Messages, errors and error handling
42
The following plain text displays of the error message are visualised:
Message on display
Possible cause
Control / Action
Error sensor 1
Sensor break or short circuit
temperature sensor
Version LEFT T1
Version RIGHT T3
Check or replace sensor
Error sensor 2
Sensor break or short circuit
temperature sensor
Version LEFT T2
Version RIGHT T4
Check or replace sensor
Error sensor 3
Sensor break or short circuit
temperature sensor
Version LEFT T3
Version RIGHT T1
Check or replace sensor
Error sensor 4
Sensor break or short circuit
temperature sensor
Version LEFT T4
Version RIGHT T2
Check or replace sensor
Supply air temperature too low
Minimum supply air temperature
< setpoint;
Supply air temperature >
se 1 K
Intake air temperature too low
Current intake air temperature <
setpoint; longer than 30 minutes
Intake air temp > setpoint;
control after 1 h
Error fan 1 Hall
Version LEFT; supply fan speed
does not report
Version RIGHT, exhaust fan speed
does not report
manual adjustment of fan speed
Error fan 2 Hall
Version LEFT; exhaust fan speed
does not report
Version RIGHT, supply fan speed
does not report
manual adjustment of fan speed
Error by-pass
No end position, by-pass not
working
Test by-pass
BUS version incompatible
Software versions of the
components not compatible
Replace software versions
Too many devices connected
Too many components connected
to the BUS
Remove surplus components
Fan slave not connected
Lack of BUS-communication
Fan slave connected
Communication error
fan slave
Lack of BUS-communication
Check BUS-communication
Communication error
defroster
Lack of BUS-communication
Check BUS-communication
Communication error
heater battery
Lack of BUS-communication
Check BUS-communication
Communication error
flap of the geothermal heat exchanger
Lack of BUS-communication
Check BUS-communication
Communication error
general
Lack of BUS-communication
Disconnection from power
supply, then restart
Heating does not switch off
Error BUS-thermostat
Replace BUS-thermostat
General control unit error
Lack of BUS-communication with
control unit
Check BUS-communication
Tab. 5: Overview of messages, error visualisation and error treatment by means of the TFT touch panel
Содержание NOVUS 300
Страница 36: ...Replacement of the bypass motor 36 16 Mount all parts in reverse order 17 Re establish the mains connection ...
Страница 54: ...Appendix 54 Appendix Appendix 1 Circuit diagram NOVUS ...
Страница 55: ...Appendix 55 Appendix 2 Circuit diagram NOVUS with integrated defroster ...
Страница 56: ...Appendix 56 Appendix 3 Terminal scheme of through terminal X10 ...
Страница 57: ...Notes 57 Notes ...