Page 26
NORMAL
OPERATION
IS THE PRESSURE BELOW THE
LOWER SET POINT?
YES
START
COMPRESSOR
WITH 'AVAILABLE
COMPRESSOR
FLAG'
START 'FORCED ON
SEQUENCE'
IS THE PRESSURE ABOVE THE
LOWER SET POINT?
NO
YES
NO
IS '5 MIN AT PRESSURE
FLAG' SET?
YES
NO
OPEN OFFLOADER
FOR 15 SECS
IS THE PRESSURE BELOW THE
LOWER SET POINT?
YES
NO
CLOSE
OFFLOADER
START 'NORMAL
OPERATION'
CLOSE
OFFLOADER
START
'COMPRESSOR
SHUT DOWN
SEQUENCE'
START 'START UP
SEQUENCE'
START '1 MIN AT
PRESSURE
SEQUENCE'
ARE '1 MIN PRESSURE FLAG',
'FORCED ON FLAG' & 'FORCED OFF
FLAG'
ALL
SET?
NO
YES
START
'COMPRESSOR
SHUT DOWN
SEQUENCE' FOR
COMPRESSOR
WITH 'AVAILABLE
COMPRESSOR
FLAG'
START 'NORMAL
OPERATION'
SWITCH 'AVAILABLE
COMPRESSOR
FLAG' TO OTHER
COMPRESSOR
IS 'FORCED ON FLAG' SET?
NO
YES
START '5 MINS AT
PRESSURE
SEQUENCE'
IS THE PRESSURE BELOW THE
LOWER SET POINT?
NO
HALT '5 MINS AT
PRESSURE
SEQUENCE'
YES