16 System Functions
EN
Ensure that the water seal connected to the
domestic wastewater system is always filled
with water.
Ensure that the hose end terminates at least
60 mm below the water level. This will pre-
vent the santos from drawing in air.
Do not connect the condensate drain direct-
ly to the sewage drain system (for example
flowing freely into funnel with condensation
drain at the sewage system)
3.7 Commissioning the santos
The santos can be put into operation after instal-
lation.
It is possible to carry out the commissioning proce-
dures utilising P menus on the digital control panel.
These P menus allow various settings (in particular
for ventilation control) to be selected for the san-
tos. An overview of the available P menus is given
below:
Menu
Possible options
P1
View status (from menu P2)
P2
Set time delay values
P3
Set ventilation levels
P4
View temperatures
P5
Set additional control functions
P6
Set additional control functions
P7
Read and reset malfunctions (and sys-
tem information)
P8
Set 0-10 V inputs
P9
View status (from menu P5)
The P menus P1, P2 and P9 are user accessible
and serve mainly for viewing statuses and setting
time delays. The remaining P menus P3 to P8 are
reserved
exclusively
for the installer.
The bypass valve will not move in the first
4 minutes following a drop in voltage, if the
setting mode is not activated.
3.7.1 Display on unit
Call up menu
Up
OK
Down
Supply air off
Exhaust air and
supply air on
(LED green)
(LED green)
Comfort temperature
Display read-out:
Ventilation level absent
Ventilation level low
Ventilation level medium
Ventilation level high
Menu display
Malfunction code (flashes)
Bypass
Accessing menus
Se-
quence
Operating
keys
Display
Description
1
MENU
P2
Time delay values
2
s
+
▼
(3 seconds)
P3
Press keys
simultaneously
3
s
P4
Temperatures
4
s
P5
Control settings
5
s
P6
Control settings
6
s
P7
Malfunction / reset /
Self-test
7
s
P8
0 - 10 V inputs
8
s
P9
Status display
Settings example
Set the power of the supply air fan at
THE MEDIUM LEVEL to 40%
Se-
quence
Operating
keys
Display
Description
1
MENU
P2
Time delay values
2
s
+
▼
(3 seconds)
P3
Press keys
simultaneously
3
OK
P30
Exhaust air fan
Level A
4
s
(6x)
P36
Select P36
5
OK
50
Current setting
6
▼
(10 x or
hold down)
40
Select 40
7
OK
P35
Current value is 40
8
MENU
P3
9
MENU
1
Fan steps
Some P menus (for example P1 and P9) are
view only.
End (read) menu
• Press "MENU" (instead of "OK").
The display cannot be used to set the san-
tos ventilation levels. Arrow keys are used
only to determine additional programmes.
1
A
2
3
X X
X X
•
1
A
2
3
X X
X X
•
1
A
2
3
X X
X X
•
1
A
2
3
X X
X X
•
1
A
2
3
X X
X X
•
OK
MENU
·
·
·
OK
MENU
·
·
·
OK
MENU
·
·
·
OK
MENU
·
·
·
OK
MENU
·
·
·
1
A
2
3
X X
X X
•
1
A
2
3
X X
X X
•