COLD START 40 60 83 99 112 119 139 140 A B WARM START 60 90 126 150 170 181 211 212 PP 60 A COLD START 133 150 159 186 187 212 231 B COLD START 99 112 119 139 140 159 173 A B WARM START 153 173 183 214 215 244 266 PP 80 A COLD START 133 150 159 186 187 212 231 239 265 281 ...

Страница 7: ... Be sure that the arrow on the circulator is facing the correct flow direction See pressure drop sizing for circulator this manual On the tank the boiler return connects to the return side of the boiler The return s from heating loop s should have a flow check or swing check valve installed before the return pipe from the tank Steam boiler applications Use only with Peerless Series 63TM or Series ...

Страница 8: ...s used a thermal expansion tank must be installed on the cold water supply between the tank and valve If the tank is replacing a tankless coil in the boiler disconnect coil plumbing and use the cold inlet pipe and hot water outlet pipes for the water heater D Temperature and Pressure Relief Valve The temperature and pressure T P relief valve is provided on all models Install as detailed in the pip...

Страница 9: ...here is a back flow preventer or any other type of no return or check valve in the system a thermal expansion tank IS MANDATORY The expansion tank must be sized for the entire water volume of the hot water system A weeping relief valve indicates the need for an expansion tank See the Typical Expansion Tank example in the Piping section for details G Pressure Drop Sizing For Circulator The boiler c...

Страница 10: ...w preventer and the cold water inlet 3 All circulators should have an integral flow check 4 Drains and check valve between the heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve ...

Страница 11: ...w check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent sca...

Страница 12: ...quired 2 A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet 3 All circulators should have an integral flow check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The install...

Страница 13: ...s recommended that a disconnect switch be installed between the boiler control and the water heater Figure 11 Wiring with Circulators Figure 12 Wiring with Zone Valves CAUTION When wiring the water heater and controls be sure to label all wires to ease future maintenance Wiring errors can cause improper and dangerous operation CAUTION NOTE DO NOT attempt to remove the control well The control well...

Страница 14: ... the water heater to properly flush the system 4 Initiate a call for hot water Ensure each zone valve or circulator operates only when its thermostat calls for heat Purge each zone of air to ensure proper operation 5 Set the water heater to the desired temperature Boiler high limit should be set at least 20oF higher than the heater temperature Set the low limit of the boiler control at the minimum...

Страница 15: ... is blocked or does not operate properly NOTE TAKE CAUTION WHEN OPERATING RELIEF VALVE DISCHARGED WATER MAY PRESENT A SCALD RISK Drain Valve Open the drain valve and drain a few quarts of water from the bottom of the tank to flush any hard water deposits Replace if valve is blocked or does not operate properly NOTE TAKE CAUTION WHEN OPERATING DRAIN VALVE DRAINED WATER MAY PRESENT A SCALD RISK Fina...

Страница 16: ...ge Air Not Enough Hot Water Zone valve restriction 1 full bore replace zone valve Circulator arrow reversed Reverse circulator Tank temperature too low Raise tank temperature Boiler temperature too low Raise boiler temperature Boiler sized too small Check sizing chart Tank sized too small Demand flow rate too high Install mixing valve Raise tank temperature Air trap in loop Purge air Install flow ...

Страница 17: ... Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer IMPORTANT Customer Please only sign after the qualified installer service technician has fully reviewed the installation safety proper operation and maintenance of the system If the system has any problems please call the qualified installer service techn...

Страница 18: ...r future reference TO THE OWNER This water heater should be inspected annually by a Qualified Service Agency X8033 R16 10 19 1M Printed in U S A PB HEAT LLC 131 S CHURCH STREET BALLY PA 19503 2019 PB Heat LLC All rights reserved The surfaces of these products contacted by potable consumable water contain less than 0 25 lead by weight as required by the Safe Drinking Water Act Section 1417 ...

Отзывы: