If the menu item Delete function is confi rmed by pressing button
➄
, a safety
enquiry appears. The setting can be changed between Yes and No by pressing
buttons
❷
and
❹
. If Yes has been selected and confi rmed by pressing button
➄
, the function is deleted and available under Add new function... again. The
corresponding relays are available again.
Bypass
The Bypass function can be used for avoiding an energy loss from the store direct-
ly after loading has started. The still cold heat transfer medium in the pipework is
diverted through a bypass past the store. Once the pipe is warm enough, the store
can be loaded. The switch-on conditions can be adjusted individually.
Solar / Opt. functions / Add new function... / Bypass
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Collector
Collector fi eld
system dependent
system
dependent
Relay
Bypass relay
system dependent
system
dependent
Variant
Variant (pump or valve logic) pump, valve
pump
Inverted
Valve logic inversion
Yes, No
No
Sensor
Bypass sensor
system dependent
system
dependent
D
Ton
Switch-on temperature
difference
1.0 … 20.0 K
6.0 K
D
Toff
Switch-off temperature
difference
0.5 … 19.5 K
4.0 K
Funct.
Activation / Deactivation
Activated, Deactivated Activated