background image

1410 RD CLEARANCES

29.

Aerion Range

METAL FRAME

Possible vent locations  

4 minimum vents required for airflow

H*= 395mm

Possible control box locations

CLEARANCE TO COMBUSTIBLES

Extra notes:

For timber frame installations the unit can be either floor mounted or mid mounted. However, for steel frame installations, the appliance must

be mid mounted.

Drawings above are for visual illustration purposes only. When the appliance is symmetrical you may choose to change 

the location of the control box or vents given you meet the minimum clearance requirements.

For installations where the control box is below the appliance – to the side of the cavity, you may choose to install the vent below the control 

box (not shown in the drawings) given the appliance is raised high enough to allow the minimum clearances and there is adequate space for

the vent.

The external façade/surrounding of the timber/steel frame should be constructed with 9mm Villa board (minimum).

* G dimension is only applicable if the control box is installed to the side of the cavity, inline or above from the bottom of the appliance. Similarly, H 

dimension is only applicable if the control box is installed either directly below the appliance or below the appliance – to the side of the cavity

Unit Dimensions

Metal Stud Frame

FOR METAL STUD FRAME, UNIT MUST BE IN PLACE

In mm

Clearance to the inside of the metal stud

Unit Height 

+50mm top

Unit Width +150mm 

either side to internal 

side of metal stud

Reduced Depth Clearance N/A for Tunnel Units

Metal Studs fixed to rear combustible wall.

25mm Steel Battens fixed to combustible wall +13mm Firestop Board

+50mm air gap to unit

H

W

D

A

B

C

850

1500

420

900

1800

N/A

270mm

A

B

C

Содержание Aerion Series

Страница 1: ...G1410 GF2R GF1410 GF3 G1410 RD G1410 T G1250 GF G1250 GF2L G1250 GF2R G1250 GF3 G 800 GF G 800 T G 650 GF ALTO GF ALTO T Version 3 28 02 22 Contents of manual may be updated without notice For the la...

Страница 2: ...and Maintenance instructions included Please read this manual before installing and using this space heater Leave this manual with the owner This space heater is approved for Natural Gas and Universal...

Страница 3: ...50 GF2R 6 G1250 GF3 6 G800 GF 7 G800 T 7 G650 GF 8 ALTO GF 8 ALTO T 9 Technical Data Summary Vue 1410 Range 10 Technical Data Summary Vue 1250 Range 11 Technical Data Summary Quadro 800 Range 12 Techn...

Страница 4: ...24 GF1410 GF3 26 G1410 RD 28 G1410 T 30 G1250 GF 32 G1250 GF2R 34 G1250 GF2L 36 G1250 GF3 38 G800 GF 40 G800 T 42 G650 GF 44 ALTO GF 46 ALTO T 48 Installation Instructions 50 Prohibited Area for Flue...

Страница 5: ...erion Range Alto Range 74 Quadro 800 Range 77 Quadro 650 Range 80 Main Burner Check 82 Remote Control Installation 84 Error Codes 90 Servicing 91 Trouble Shooting 92 Cleaning the Ceramics 97 Cleaning...

Страница 6: ...ions AS5601 1 2013 installation code for gas burning appliances and any other relevant statutory regulations Keep any flammable or combustible items curtains clothes furniture perfume etc at least 900...

Страница 7: ...PRODUCT DIMENSIONS 2 G1410 GF G1410 GF2L Aerion Range...

Страница 8: ...PRODUCT DIMENSIONS 3 G1410 GF2R GF1410 GF3 Aerion Range...

Страница 9: ...PRODUCT DIMENSIONS 4 G1410 RD G1410 T Aerion Range...

Страница 10: ...PRODUCT DIMENSIONS 5 G1250 GF GF1250 GF2L Aerion Range...

Страница 11: ...5 kg UNLESS OTHERWISE STATED DEBURR ALL SHARP EDGES RIPTION DATE DRAWN APPROVED REVISION 87 5 kg OT SCALE THIRD ANGLE PROJECTION UNLESS OTHERWISE STATED DEBURR ALL SHARP EDGES V DESCRIPTION DATE DRAW...

Страница 12: ...PRODUCT DIMENSIONS 7 G800 GF G800 T Aerion Range...

Страница 13: ...PRODUCT DIMENSIONS 8 G650 Aerion Range ALTO GF...

Страница 14: ...PRODUCT DIMENSIONS 9 ALTO T Aerion Range...

Страница 15: ...AS 10 Gas consumption high MJ hr 44 40 Gas consumption low MJ hr 30 35 Burner pressure high kPa 0 7 2 4 Burner pressure low kPa 0 38 1 96 Number of burners 3 Large burner 1 Small burner 2 Injector Br...

Страница 16: ...G 1250 Type Number AS 6 Gas consumption high MJ hr 34 Gas consumption low MJ hr 22 Burner pressure high kPa 0 6 Burner pressure low kPa 0 3 Number of burners 1 Large burner 1 Small burner Injector Br...

Страница 17: ...hr 31 0 28 0 Gas consumption low MJ hr 19 0 24 0 Burner pressure high kPa 0 7 2 4 Burner pressure low kPa 0 3 1 8 Number of burners 1 Large burner 1 Small burner Injector Bray type multiport 1 25 0 55...

Страница 18: ...sumption low MJ hr 16 13 Burner pressure high kPa 0 7 2 4 Burner pressure low kPa 0 3 0 8 Number of burners 1 Large burner 1 Small burner Injector Bray type multiport 1 10 0 55 Injector Bray type mult...

Страница 19: ...s consumption low MJ hr 35 32 Burner pressure high kPa 0 6 2 40 Burner pressure low kPa 0 4 1 52 Number of burners 2 Large burner 1 Small burner 1 Injector Bray type multiport 1 25 0 55 Injector Bray...

Страница 20: ...e situatedatthebottomof theenclosure Asthiswarmaircool itfallstowardthefloorwhereit sdrawnintotheinlet and the cycle repeats The room air inlets are part of the fireplace and cannot be blocked The amo...

Страница 21: ...VENT LOCATIONS AND SIZES Figure 1 3 Vent Size Figure 1 2 Vents NOTE Vent location minimum of 300mm down from the finished surface of the ceiling This 300mm istheoptimumloca tionoftheventrelativetoeffi...

Страница 22: ...17 Aerion Range UNIT TO TV CLEARANCES COMBUSTIBLE MANTLE Figure 1 4 Clearance from Unit to TV...

Страница 23: ...aranceforairflow Ifunitismounted onfloor controlpanelcanonlybelocatedtothesidewith theminimumclearanceof250mmtotheside Ifunderneath the unit base will need to at a desired height for the unit butalsoa...

Страница 24: ...ge CLADDING MATERIAL Note A gap of 4mm needs to be left between the villa board and the top part of the firebox 9mm Villa Board can be used as an alternative approved cladding material Figure 1 7 Clad...

Страница 25: ...ra notes Fortimberframeinstallationstheunitcanbeeitherfloormountedormidmounted However forsteelframeinstallations theappliancemust be mid mounted Drawings above are for visual illustration purposes on...

Страница 26: ...drawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Vill...

Страница 27: ...sadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideoft...

Страница 28: ...otshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed w...

Страница 29: ...adequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofth...

Страница 30: ...otshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed w...

Страница 31: ...notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed...

Страница 32: ...boxisbelowtheappliance tothesideofthecavity youmaychoosetoinstalltheventbelowthecontrol box notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacef...

Страница 33: ...ntrol box notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be co...

Страница 34: ...theapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimu...

Страница 35: ...arancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinsta...

Страница 36: ...entheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board mini...

Страница 37: ...andthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtot...

Страница 38: ...drawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Vill...

Страница 39: ...arancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinsta...

Страница 40: ...howninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with...

Страница 41: ...ancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstall...

Страница 42: ...ninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9m...

Страница 43: ...box notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be construc...

Страница 44: ...boxisbelowtheappliance tothesideofthecavity youmaychoosetoinstalltheventbelowthecontrol box notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacef...

Страница 45: ...clearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisin...

Страница 46: ...cefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofthecavity inl...

Страница 47: ...learancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisins...

Страница 48: ...efor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofthecavity inli...

Страница 49: ...mclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisi...

Страница 50: ...external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofthecavity inlineorabovefromthebo...

Страница 51: ...oughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicab...

Страница 52: ...for the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofthecavity inlin...

Страница 53: ...owthecontrol box notshowninthedrawings giventheapplianceisraisedhighenoughtoallowtheminimumclearancesandthereisadequatespacefor the vent The external fa ade surrounding of the timber steel frame shoul...

Страница 54: ...acefor the vent The external fa ade surrounding of the timber steel frame should be constructed with 9mm Villa board minimum Gdimensionisonlyapplicableifthecontrolboxisinstalledtothesideofthecavity in...

Страница 55: ...trol hatch to the transit bracket Before removingthelastscrew supportthe bottomofthecontrolhatch removethelastscrew andlaythecontrolhatchontheprotectivematerial toprotectagainstdamagetothepowdercoatin...

Страница 56: ...heater during the heating cycle is to have some flexibility to counter react to the expansion forces due to heat If the heater is secured to the surrounding frame the top of the heater may distort Bu...

Страница 57: ...panner or 10 mmnutsertremovetheboltsfromthebracketanddiscard Thetransitbracketafterremovingthesecuringboltscanbe pushed and accommodated under the base of the heater Fitment of the control hatch The c...

Страница 58: ...h the manufacturer sinstallationinstructions localgasfittingregulation municipalbuildingcodes electricalwiringregulationsandAS NZS 5601 1 Gas installations DO NOT INSTALL INTO A FIREPLACE The data lab...

Страница 59: ...tainthe desired clearance i e 250 mm or 50 mm The250mmmeasurementisforclearanceto combustiblematerials The50mmclearance isfornon combustiblematerialsinaccordance witha50mmclearancefromtherearofthe app...

Страница 60: ...STRUCTIONS Fitment adjustment of spacer brackets Thespacerbracketswhenadjustedmaintainagapbetweenthecarcassoftheheaterandanysurroundingmaterials Rear and side spacers are factory fitted refer below im...

Страница 61: ...emisbasedona concentricfluesystemwhichutilisesaninnerflueof104mmdiameterandanouterflueof170mmdiameter These concentric flues terminate outside of the property Theheatersinthismanualarebalancedflueunit...

Страница 62: ...to 150 MJ h input 500 300 Appliances over 150 MJ h input up to 200 MJ h input 1500 300 Appliances over 200 MJ h input up to 250 MJ h input 1500 500 Appliances over 250 MJ h input 1500 1500 Allfan assi...

Страница 63: ...the inner wall of the flue pipe Aerion Range Flue Components for Installing PAD series Gas Space Heaters Manufacturer DuraVent Flue Component Part Number Termination cap 46DVA VCH 900 mm flue length 4...

Страница 64: ...eofa90 elbowisequalto0 5metresinfluelength andthe45 bendisequalto0 25metresinfluelengthi e ifone90 elbowisusedthenthetotalmaximumfluelength is reduced to 5 5 metres Nomorethantwo 2 90 elbowsorfour 4 4...

Страница 65: ...5601 1 2013 Flue Length Calculations Maximum permissible run H 6 0m Maximum permissible run H V 6 0m Special consideration model G1410 H V 7 3m 1 Straight Vertical The maximum vertical distance is 6...

Страница 66: ...sleevearoundthescrew thisretains both the cover and the motor The Control valve is now ready to be fitted with the simple up down control system Simple Version Up and Lower control only Thisrequiresno...

Страница 67: ...lthebatteriesintothereceiverandthehandset thesewillbe4x1 5VAAalkalineand9VPP3alkalinerespec tively ThisReciever Handsetworksusingsoundwaves andassuchnodirectlineofsightisrequiredbetweenthereceiv er an...

Страница 68: ...chenablesanyof16pre selectedcodes Pressingtheswitchonthereceiveractivatesthe new code Thereceiverunitcanbehiddenawayunderorbehindthestove ensurethatthereceiverislocatedinanareathat hasatemperaturebelo...

Страница 69: ...ter front dimensionsof1323x375mmx4mmthick andoneoutersidepanels dimensionsof312x375 mm x 4 mm thick Wearingtheglovesprovidedremovetheglassfrom thebubblewrapandlocateinasafeplace Donot touch the glass...

Страница 70: ...te into thebottomsupportingchannel Replace the outer side trim in reverse order Step4 Formodelswiththeside glassremovetheouterrearside trim Gripthetrimandapplyan upwardmotiontodisengagethe securing ta...

Страница 71: ...innerfascia The bottom of the glass is now clear of the bottom supportingchannel Swingthebottomoftheglass outwardwithonehandholdingtheglasspadand theotherhandgrippingthebottomcentreedgeof the glass St...

Страница 72: ...m the top glass clamp Repeat the same with the bottomsupportingchannelropewithanupward motion Apply the glass suction pad provided to the centre of the glass and engage To protect the edgeoftheglassin...

Страница 73: ...age Toprotectthe edgeoftheglassinsertacoupleofsoftclothsinto the cavity before removing the glass panel With the glass supported and with an upward motionliftthetopedgeoftheglassupwardinto thetopfront...

Страница 74: ...tep 1 16 to place the burner media correctly in your firebox STEP 1 Log 5 Make sure the log tray is clear of any debrisorforeignmaterial Makesureyoukeep thepilotburnerareaclearofanyburnermedia STEP 2...

Страница 75: ...ET UP VUE 1410 RANGE STEP 7 Log 1 2 4 5 6 STEP 8 Log 1 2 4 5 6 STEP 9 Log 1 2 4 5 6 STEP 10 Log 1 2 3 4 5 6 STEP 11 Log 1 2 3 4 5 6 STEP 12 Log 1 2 3 4 5 6 STEP 13 Log 1 2 3 4 5 6 Aerion Range STEP 14...

Страница 76: ...PLACEMENT OF FIBRE EMBER STEP 1 Pull apart the fire embers into fine and thin pieces before placing over the burner STEP 2 Place fibre embers only on the burner cross lightingportsbyavoidingthemainslo...

Страница 77: ...1 6 to place the burner media correctly in your firebox STEP 1 Log 1 2 3 4 Make sure the log tray is clear ofanydebrisorforeignmaterial Makesureyou keep the pilot burner area clear of any burner media...

Страница 78: ...50 RANGE STEP 5 Place 5 embers on top of the BurnerTubes as shown Aerion Range STEP 6 EvenlyplacetheremainingEmbersaroundthe Grate area but avoiding the Burner tubes as shown ENSURE MEDIA DOES NOT RES...

Страница 79: ...ia box Follow Step 1 13 to place the burner media correctly in your firebox STEP 1 Log1 Makesurethelogtrayisclearofanydebrisor foreignmaterial Makesureyoukeepthepilotburner area clear of any burner me...

Страница 80: ...75 BURNER MEDIA SET UP ALTO RANGE STEP 5 Log 1 2 3 4 5 Aerion Range STEP 6 Log 1 2 3 4 5 6 STEP 7 Log 1 2 3 4 5 6 7 STEP 8 Log 1 2 3 4 5 6 7 8 STEP 9 Log 1 2 3 4 5 6 7 8 9...

Страница 81: ...EP 11 Log 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 STEP 12 Place4EmbersontopoftheFrontBurnerTube and2 on top of the Rear Burner Tube STEP 13 EvenlyplacetheremainingEmbersaroundtheGrate area but avoiding...

Страница 82: ...Follow Step 1 13 to place the burner media correctly in your firebox STEP 1 Log1 Makesurethelogtrayisclearofanydebrisor foreignmaterial Makesureyoukeepthepilotburner area clear of any burner media Aer...

Страница 83: ...IA SET UP QUADRO 800 RANGE STEP 6 Log 1 2 3 4 5 6 Aerion Range STEP 7 Log 1 2 3 4 5 6 7 STEP 8 Log 1 2 3 4 5 6 7 8 STEP 9 Log 1 2 3 4 5 6 7 8 9 STEP 10 Log 1 2 3 4 5 6 7 8 9 10 STEP 11 Log 1 2 3 4 5 6...

Страница 84: ...DRO 800 RANGE STEP 12 Place3EmbersontopoftheBurnerTubesasshown Aerion Range STEP 13 EvenlyplacetheremainingEmbersaroundtheGrate area but avoiding the Burner tubes as shown ENSURE MEDIA DOES NOT REST O...

Страница 85: ...media box Follow Step 1 10 to place the burner media correctly in your firebox STEP 1 Log1 Makesurethelogtrayisclearofanydebrisor foreignmaterial Makesureyoukeepthepilotburner area clear of any burner...

Страница 86: ...Range STEP 6 Log 1 2 3 4 5 6 STEP 7 Log 1 2 3 4 5 6 7 8 STEP 8 Place a single Ember on top of the Burner Tube as shown STEP 9 EvenlyplacetheremainingEmbersaroundtheGrate area but avoiding the Burner t...

Страница 87: ...bladed screw driver for access to HI fire out burner pressure adjustment 4 mm Allen key for access to LO fire pressure adjustment Pressure check with gas valve installed in the control hatch The Merti...

Страница 88: ...hlighted on page 10 14 dependant on model of this manual adjust the regulator Access to regulator refer below The regulator adjustment for low fire is located below the pressure test points identified...

Страница 89: ...LIGHT DIMMER OPERATION CIRCULATING FAN OPERATION AUXILIARY FEATURE 2ND BURNER FEATURE COUNTDOWN TIMER The Symax System uses the same easy to operate logic nd the symbol for the function you want and t...

Страница 90: ...d buttons simultaneously or wait C CH HI IL LD D P PR RO OO OF F 1 2 ON AM PM OFF ON To activate press and buttons simultaneously displayed and the handset is rendered inoperable except for the OFF fu...

Страница 91: ...FF Handset Press button to turn OFF NOTE A new ignition is possible after the OFF icon stops ashing F FL LA AM ME E H HE EI IG GH HT T A AD DJ JU US ST TM ME EN NT T 1 2 ON AM PM OFF Handset To increa...

Страница 92: ...to enter Eco Mode 1 2 ON AM PM OFF SETTING 1 Press button and hold until dis played temperature ashes 2 To adjust set temperature press or button 3 To con rm press button or wait P PR RO OG GR RA AM M...

Страница 93: ...Timer Unique ON and OFF times may be set for a single day of the week for multiple days of the week or for every day of the week Wait to nish setting A AU UX XI IL LI IA AR RY Y F FE EA AT TU UR RE E...

Страница 94: ...life RECEIVER Threeshortaudiblebeepswillsoundwhentheapplianceisontoindicatethatthebatteriesinthereceiverare getting low Whenthebatteriesgetverylowtheappliancewillbeturnedoffbytheremotecontrol Thiswill...

Страница 95: ...he line No spark F12 Contact service Motorturnstopilotlightposition Receiver temperature above 60 F13 Contact service Motorturnstopilotlightposition Receiver temperature above 60 F14 Contact service 5...

Страница 96: ...Window Panel 5 Carefully remove the Ceramic components including Embers or Gravels 6 Use a Vacuum cleaner to clean the top of the burners and grate 7 Remove Grate 8 Using a vacuum cleaner fully clean...

Страница 97: ...3 short beeps Receiver batteries low Test the batteries replace if necessary Quality 1 5V AA alkaline recommended No 1 long beep 8 wire cable is off or not operating properly Confirm proper operation...

Страница 98: ...gas magnet unit drops after 30 second audible count Check gas supply Spark not lighting the pilot Check spark is crossing pilot orifice Cracked ignitor rod spark heard but not seen Ensure that ignitor...

Страница 99: ...e ignition cable Yes G Main burner is lit No Manual knob is in the MAN position Turn the control knob to ON position a positive latch is required Yes Pilot flame is too low Confirm correct gas pressur...

Страница 100: ...valve will turn to pilot flame if the set temperature and the ambient temperature remain the same over a 6 hour period Yes Yes Receiver batteries low Test the batteries replace if necessary Quality 1...

Страница 101: ...gas the air shutter must be fully open See conversion instructions Ensure that the flue configuration is within the vent chart requirements Check termination for blockage and or appropriate type No C...

Страница 102: ...uineLivingFirespecifiedparts Sealanyscrapceramicsin plasticbagsanddisposeatproperrefusesites Whenusingavacuumcleaner itisrecommendedthat one with a HEPA filtering system is used Re fittheFirebedarrang...

Страница 103: ...Cleantheouterglasswithamildliquid or spray or glass cleaner Do not use harsh abrasive cleaners or sharp metal scrapers to clean the heaterglassfrontastheycanscratchthesurface whichmayresultinshatterin...

Страница 104: ...Distributed By LIVING FIRE 61 3 99 777 888 info livingfire com au www livingfire com au...

Отзывы: