PDi Communication Systems, Inc.   40 Greenwood Lane   Springboro, Ohio 45066 USA   PH 1-800-628-9870  FX 937-743-5664  

 

 

 

 

 

 

  

FAULT 

CORRECTIVE ACTION 

TV picture noisy 
on all TVs. 

1.  At the central power supply, remove the 

input RF cable and check the signal level.  
The central power supply requires a 
minimum RF level of +20 dbmv for a 
healthy RF signal level at each TV. 
 

2.  At the central power supply, remove the 

output coax and check the signal level at 
each “F” output.  With a know RF input 
signal level to the central power supply “RF 
IN”, check for an insertion loss of 14 dbmv 
at each “F” output.  Any insertion loss 
greater than 14 dbmv indicates a fault.  
Remove from service and replace with a 
know good working central power supply.  

 

 

TV picture noisy 
on one TV.  

1.  At the TV, open the cover on the support 

arm.  Slide the rubber boot and expose the 
“F” barrel connection.  Disconnect the “arm 
side” coax and verify an RF signal level 
equal to or greater than 0 dbmv.  Caution 
AC voltage is present on the coax during 
this measurement.  If the signal level is less 
than specified check for coax wiring faults. 
   

2.  If the signal level is greater than 0 dbmv, 

replace the “F-61” barrel connector and 
check the TV’s picture. 
 

3. 

If the TV’s picture is noisy, replace the TV. 

 