1. Fill the water heater by opening the cold water shut-off valve. 

Purge air from the system by opening a hot water outlet at a fixture 

in a kitchen or bathroom. When water flows freely from the outlet, the 

system is purged.

Part 5 - Start-Up and Operation

When filling the water heater, open a hot water tap to release air in 

the tank and piping to ensure proper water heater operation. Failure 

to ensure the water heater is full before turning on the system will 

result in damage to the water heater, and could result in property 

damage. Such damages ARE NOT covered by warranty.

2. Check the system for leaks.

Fix any leaks before continuing the installation. Failure to do so 

could result in property damage or personal injury.

Risk of scald injury increases as you increase water temperature.

Figure 13 - Sealing the Water Heater for Sanitary Applications

3. After ensuring there are no leaks within the system, flush the system 

to clear any soldering residue. Many soldering fluxes contain Zinc 

Chloride, which can corrode stainless steel.
Draw at least three times the volume of the water heater to properly 

flush the system.
4. Initiate a call for hot 

water. Ensure each 

zone valve or circulator 

operates only when its 

thermostat calls for heat. 

Purge each zone of air to 

ensure proper operation.
5. Set the water heater to 

the desired temperature. 

Boiler high limit should 

be set at least 20

o

higher than the heater 

temperature. Set the low 

limit of the boiler control 

at the minimum setting 

- this will call the burner 

on only to satisfy the tank 

control.
A water heater 

temperature setting of 

120

o

F is recommended. 

However, a lower 

temperature setting may 

be required to comply 

with local and state codes 

for normal operation. 

The differential should 

be set at 10 to 15

o

F.  Installation conditions may require a higher or 

lower temperature setting. A mixing valve in conjunction with a high 

temperature setting may be used for high demand applications (spas, 

hot tubs, whirlpools).
6. When the system is completely flushed, purged of air, and the 

temperature is set, turn on the boiler. Observe operation. Ensure the 

boiler shuts down after the indirect water heater set point is satisfied.

Repair Parts

Thermostat:

Honeywell L4080B

Stock code: 51292

Temperature and Pressure Relief Valve:

PP-40: Watts 100XL-8 (100 Mbh, 8” element)

PP-60/80/120: Watts 40XL-8 (200 Mbh, 8” element)

Содержание Partner PP-120

Страница 1: ...Partner Water Heater Peerless Indirect Fired Installation Operation Maintenance Manual ...

Страница 2: ...may be the AHJ NOTE The manufacturer reserves the right to modify product technical specifications and components without prior notice For the Installer This water heater must be installed by qualified and licensed personnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements Installations Must Comply With Local sta...

Страница 3: ...nents of the water heater as well as plastic vent pipe materials Such damages ARE NOT covered by warranty It is recommended to keep a minimum clearance of 8 from high heat sources Observe heat source manufacturer instructions as well as local state provincial and national codes laws regulations and ordinances when installing this water heater and related components near high heat sources C Freeze ...

Страница 4: ...alized to the piping system as possible Also locate the water heater and domestic water piping where it will not be exposed to freezing temperatures All piping should be insulated Additionally place the water heater so that the drain controls and inlets outlets are easily accessible NOTE To save on heating costs and improve energy efficiency keep the distance between the boiler and water heater to...

Страница 5: ...ity Continuous Flow Example PP 40 314 75 X 45 280 25 MODEL HEAT EXCHANGER SURFACE VOLUME PRESS DROP FT TEST PRESS WORK PRESS 180O BOILER WATER FIRST HOUR RATINGS GAL 200O BOILER WATER FIRST HOUR RATINGS GAL 180O F BOILER BTU SIZE 200O F BOILER BTU SIZE RECOMMENDED FLOW RATE 140O F 115O F 140O F 115O F PP 30 LB 15 SQ FT 1 5 GAL 6 0 300 PSI 150 PSI 169 234 189 257 114 000 131 000 8 PP 40 20 SQ FT 2 ...

Страница 6: ...0 111 133 150 B COLD START 40 60 83 99 112 A B WARM START 60 90 126 150 169 PP 45 A COLD START 53 80 111 133 150 159 186 187 B COLD START 40 60 83 99 112 119 139 140 A B WARM START 60 90 126 150 170 181 211 212 PP 60 A COLD START 133 150 159 186 187 212 231 B COLD START 99 112 119 139 140 159 173 A B WARM START 153 173 183 214 215 244 266 PP 80 A COLD START 133 150 159 186 187 212 231 239 265 281 ...

Страница 7: ... Be sure that the arrow on the circulator is facing the correct flow direction See pressure drop sizing for circulator this manual On the tank the boiler return connects to the return side of the boiler The return s from heating loop s should have a flow check or swing check valve installed before the return pipe from the tank Steam boiler applications Use only with Peerless Series 63TM or Series ...

Страница 8: ...s used a thermal expansion tank must be installed on the cold water supply between the tank and valve If the tank is replacing a tankless coil in the boiler disconnect coil plumbing and use the cold inlet pipe and hot water outlet pipes for the water heater D Temperature and Pressure Relief Valve The temperature and pressure T P relief valve is provided on all models Install as detailed in the pip...

Страница 9: ...here is a back flow preventer or any other type of no return or check valve in the system a thermal expansion tank IS MANDATORY The expansion tank must be sized for the entire water volume of the hot water system A weeping relief valve indicates the need for an expansion tank See the Typical Expansion Tank example in the Piping section for details G Pressure Drop Sizing For Circulator The boiler c...

Страница 10: ...w preventer and the cold water inlet 3 All circulators should have an integral flow check 4 Drains and check valve between the heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve ...

Страница 11: ...w check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent sca...

Страница 12: ...quired 2 A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet 3 All circulators should have an integral flow check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The install...

Страница 13: ...s recommended that a disconnect switch be installed between the boiler control and the water heater Figure 11 Wiring with Circulators Figure 12 Wiring with Zone Valves CAUTION When wiring the water heater and controls be sure to label all wires to ease future maintenance Wiring errors can cause improper and dangerous operation CAUTION NOTE DO NOT attempt to remove the control well The control well...

Страница 14: ... the water heater to properly flush the system 4 Initiate a call for hot water Ensure each zone valve or circulator operates only when its thermostat calls for heat Purge each zone of air to ensure proper operation 5 Set the water heater to the desired temperature Boiler high limit should be set at least 20oF higher than the heater temperature Set the low limit of the boiler control at the minimum...

Страница 15: ... is blocked or does not operate properly NOTE TAKE CAUTION WHEN OPERATING RELIEF VALVE DISCHARGED WATER MAY PRESENT A SCALD RISK Drain Valve Open the drain valve and drain a few quarts of water from the bottom of the tank to flush any hard water deposits Replace if valve is blocked or does not operate properly NOTE TAKE CAUTION WHEN OPERATING DRAIN VALVE DRAINED WATER MAY PRESENT A SCALD RISK Fina...

Страница 16: ...ge Air Not Enough Hot Water Zone valve restriction 1 full bore replace zone valve Circulator arrow reversed Reverse circulator Tank temperature too low Raise tank temperature Boiler temperature too low Raise boiler temperature Boiler sized too small Check sizing chart Tank sized too small Demand flow rate too high Install mixing valve Raise tank temperature Air trap in loop Purge air Install flow ...

Страница 17: ... Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer IMPORTANT Customer Please only sign after the qualified installer service technician has fully reviewed the installation safety proper operation and maintenance of the system If the system has any problems please call the qualified installer service techn...

Страница 18: ...r future reference TO THE OWNER This water heater should be inspected annually by a Qualified Service Agency X8033 R16 10 19 1M Printed in U S A PB HEAT LLC 131 S CHURCH STREET BALLY PA 19503 2019 PB Heat LLC All rights reserved The surfaces of these products contacted by potable consumable water contain less than 0 25 lead by weight as required by the Safe Drinking Water Act Section 1417 ...

Отзывы: