Device Chain: Readings ___________________________________________________________
Ctrl Nr: PM375103 Revision: 003
27
5
Device Chain: Readings
Each device in the Monitor’s device chain has a
READINGS
screen chain, providing power
monitoring information.
•
Select (touch)
DEVICES
to see the device list and then
READINGS
.
•
Use
PREVIOUS/NEXT
to step through the screen chain.
5.1
PDU Device Readings
READINGS
from the PDU are power measurements at input to and output from the PDU transformer
(Figure 22).
Select (touch)
PDU device name
in the device list. Device
name turns blue when selected and device name displays
in header.
PDU
is the default generic device name.
Users can change the device name in
SETTINGS
.
Touch
READINGS
to see PDU power monitoring data.
INPUT
to the PDU transformer:
Voltage
: AB BC CA
THD
(total harmonic distortion):
AB BC CA
Frequency
: in Hz
Current
A B C (optional)
THD
A B C (optional)
Ground Current
OUTPUT
from the PDU transformer:
Instantaneous measurements:
Voltage
: AB BC CA AN BN CN
ABC(N) phase readings and totals:
Current
KW
KVA
KVAR
PF
Cumulative Measurement:
KWH
Touch
Clear
to set KWH to 0.
Figure 22 Readings: PDU