PowerWave 2 Bus System BCMS Setup and Operation
Cntl Nr: PM375107-002
10
Figure 2 Attach Modbus RTU Cable to Accumulator
Attach Modbus RTU Cable to the Accumulator PCB in the Comm Box
1.
Open the
Comm Box door
.
Unscrew the captive screws on
the Comm Box door and open
the door.
The door swings up to 180°.
2.
Locate the
Accumulator PCB
in
the Comm Box.
The Accumulator PCB is in the
bottom right corner of the Comm
Box.
Note: If Modbus TCP/IP or SNMP
is a selected option, a protocol
converter is installed as shown.
When either option is selected,
you cannot connect a Modbus
RTU cable to the Accumulator
PCB because the protocol
converters and the Modbus RTU
cable use the same
J5
connection
on the PCB.
3.
Run your network Modbus RTU
cable through the
Modbus RTU
cable entry hole
on the bottom
of the Comm Box.
Accumulator PCB
Optional Protocol Converter for
Modbus TCP/IP or SNMP is installed here.