7 | 

P a g e

 

 

Worm Gear Mechanism 

 

With ground strap in place on vertical operating 

pipe, slide worm gear mechanism (Fig. 5) over the 

vertical operating pipe and attach it to the 

structure.  Remove the small position indicators, 

which are attached to the worm gear coupling with 

Allen set screws. Tighten hex  head set screws in 

the coupling until the vertical operating pipe is 

pierced.  The three-pole switch should now be 

operated manually to check for proper adjustment. 

If all stops at switch elevation have been set, 

including the offset bearing, then it is safe to 

reinstall the position indicators on the worm gear 

mechanism.  These indicators should not quite 

touch the raised boss on the worm gear housing in 

either the open or closed position.  There is a 

possibility of damage to the indicators or the 

coupling if this is not observed 

 

Motor Operator 

For remote operation, a motor operator is supplied 

and it should be installed per the instructions 

supplied with it.   

 

 

Step 10—Arcing Horns or Arc Restrictors 

When arcing horns of Arc Restrictors are supplied, 

they should now be installed and adjusted in 

accordance with the drawings. The stationary horn 

is attached to the jaw and should be adjusted, or 

even bent slightly, to give a light contact pressure 

between the horn and the switch blade. 

 

Step 11—Installation of Sleet/Corona Shields 

The combination sleet/corona shields should now 

be installed over the blade mechanism at the top of 

the center insulator stack and on top of the two 

jaws as shown on single pole drawings. 

 

Step12—Final Checks  

 

The completed 3-pole installation should be 

checked for the following: 

1.

 

In the open position, the blades should be at an 

angle of 70° to the centerline of the switch 

base, and stop at each base and the stop for the 

operating bearing should be touching, or 

nearly so. The indicator at the  worm gear 

operating mechanism should indicate the 

switch is open. 

2.

 

In closing, blades should make central entry 

into their jaws at approximately the same time. 

3.

 

In the closed position, all blades must be in 

full contact with jaw contacts and also vertical 

within the tolerances described previously. The 

stop at each switch base and the stop for the 

operating bearing should be touching, or nearly 

so. The  indicator  to  the worm gear operating 

mechanism should indicate the switch is closed. 

 

MAINTENANCE 

 

A  certain amount of care and inspection is 

recommended. The frequency of inspection depends 

upon atmospheric conditions and frequency of 

operation.  The service interval is largely 

determined by the user.  Recommended 

maintenance is similar to that listed in  the latest 

industry standards.

1

  First, it is important that the 

insulators are always clean. It is also important that 

the contacts be examined to see that they are 

aligned, clean, and have a firm uniform pressure. If 

the contacts are pitted, or burned to  some extent, 

they should be removed and replaced. 

 

Under normal service conditions, the jaw contacts 

should be examined and maintained at least once a 

year, depending upon the type of atmosphere to 

which they are exposed. 

 

Periodic maintenance should consist of cleaning the 

contact surfaces thoroughly by carefully scraping 

off any contamination or deposit and sanding the 

surface entirely clean, a coating of lubricant should 

be applied. Suggested lubricants are MOBIL 28 

grease of NO-OX-ID  “A Special”. MOBIL 28 is an 

Exxon Mobil Company product. NO-OX-ID is 

made by SANDCHEM INC. 

 

In general, operating linkages require virtually no 

maintenance. However, in contaminated 

atmospheres of where operation under sleet 

conditions is common some lubrication at pivot 

points may be desirable. The grease used should be 

durable even when exposed to the elements, and 

should retain its viscosity over a wide temperature 

range.  

 

Terminal Connections 

 

The aluminum surface of the terminal connection 

provides for easy current transfer. 

                                                 

1

 ANSI C37.35 (American National Standard Guide for 

the Application, Installation, Operation and Maintenance 

of High-Voltage Air Disconnecting and Interrupter 

Switches) 

Содержание TTT7

Страница 1: ...IB TTT7 May 2012 ...

Страница 2: ...ase and Operating Connecting Rods 4 Step 8 Installing Vertical Operating Pipe 4 Step 9 Installing Vertical Operating Pipe and Operation Mechanism 5 Step 10 Arcing Horns or Arc Restrictors 7 Step 11 Installation of Sleet Corona Shields 7 Step 12 Final Checks 7 Maintenance 7 Terminal Connections 7 Renewal Parts 9 Suggested Tools 15 16 Open End Wrench 15 16 Socket 3 4 Open End Wrench 2 3 4 Socket 1 1...

Страница 3: ...ic representative HANDLING Handling of disconnect switches should be done with care Porcelain is fragile and may be damaged due to improper handling Factory drawings should be followed during installation It is recommended that switches be fully assembled and adjusted at ground level before being placed into position This should minimize final adjustments Lifting of switches by insulators contacts...

Страница 4: ...essary to adjust the insulator columns for variation in heights or proper angle use the shims leveling bolts or leveling screws as provided see Fig 1 Step 5 Mounting Current Carrying Parts Rotate the center insulator column to the open position as shown on the drawings The stop at the bottom of the column limits the travel At this time the crank at the bottom of the insulator column will be at an ...

Страница 5: ... three pole switch In fact after all three poles have been adjusted in the open position and then closed you may find that one pole will be high on the right one fairly level and one high on the left This is due to many variables and tolerances plus the free play or clearance in pin connections of all the switches and control parts 6 3 Blade Engagement When Switch is Closed Due to varying friction...

Страница 6: ...ide plate which can be easily adjusted in an arc to provide the required rotation These act as locks for the manual operating handle when it is dropped from the operating position The handle must be raised to a horizontal position for operation With the switch in the fully closed position set the handle clamp so its set screws are 4 inches above the lock plate and its vertical centerline is at or ...

Страница 7: ...6 P a g e ...

Страница 8: ...blades should make central entry into their jaws at approximately the same time 3 In the closed position all blades must be in full contact with jaw contacts and also vertical within the tolerances described previously The stop at each switch base and the stop for the operating bearing should be touching or nearly so The indicator to the worm gear operating mechanism should indicate the switch is ...

Страница 9: ...ntact surfaces of conductors and fittings using a stiff wire brush to remove heavy oxide coatings until the aluminum finish is visible and restored 2 Prepare any bare copper surfaces in the usual manner 3 Coat these now clean contact areas with a liberal amount of corrosion inhibitor such as NO OX ID A Special or no 2 EJC 4 Abrade the contact surface through the corrosion inhibitor using a stiff w...

Страница 10: ...each switch pole The same data is shown on the record engineering drawings The master file at the factory is linked to the serial number on the nameplate Renewal Parts Ordering Information Serial Number Switch Type Part Name Quantity Required Max kV B I L kV Cont Amps Mom Amps Refer your requests for renewal parts to the Factory ...

Отзывы: