28
For Vertical Vent Termination - PVC, CPVC or PP Material
Roof Flashing
Storm Collar
Roof
Flashing
Storm
Collar
≥ 3 ft Min.
≥ 3 ft Min.
12 in. over
maximum
snow level
12 in. over
maximum
snow level
Support
Hanger
Strap
2 in. pipe*
3 in. pipe
2 in. × 3 in. Increaser
coupling
• A short horizontal section is
required to prevent debris
from falling into the water
heater.
• When using a horizontal
section, slope the horizontal
vent 1/4 in. upwards for
every 12 in. (305 mm)
toward the termination to
drain condensate.
When the vent
penetrates a floor or
ceiling and is not
running in a fire rated
shaft, a firestop and
support is required.
*
About the termination
• When choosing intake and exhaust terminations, you must use the same type of elbow (i.e.
both 90° elbows).
This will help with proper combustion by putting both terminations in the same pressure zone.
• Insert Bird Screen in End of 90° Elbow.
Bird Screen is not supplied with water heater, order separately.
• To prevent excessive condensation formation, only the vent termination should be located on
the exterior of the building.
When the vent termination
is located not less than 8 ft
(2.4 m) from a vertical wall
or similar obstruction,
terminate above the roof at
least 2 ft (0.6 m), but not
more than 6 ft (1.87 m), in
accordance with the
National Fuel Gas Code
ANSI Z223.1 / NFPA 54 or
Natural Gas and Propane
Installation Code CSA
B149.1.
Provide vertical
support every 3 ft
(0.9 m) or as
required by the vent
pipe manufacturer's
instructions.
Support
Firestop
2 in. × 3 in. Increaser couplings are
required when using 3 in. (75 mm)
pipe.
• The combustion
air intake of any
appliance
• Any other building
opening
Firestop
Firestop
*
*
Firestop
* The length of the pipe
between the Increaser
couplings and the Exhaust
and Intake Flue of the
Water Heater should be up
to 6 in. (152 mm).
Exhaust
2 in. (50 mm)
or
3 in. (75 mm)
Intake
2 in. (50 mm)
or
3 in. (75 mm)
6.4.3 Vertical Vent Termination
Venting the Water Heater
Содержание GQ-C3260WX-FF PB US
Страница 68: ......