61
ENGLISH |
MODE5 CONFIG
COSFI REC:ON
• Enable (
ON
) or disable (
OFF
) automatic COSFI recovery when it is below
COSFI MIN (dry running)
• With COSFI RECOVERY, the control panel attempts to automatically recover
an electric pump that is in the dry running alarm state (COSFI read < COSFI
minimum)
MODE5 CONFIG
REC TIME:2m
• Recovery time for automatic deactivation of the dry running alarm.
• The control panel attempts automatic recovery after the set time, and then
doubles it on each subsequent cycle (e.g. 2 min, 4 min, 8 min ...), up to the
maximum recovery time (see the next parameter).
Default
2 min
Range
0-10 min
Step
1 min
MODE5 CONFIG
MAX REC T:60m
• Maximum recovery time for automatic deactivation of the dry running
alarm.
• The control panel attempts automatic recovery up to the set maximum val-
ue (e.g. every 60 min).
Default
60 min
Range
0-120 min
Step
1 min
Configuring MODE 6
SELECT
MODE CONFIG
• Press the
key to confirm the choice and enter the submenu.
9
MODE CONFIG
MODE:1
• Press the
key to enter the submenu and change mode.
6
9
MODE:6
• Press the
or
key to select mode 6
(from modes 1 to 6)
• Press the
key to confirm the choice of MODE:6
• Press the
key to continue with the configuration
9
MODE CONFIG
SETUP
• Press the
key to enter the mode 6 configuration submenu
9
MODE6 CONFIG
RUN:EMPTYING
• Set the operating mode:
– EMPTYING (empty the collection tank)
– FILLING (fill the tank)
– PRESSUR. (pressurise the domestic/industrial system)
MODE6 CONFIG
SENS L:OFF
• Enable (
ON
) or disable (
OFF
) the capacitive level sensors
MODE6 CONFIG
IN1:RUN
• Set the first input (IN1):
– STOP (input enabled to stop the first pump)
– RUN (input enabled to start the first pump)
– OFF (input disabled)
Continued