
Figure 4. Single Phase Wiring Diagram, C84A or
C93A Float Controls
NOTES:
1. Float Control must be wired in series with P1 & P2 and set to open circuit
when liquid level drops no lower than minimums shown on pump dimension
drawings.
2. Connect to A.C. supply line of voltage required. All wiring must be in
accordance with N.E.C. and/or local electrical codes.
3. Connect terminals
7 & 8
to remote alarm device (by others). Terminals
5 & 6
can be wired in series with float control to shut pump down if moisture is
detected.
4. Combined length of control circuit leads and control wiring to moisture
detection control must not exceed 100 feet.
5. Motors are furnished by factory with motor leads connected for specifies
voltage. If it is necessary for voltage to be changed in the field reconnect
terminals in motor terminal head in accordance with conversion
diagrams. Splices must be watertight (see motor instructions for further
information).
6. The motor warranty is valid only if moisture detection and thermal protection
system is connected and operable. Failure to utilize these voids warranty.
7. Connections to motor starter and disconnect switch are typical only. All
equipment furnished by others is to be in accordance with N.E.C. and/or
local electrical codes.
Figure 5. Three Phase Wiring Diagram, C84A or
C93A Float Controls
8
2899213
Содержание UWLLB3
Страница 6: ...Figure 3 Installation Dimensions 6 2899213 ...
Страница 11: ...Figure 9 Type UW Sewage Pump 11 2899213 ...