background image

Manual 

10 

 If 

“ESC” is indicated in the LC display of the remote display unit, you must adopt protective 

measures before entering the room where the sensor unit has been installed. 

Check the room’s 

ventilation and find out whether there is a CO

leak, wearing protective clothing / equipment. As soon as 

the CO

concentration in the ambient air has reached the second alarm thr

eshold, “ESC” appears in the 

display of the sensor unit as well as in the display of the remote display unit. The yellow LED “FLT” 
(standing for fault) flashes. Use the 

„ReFactSet“ function to reset the gas leak detector to factory defaults. 

The “ESC” indication should now disappear. Alternatively, you can remove the mains adaptor and plug it 
back into the socket. 
 
The remote display unit shows the readings and safety warnings of the sensor unit. It is connected to the 
sensor unit via a communication cable (cable length: max. 8 m). the remote display unit should not be 
placed in the same room as the sensor unit. It should be mounted in a way which provides high visibility 
and an easy reading of the CO

2

 concentration before entering the room where the sensor unit is located. 

The connection between both devices can be checked by using the “DIAG” function which is described in 
the further course of this manual. To reset the PCE-

WMM 50, the “Reset” key on the sensor unit is used.  

 

4  Getting started 

4.1  Preparation 

 When taking the PCE-WMM 50 out of its box, remove the protective rubber cap from the gas input 

(M) and put it to position L. During operation, make sure that the gas input (M) is not blocked at any time. 
 

 

power supply (ventilation) 

fan 

mains adaptor 

sensor unit 

gas bottles 

6 / 7 

remote display unit 

door 

 
Open the box and take out the sensor unit, the remote display unit and all accessory parts. 
 
Mount the sensor unit in the area which you want to monitor. It should be placed 0.45 m above the 
ground and as near as possible to the pipes and valves. Mount the wall mounting to a wall by using 4 
screws. The sensor unit can be placed in the mounting afterwards. Make sure that the sensor unit sits in 
the mounting tightly. 
 
Mount the remote display unit outside of the room to be monitored. Mount the wall mounting to the wall by 
using screws. The display unit can be placed in the mounting afterwards. Make sure the display unit sits 
in the mounting tightly. 

Содержание PCE-WMM 50

Страница 1: ...iter FL 33458 USA From outside US 1 Tel 561 320 9162 Fax 561 320 9176 info pce americas com www pce instruments com english www pce instruments com PCE Instruments UK Ltd Units 12 13 Southpoint Busine...

Страница 2: ...n 6 3 1 Device 6 3 2 Display 9 4 Getting started 10 4 1 Preparation 10 4 2 Power connection 11 5 Operation 12 5 1 Further measuring functions 12 5 2 Settings 13 6 Maintenance 14 6 1 Repair cleaning an...

Страница 3: ...tightly with the elastic plug lock so that it can only be removed using mechanical tools If you wish to connect a fan to the potential free contacts of the sensor unit make sure that the fan has its o...

Страница 4: ...250 V AC max 2 A Alarm thresholds Alarm 1 0 5 1 1 5 2 Alarm 2 1 5 2 2 5 3 3 5 4 Menu items Function test of connection between sensor unit and remote display unit calibration switching between C and F...

Страница 5: ...nal digital display to measure temperature in C and F LEDs for operation alarms 1 2 and monitoring of voltage supply Display elements Function test Reset menu selection Enter shifting between C and F...

Страница 6: ...tential free contact which can for instance activate a fan which reduces the increased CO2 concentration in the room concerned Sensor unit A LC display B Yellow LED error indication C Red LED 2 AL2 D...

Страница 7: ...between sensor unit and remote display unit CAL Calibration of gas detector ReFactSet Reset to factory default settings You can set two alarm thresholds AL1 AL2 1 Alarm threshold Selectable threshold...

Страница 8: ...te display unit O Green LED power supply P Red LED 1 AL1 Q Red LED 2 AL2 R Yellow LED error indication S LC display T Enter key U Mode key V RJ45 connection Output W RJ45 connection for sensor unit In...

Страница 9: ...d LED 1 flashes the buzzer sounds and the potential free contact closes if the red and blue cables are connected or closes if the white and blue cables are connected Second alarm threshold If the CO2...

Страница 10: ...2 concentration before entering the room where the sensor unit is located The connection between both devices can be checked by using the DIAG function which is described in the further course of this...

Страница 11: ...blue cables are connected the contact closes B blue cable R red cable W white cable 1 power connection fan 2 fan 4 2 Power connection Connect the mains adaptor to the wall socket Attach the elastic sa...

Страница 12: ...larms are triggered early 5 1 Further measuring functions DIAG function The communication between the sensor unit and the remote display unit should be checked on a regular basis by using the DIAG fun...

Страница 13: ...actory default settings are restored after the confirmation 5 2 Settings Lock unlock The gas detector has an automatic lock function to prevent the settings from being changed unintentionally If you w...

Страница 14: ...e key The following options are available 1 5 2 2 5 3 3 5 4 Select the desired option and press the Enter key to confirm 6 Maintenance 6 1 Repair cleaning and maintenance Repairing Do not try to repai...

Страница 15: ...ubber cap on the gas input M to prevent water from getting into the device Maintenance The communication between the sensor unit and the remote display unit should be checked on a regular basis by usi...

Страница 16: ...f this does not help please contact our customer support Er7 Internal data transfer error Er7 flashing LED FLT flashing buzzer makes noise Er7 flashing LED FLT flashing buzzer makes noise Unplug the p...

Страница 17: ...use them or give them to a recycling company which disposes of the devices in line with law If you have any questions please contact PCE Instruments 9 Contact If you have any questions about our rang...

Отзывы: