Summing Operation & Maintenance Manual
Paragon Controls Incorporated
21
Revision Level 002
8. FIELD SETUP MENUS
(To enter the Field Setup Menu, depress and hold the Enter button for 5 seconds)
8.1. OPERATING
RANGE
The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range.
Field Setup
Menu
Operating Range
Operating Range
Zero Calibration
(6,932-12,656)
Eng. Units
(ACFM)
Lockdown
Flow Correction
Enter Value
Auto Zero
(010,000)
Temp. Comp.
Meas. Fl. Disp. Fltr
8.2. ZERO
PRESSURE
CALIBRATION
The Zero Calibration Menu allows the user to perform a zero transducer calibration to eliminate any
transducer zero shift.
(Caution: Before performing a zero calibration, disconnect the Total (High) and Static (Low)
pressure connections, perform a zero calibration and then reconnect the Total and Static pressure
connections).
Field
Setup
Menu
Operating Range
Input Value
CPU
Taking
Zero Calibration
(0.000) in. W.C.
Samples
Eng. Units
Lockdown
(Press Enter)
(Please Wait)
Flow Correction
Auto Zero
Temp.
Comp.
Meas. Fl. Disp. Fltr