Summing Operation & Maintenance Manual
Paragon Controls Incorporated
45
Revision Level 002
9.8.2. Voltage Output Level Select
The Voltage Output Level Selection Menu allows the user to select either 0-5VDC or 0-10VDC for the
Process Output voltage signal. See Section 4.4 for switch selection.
Tech Config
Password: 1000
Controller Parameters
Output Selection
Volt Out 5/10vdc
Area Factor
Volt Out 5/10vdc
Transducer Cal.
Min Calibration
(0-5V / 0-10V)
Ext. Flow Source
Span Calibration
Ext. Flow Span
Return to Menu
(05) Volt
Altitude
Process Output Menu
Temp. Output Menu
9.8.3. Minimum
Calibration
The Minimum Calibration Menu allows the user to make output zero adjustments. Monitor the output
and with each Up or Down button depression, the output will increase or decrease by 0.01VDC or
0.01mA depending on output selection.
Tech Config
Password: 1000
Controller Parameters
Output Selection
Use Up/Down
Area Factor
Volt Out 5/10vdc
Buttons
Transducer Cal.
Min Calibration
To Adjust Output
Ext. Flow Source
Span Calibration
(Press Enter)
Ext. Flow Span
Return to Menu
Altitude
Process Output Menu
Temp. Output Menu