5 Scope of delivery [specialist]
2020/04
993x083x-mub-en – V04
13
1.
Take off the thermometer handles (A-2,
F-2) and remove the insulating front shell
of the HeatBloC
®
.
2.
Unscrew the nuts on the lower
connections of the HeatBloC
®
and take out the sealing rings.
If a PAW modular distribution manifold
or transition connection is used:
3.
Put the two nuts over the flanges.
4.
Insert the sealing rings into the nuts.
5.
Put the HeatBloC
®
onto the two nuts.
6.
Tighten the nuts.
Make sure that the nuts do not get
jammed and that the sealing rings
do not slip.
7.
Connect the HeatBloC
®
to the installation
by using the pipes. The installation to
the piping must be carried out without
any tension.
8.
Connect the pump.
9.
Carry out a pressure test and
check all thread connections.
10.
Mount the insulating front shell and
the thermometer handles (A-2, F-2).
5
Scope of delivery [specialist]
NOTICE
Complaints and requests/orders of spare parts will only be processed with information on
the serial number! The serial number is placed on the return pipe of the heating circuit.