Gas Supply and Burner Information 

Supply pressure should be minimum of 4" W.C. for natural gas or 10" W.C. for propane. The fryer comes 

with  ¾”  NPT  male  connector  on  a  ½”  pipe,  allowing  you  to  connect  with  either  ¾”  or  ½”  NPT  female 

connector. 

Model 

Burners 

Gas Type 

Manifold 

Pressure 

Number of 

heat tube 

Rate Each 

BTUs / Hour 

Total Rate 

BTUs / Hour  Orifice Size 

3 burner 

fryer  NG 
3 burner 

fryer LP 

Main 

Natural 

4" W.C. 

30,000 

90,000 

# 39 

Propane 

10" W.C. 

30,000 

90,000 

# 52 

4burner 

fryer NG 
4 burner 

fryer -LP 

Main 

Natural 

4" W.C. 

30,000 

120,000 

# 39 

Propane 

10" W.C. 

30,000 

120,000 

# 52 

5 burner 

fryer -NG 
5 burner 

fryer -LP 

Main 

Natural 

4" W.C. 

30,000 

150,000 

# 39 

Propane 

10" W.C. 

30,000 

150,000 

# 52 

* Minimum supply pressure is 4" W.C. for natural gas and 10" W.C. for propane.

** Orifice sizes are for units installed at altitudes between 0 and 2000 feet above sea level.

I

NSTALLATION

 

NOTICE 

Installation  must  conform  with  local  codes,  or  in  the  absence  of  local  codes,  with  the 

National  Fuel  Gas 

Code,  ANSI  Z223.1,  Natural  Gas  Installation  Code,  CAN/CGA-B149.1,

  or  the 

Propane  Installation  Code, 

CAN/CGA-B149.2,

 as applicable. 

NOTICE 

These installation procedures must be followed by qualified personnel or warranty will be void. 
Local  codes  regarding  installation  vary  greatly  from  one  area  to  another.  The  National  Fire  Protection 

Association, Inc. states in its NFPA 96 latest edition that local  codes are the “authority having jurisdiction” 

when it comes to installation requirements for equipment. 

Содержание PT-F3-NG

Страница 1: ...E INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT Please call the Service Department and ask for contact informati...

Страница 2: ...could result in injury product damage or property damage NOTICE This symbol refers to information that needs special attention or must be fully understood even though not dangerous WARNING FIRE HAZAR...

Страница 3: ...of reliable trouble free operation For best results read this manual carefully RETAIN THIS MANUAL FOR FUTURE REFERENCE MODELS This manual is for Gas floor model Fryers with 40 lbs 50 lbs and 90 lbs ca...

Страница 4: ...Height in Gas Connection in Total BTU hr Crated Weight lbs A B C D E F G H I 3 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7 0 90 000 150 4 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7...

Страница 5: ...50 000 39 Propane 10 W C 5 30 000 150 000 52 Minimum supply pressure is 4 W C for natural gas and 10 W C for propane Orifice sizes are for units installed at altitudes between 0 and 2000 feet above se...

Страница 6: ...are pre mounted on the base plates 1 Raise fryer sufficiently to allow legs or casters to be screwed into the base plate For safety shore up and support the fryer with an adequate blocking arrangemen...

Страница 7: ...iance is moved to its original installed position WARNING When this appliance is installed with casters it must be installed with the casters supplied a connector complying with either ANSI Z21 69 or...

Страница 8: ...8 Step 3 Flue Installation 1 Unpack the flue box and flue wrap 2 Slide the flue box over the flue and secure it with the two self tapping screws using a 5 16 socket 3 Slide the flue wrap over the flue...

Страница 9: ...FLOOR MODEL FRYERS SHALL BE INSTALLED WITH AT LEAST A 16 INCH SPACE BETWEEN THE FRYER AND SURFACE FLAMES FROM ADJACENT EQUIPMENT A FLAME GUARD IS ACCEPTABLE IF ALLOWED UNDER LOCAL CODE No additional s...

Страница 10: ...cked at installation and adjusted if necessary For orifice sizes and pressure regulator settings see the chart on page 4 If the fryer is being installed at over 2 000 feet altitude and that informatio...

Страница 11: ...SURES IN EXCESS OF 14 WC 1 2 PSIG or 3 45 kPa If the incoming gas pressure is in excess of 14 WC 1 2PSI 3 45 kPa a proper step down regulator will be required See PHOTO 1 for LP application Connect th...

Страница 12: ...knob down use a lit match to ignite the pilot Continue to press the knob down for about 30 seconds If the pilot does not stay lit when the knob is released repeat the lighting procedure and keep the k...

Страница 13: ...BURNERS WHEN THE FRYPOT IS EMPTY 7 To prevent burning or scorching the solid shortening keep the thermostat set at the lowest temperature until all the solid shortening between and above the tubes has...

Страница 14: ...d food CLEANING The equipment is constructed with the best quality materials and is designed to provide durable service when properly maintained To expect the best performance your equipment must be m...

Страница 15: ...residue from stainless steel use ordinary soap and water with or without detergent applied with a sponge or cloth Dry thoroughly with a clean cloth Never use vinegar or any corrosive cleaner To remove...

Страница 16: ...ontact your Service Representative for reliable service dependable advice or other assistance and for genuine factory parts All units are adjusted at the factory In case of problems in operation at in...

Страница 17: ...ace adjustment screw cap CHECKING AND ADJUSTING CALIBRATION OF THERMOSTAT All thermostat controls are carefully calibrated at the factory i e the dial is properly set to control appliance temperatures...

Страница 18: ...ed Combination gas valve is in OFF position Pilot gas not adjusted properly Gas supply to unit off Bad thermopile Dirty thermopile connections at combination gas valve or high limit Clogged orifice Dr...

Страница 19: ...19 Wiring Diagram...

Страница 20: ...cement parts may be ordered either through a Authorized Parts Distributor or a Authorized Service Agency When ordering parts please supply the Model Number Serial Number Part Number and Description In...

Страница 21: ...sys 4 PT 400146 1 Combination valve LP _Invensys 4 PT 400242 1 Combination Valve Nat _Honeywell 4 PT 400246 1 Combination valve LP _Honeywell 5 PT 400070 1 Tubing fryer pilot 10 PT 300031 ea Burner Fr...

Страница 22: ...T 400076 1 Flue top removable 4 tube fryer PT 400077 1 Flue top removable 5 tube fryer 6 PT 400078 1 Flue wrap top removable 3 and 4 tube fryer PT 400079 1 Flue wrap top removable 5 tube fryer not sho...

Страница 23: ...We all recognize however that replacement parts and occasional professional service may be necessary to extend the useful life of this unit When service is needed contact an Authorized Service Agency...

Страница 24: ...ntiguous United States Hawaii and metropolitan areas of Alaska and Canada may vary The following conditions are not covered by warranty Equipment failure relating to improper installation improper uti...

Отзывы: