System Manual | 2014

PA8500-VES System

UK

CR8506-V 

|

 RT8506-V

8.4.1.5  POWER SUPPLY FAULTS

 

Power supply and display memory diagnostics

From.the.FAULTS.panel.(point.8.4.1),.press.numerical.key.

4

.to.access.the.

panel.for.viewing.the.diagnostics.of.the.primary.and.secondary.power.supplies.

and.of.the.memory.for.managing.the.display.

The.diagnostic.state.of.each.item.monitored.is.reported,.as.shown.in.the.

following.table.

Press.ESC.to.return.to.the.FAULTS.panel.

Label

Part being diagnosed Display

Cause

Action required

All

All

Ok

No.failures

-

N.T.

NOT.TEST..Diagnostics.disabled.

during.configuration.(See.Menu.

set>.BACkGROUND.TEST)

-

Res.

Failure.cleared.due.to.previous.

failure.signal

Access.the.Report>.FAULTS.panel.from.

the.OPERATOR.menu.and.carry.out.a.

MANUAL.RESET.of.the.FAILURE.signal.

..Contr..mains

Primary.power.supply.

of.the.controller.

@230V

ac

Fault

Primary.power.supply.of.the.

controller.not.detected

Check.the.230.VAC.power.supply,.the.

connecting.cable.and.the.mains.fuse..

If the failure persists, contact the Service 

Centre.

..Contr..24VDC

Secondary.power.

supply.of.the.

controller

@24V

dc

Secondary.power.supply.of.the.

controller.not.detected

Check.the.24.VDC.power.supply,.the.

connecting.cable.and.the.mains.fuse..

If the failure persists, contact the Service 

Centre.

..3-Rtr/PA.mains

Primary.power.supply.

of.the.router/PA.

@230V

ac

Primary.power.supply.of.the.

router.or.PA8506-V.not.detected

Check.the.230.VAC.power.supply,.the.

connecting.cable.and.the.mains.fuse..

If the failure persists, contact the Service 

Centre.

..4-Rtr/PA.24VDC

Secondary.power.

supply.of.the.router/

PA.@24V

dc

Secondary.power.supply.of.the.

router.or.PA8506-V.not.detected

Check.the.24.VDC.power.supply,.the.

connecting.cable.and.the.mains.fuse..

If the failure persists, contact the Service 

Centre.

.Ctr.display

Controller.display.

Fault

Upset.detected.on.display

Contact the Service Centre.

.PA.display

PA8506-V.display

Fault

Upset.detected.on.display

Contact the Service Centre.

Tab..8.4.1.5

Содержание PA8500-VES

Страница 1: ...Cert EN 54 16 2008 n 0068 CPR 082 2013 CR8506 V VES Controller Voice Evacuation Systems PA8500 VES RT8506 V VES Router Instructions for use Version 1 3...

Страница 2: ......

Страница 3: ...6 1 INTRODUCTION 22 6 2 CREATING A NEW PROJECT FILE 22 6 3 OPENING AN EXISTING PROJECT 22 6 4 INSERTING THE CONTROLLERS 23 6 5 CONFIGURING THE CONTROLLER 23 7 MENU STRUCTURE 30 7 1 HOME functions Acc...

Страница 4: ...s are required The simplicity of the connections using Cat 5e SF UTP shielded cable between the various different management units amplifiers and emergency microphone stations makes sound broadcasting...

Страница 5: ...System Manual 2014 PA8500 VES System UK CR8506 V RT8506 V CR8506 V controllers and digital amplifiers of the PMD CR8506 V controller and RT8506 V PA8500 VES System featuring a mixed configuration...

Страница 6: ...PMB106 G PMG112 G R5 Balanced input for a microphone or outside source Terminal block for connecting a precedence contact R6 Input for external microphone R7 Input for connecting an external source of...

Страница 7: ...dedicated software Automatic management of the stand by amplifier Input for 24 VDC secondary power supply 7 programmable and controlled input contacts 3 relay outputs 6 control lines for digital ampli...

Страница 8: ...y activities inside the equipment such as maintenance operations and so on must be carried out solely by specialised personnel When the cover is removed parts become accessible that entail a risk of e...

Страница 9: ...System Manual 2014 PA8500 VES System UK CR8506 V RT8506 V 4 CONNECTIONS...

Страница 10: ...rs of the system max 6 with one another B Connecting THE output lines Use the SLAVE LINK OUTPUTS sockets R9 to connect the following to the controller B1 RT8506 V router B2 PA8506 V compact emergency...

Страница 11: ...at 5e SF UTP cable to connect one of the SLAVE LINK OUTPUTS sockets R9 to the REMOTE LINK socket on the PA8506 V compact system B3 Amplifiers of the PMD range Use a Cat 5e SF UTP cable to connect one...

Страница 12: ...of the radio microphone kit with output balanced at the level of the microphone connected to the IN 1 input To receive select the INPUT 1 BGM source from the MUSIC menu Set the following via the INPU...

Страница 13: ...IC 2 OFF Caution Do not connect any other equipment to the LINE terminals of the IN 2 input C Digital microphone stations connected in cascade formation to the PAGING UNIT input The announcement will...

Страница 14: ...nputs There are 7 contacts on the CONTROL INPUTS R8 socket An example of a connection is shown in the figure N B In the example contacts 1 to 6 are controlled while contact 7 is not G Connection to a...

Страница 15: ...ted This operating condition signals that the Alarm signals for at least one output zone have been set to a Disablement condition The system can in any case carry on the functions pertaining to the Qu...

Страница 16: ...8506 V system manages priorities as shown in the following tables The active sources in the Voice Alarm condition always have priority over those active in Quiescent condition regardless of the priori...

Страница 17: ...r emergency Together with the knob and with the multi purpose keys it is useful for navigating through the menus for adjusting working parameters and for managing advanced functions It will also displ...

Страница 18: ...7 different levels and the group of paging zones The XLR F socket enables a balanced signal of up to 100 mV to be connected by means of shielded balanced microphone cable For details concerning the s...

Страница 19: ...he presence of a failure on at least one of the 6 output lines F6 ZONE OUTPUT LEDs The red MSG LEDs indicate in real time the zone s in which the emergency voice signal is being broadcast Flashing War...

Страница 20: ...It is possible to enable diagnostics for the connecting line by installing two 10 kOhm balancing resistors in the proximity of the contact for activating the remote peripheral unit This connection ca...

Страница 21: ...tinguishes automatically and the wording RES is shown on the FAULTS display to show that a failure has been detected and subsequently remedied RESUMED The LED signalling that the fault has been cleare...

Страница 22: ...ct select Project Edit Description and enter it in the field provided max 22 digits To save the new project select File Save Project As use the dialogue box to assign a name to the project and identif...

Страница 23: ...pen in which you can select the equipment that is connected to this line none RT8506 V router PMD amplifiers or a PA8506 V compact system Select the required option and click on Continue Each option l...

Страница 24: ...plifier half way down the list is deleted by selecting model none as the model therefore all the amplifiers with the next addresses will also be removed One line can manage up to a maximum of two stan...

Страница 25: ...the required parameters with each of the 3 contacts Press End to save the configuration or press Canc to cancel it and return to the main window EMERGENCY UNITS Press EMERGENCY UNITS Configure The win...

Страница 26: ...ws The new combination selected by you will appear immediately on the list on the right hand side Press End to save the configuration or press Canc to cancel it and return to the main window Configuri...

Страница 27: ...n warning situations Alert or in evacuation situations Evac It is also possible to add a brief description of each message entered max 25 digits In addition to voice messages a warning tone Chime can...

Страница 28: ...PC 4 Wait for the operating system to load the driver of the device The Virtual Com Port icon in the example this is COM10 will appear in the Devices and printers section of the control panel 5 From...

Страница 29: ...reate SD The card will be formatted and then automatically programmed with the necessary data Once writing has been completed remove the SD card from the PC then plug it into its slot in the rear pane...

Страница 30: ...ic level the ALERT and EVAC keys are not operational OPERATOR Menu Second access level for trained personnel authorised to manage the system in emergency failure and disablement conditions A password...

Страница 31: ...the display unit to browse through the options listed then use OK to select the one you require Press ESC to return to the MUSIC menu or MENU to return to the HOME page For the specific features for e...

Страница 32: ...U to return to the HOME page For the specific features for each panel for managing the CONFIGURATION SERVICE menu refer to the appropriate schedules in Section 8 USING THE SYSTEM 8 6 CONFIGURATION men...

Страница 33: ...1 Initialising the system If the initialise procedure is complete see the instructions of the following sections For normal use of background music and voice announcements users can use just MUSIC and...

Страница 34: ...nostic test by setting 24 VDC P S ON as illustrated under POWER SUPPLY point 8 5 2 3 page 50 o Path HOME CONFIGURATION set BACKGROUND TEST 4 Power supplies Emergency messages The emergency messages ar...

Страница 35: ...onal EVAC Not operational 8 2 1 Selection of a BGM Source for the music channel Press OK to select the required source of music from among the following AUX Microphone source connected to the LINE AUX...

Страница 36: ...FOLDER FOLD 2 PLAY 3 STOP 4 SELECT PREVIOUS TRACK 5 SELECT NEXT TRACK 6 REPEAT FILES Using the external Flash Memory as an USB source Plug the flash memory into the EXT socket on the front panel C11 a...

Страница 37: ...icrophone connected to the MIC 1 IN socket 4 Mic 2 input Microphone connected to the MIC 2 IN socket 5 From remote Other controllers connected to the LINK sockets on the CR8506 V Volume control Hold d...

Страница 38: ...ing mode of the input for using the voice channel as a PA source Hold down key 2 Zone call then turn the knob to select the required mode from among the following options Z 1 Z 216 To select the speci...

Страница 39: ...e of a contact connected to the precedence terminals Off input disabled for the PA announcement function The source connected continues to be available for selection as a BGM Source 2 Zone call Settin...

Страница 40: ...of the current or cleared past failures query 8 4 2 IMP REAL TIME panel from the report IMPEDANCE option For viewing in real time the line impedance values detected by the system indicating the percen...

Страница 41: ...R8506 V will reset the beep automatically extinguish the FAULT LED and indicate RES RESUMED in the label of the part that had FAILED The RESOLVED signal will be stored until a MANUAL RESET of the fail...

Страница 42: ...For some items of equipment it may be necessary to access the sub panel by pressing the corresponding numbered key Press ESC to return to the panel FAULTS Tab 8 4 1 2 Label Part being diagnosed Signa...

Страница 43: ...has been correctly plugged into its slot on the rear panel of the controller 3 Emerg Unit Emergency microphone stations Fault Failure of at least one emergency microphone station Make sure that the m...

Страница 44: ...cess the report FAULTS panel from the OPERATOR menu and carry out a MANUAL RESET of the FAILURE signal Amplifier n Amplifiers of the PMD range connected to the controller or AW5624 48 amplifiers conne...

Страница 45: ...the controller not detected Check the 230 VAC power supply the connecting cable and the mains fuse If the failure persists contact the Service Centre Contr 24VDC Secondary power supply of the control...

Страница 46: ...rnal communication failure Contact the Service Centre SPI Data communication between CPUs All Fault Internal communication failure Contact the Service Centre Tab 8 4 1 7 Label Part being diagnosed Dis...

Страница 47: ...adcast announcements and display the INPUT EMERGENCY panel This will indicate which external input has activated the emergency point 8 8 page 58 The functionality of the inputs is defined by the firmw...

Страница 48: ...vel enables MANUAL RESETTING OF FAILURE SIGNALS 8 5 4 Firmware Version panel via the Firmware Version option This panel shows the version of the firmware installed in the system INSPECTION For going d...

Страница 49: ...es for choosing the items subjected to diagnostics are listed as shown in the figure opposite 2 Voice Alarms see point 8 5 2 1 3 Amplifiers see point 8 5 2 2 4 Power Supply see point 8 5 2 3 5 Control...

Страница 50: ...dc P S on test enabled off test disabled 4 Display on test enabled off test disabled Note The display will show the programming that has been set Press ESC to return to the BACKGROUND TEST panel 8 5 2...

Страница 51: ...password required for accessing the system again in future thus preventing unauthorised personnel from accessing the advanced functions of the system From the options list of the OPERATOR MENU turn th...

Страница 52: ...l the existence of a Disablement Condition 8 6 7 Password panel via the Password option Panel for enabling disabling and customising the password for accessing the system service levels 8 6 8 BEEP OPE...

Страница 53: ...mpedance meter The amplifiers of the PMD range use a tone that has a frequency of 30 Hz Press ESC to return to the CONFIGURATION menu Upon completing the procedure carry out a MANUAL RESET of the FAIL...

Страница 54: ...d to the system 1 Link A level Press key 1 then turn the knob 2 Link B level Press key 2 then turn the knob 4 Line music lev Music channel test levels 1 Line 1 level Press key 1 then turn the knob 2 L...

Страница 55: ...Hold the corresponding numerical key 1 to 3 down and use the knob to adjust the setting 1 Line Line 1 to 6 2 Amp Amplifier 1 to 16 ALL 3 Time Length of test 5s to 18h no test Upon completion press ESC...

Страница 56: ...he emergency mode will also be shown on the routers stations and any other controllers connected to the controller Send a voice message using the hand held microphone or an alerting message ALERT key...

Страница 57: ...r the EVAC evacuation key to send the pre recorded message to the zones that have been selected To end live emergency messages release the PTT key then press the EMERGENCY push button again Make sure...

Страница 58: ...entering the system to activate the manual controls for managing the emergency in order to RESET the messages change the current messages or send live announcements using the microphone provided for t...

Страница 59: ...ET of the failure signal as indicated under point 8 5 3 1 page 51 Note In the event of failure of a loudspeaker line due to a short circuit once the line is repaired it is necessary to carry out a MAN...

Страница 60: ...ERGENCY UNITS RJ45 for connection to a dedicated emergency microphone station Outputs SLAVE LINK OUTPUT Output level Impedance RJ45 for connection to an RT8506 V PMD PA8506 V unit Max 2000 mV 400 W CR...

Страница 61: ...voice alarm condition 7 9 Voice alarm condition output 8 3 Indication of faluts related to the transmission path 8 4 Indication of faults related to voice alarm zones 9 Disablement condition 10 Voice...

Страница 62: ......

Страница 63: ......

Страница 64: ...by this warranty free of charge if it is faulty provided the defect has occurred during normal use The warranty does not cover products that are improperly used or installed mechanically damaged or d...

Отзывы: