![Paul NOVUS 300 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/paul/novus-300/novus-300_service-instructions-manual_4031647043.webp)
Error handling
43
11
Error handling
11.1
Error fan
Measure
230 V power supply
O.K.?
Yes
No
Yes
Replacement
of the fans
Replacement
fan slave
Hall signal
defective
Measure
1,7-10 V signal
O.K.?
Yes
No
Replacement of
the master
(assume settings)
O.K.
Check
fuse of fan at
master controller
(5 A M) O.K.?
No
Replace
the fuse
restart
Error fan
Hall 1 Hall 2
Disconnect the
power supply.
Fan wheel
damaged?
No
Restart
the device
Yes
WARNING!
Do not touch the board
for under 230 V power
supply live components!