MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
34
Revision Level 002
9. TECH CONFIGURATION MENUS
To enter the Tech Configuration Menu, press the UP/DOWN buttons simultaneously, enter
password number 1000 and press the Enter button.
9.1. CONTROLLER
PARAMETERS
9.1.1. Controller
Display
The Controller Display Menu allows the user to turn the controller function and controller display data
ON and OFF.
Tech.
Config.
Password:
1000
Controller Parameters
Controller Display
Controller Display
Area Factor
Tuning Parameter
Transducer
Cal. Action
(ON
/
OFF)
Ext. Flow Source
Cont. Setpoint
Ext. Flow Span
Output Start
(ON)
Altitude
Alarm
ON/OFF
Process Output Menu
Output Override
Temp.
Output
Menu
9.1.2. Tuning
Parameters
The Tuning Parameters Menu allows the user to tune the controller parameters to match the system
dynamics. The Proportional Band value can be entered as a percent value from 1 to 100%. Reset and
Inverse Derivative values will range from 0 to 300 seconds. Decreasing any of the three tuning
parameter values will cause the controller’s response to speed up. Default values will be Proportional
Band = 10%, Reset (Integrator Time) = 70 seconds and Inverse Derivative = 60 seconds.
Tech. Config.
Password: 1000
Controller Parameters
Controller Display
Tuning Parameters
Tuning Parameters
Area Factor
Tuning Parameter
Proportional Band
Proportional Band
Transducer Cal.
Action
Integrator Time
(010)
Ext. Flow Source
Cont. Setpoint
1/Derivative
Integrator Time
Ext. Flow Span
Output Start
(070)
Altitude
Alarm
ON/OFF
1/Derivative
Process Output Menu
Output Override
(060)
Temp. Output Menu