20 System Functions
EN
P75
Restore factory settings
• Press
"
"
for 5 seconds
on the membrane keyboard to per-
form a complete reset.
This action will restore the original
factory settings.
0
1
0
Note:
After a complete reset of the santos a message
prompts you to re-enter the settings for "nL / HL"
(see P56) and "Li / Re" (see P57).
After a complete reset, all settings in menus P2 and
P3 and the existing controls P5 and P6 have to be
set again.
If the santos is equipped with a frost protection de-
vice it must be re-enabled in menu P51, because
following a complete reset the standard setting is
"disabled".
P76
Santos self-test
0
1
0
Note:
The santos switches to the highest level immediately when the self-
test is activated. In addition, the bypass valve also opens and closes
immediately after the self-test is activated. If this self-test is com-
pleted without malfunctions, the valve of the frost protection device
(if installed) then opens and closes.
P77
Reset dirty filter counter
0
1
0
Note:
This control command resets the counter that triggers the filter warn-
ing message. This allows the filter to be cleaned or replaced before
the filter warning message is displayed.
Menu P8
¨
Analogue control settings
Values (malfunction) information
Sub-menu
Description
Minimum
Maximum
Standard
810
Analogue input 1
0=absent 1=present
0
1
0
811
0=Open loop 1 =Closed loop
(analogue input 1)
0
1
0
812
Setpoint analogue input 1
(closed loop)
0
100
50
813
Min. setting analogue
input 1
0
99
0
814
Highest setting analogue
input 1
0
100
100
815
0=positive analogue input 1
1=negative setting analogue
input 1
0
1
0
816
Read out analogue input 1
0
100
-
820
Analogue input 2
0=absent 1=present
0
1
0
821
0=Open loop 1 =Closed loop
(analogue input 2)
0
1
0
822
Setpoint analogue input 2
(closed loop)
0
100
50