6 Technical data
2018/06
99423x063MGK7-mub-en
–
V01
21
C34
DN 25 (1")
DN 32 (1¼")
Hydraulics
Max. pressure
6 bars
Minimum temperature*
-
10 °C, flowable / conveyable
Max. temperature
110 °C
K
VS
value [m
3
/h]
6.0
10.1
* In general, the cooling water temperature must not fall below 15 -
16 °C in order to minimise
the formation of condensation water (shortfall of the dew point temperature) at the system
components. The diagram on page 22 allows a rough estimation to know if the dew point
temperature is undercut.
6.1
Pressure drop and pump characteristic curve C34 - DN 25 / DN 32
P
ressu
re
[m
w
c]
P
ressu
re
[kP
a]
Flow rate [l/h]