background image

5 | 

P a g e

 

 

Fig. 10 MO-10 Motor Operator

 

4.

 

If all stops at switch elevation have been set, 

including the offset bearing, then it is safe to 

reinstall the position indicators on the worm 

gear mechanism.  These indicators should 

not quite touch the raised boss on the worm 

gear housing in either the open or closed 

position.  There is a possibility of damage to 

the indicators or the coupling if this is not 

observed 

 

Motor Operator 

For remote operation, a motor operator is 

supplied and it should be installed per the 

instructions supplied with it.   

 

Step 7—Arcing Horn Installation 

 

Arcing horns are furnished only when horn 

gap switches are ordered. When arcing 

horns are used, they should be installed and 

adjusted after the switches are mounted and 

adjusted. 

The arcing horn should be adjusted to make 

very light contact when the switch is 

operated, the main switch contacts should 

separate before the arcing horns disengage. 

Refer to arcing horn assembly drawing 

supplied with the order for detailed 

information.  

 

 

 

 

Step 8—Final Checks

  

The completed 3-pole installation should be 

checked for the following: 

1.

 

In the open position, the blades should be 

between 90° to 93°. 

2.

 

In closing, blades should make central entry 

into their jaws at approximately the same 

time. 

3.

 

In the closed position, all blades must be in 

full contact with jaws. 

4.

 

All bolts are tight and all cotter pins are bent 

adequately. 

5.

 

The single poles are held against or nearly 

against their individual rotor bearing stops in 

both the open and closed positions and also 

the stops on the offset bearings are engaged. 

6.

 

Operating effort required to operate the 

switch is not excessive. 

  

 

 

 

 

 

 

 

 

 

 

 

Fig. 9 Geared Mechanism 

Содержание FAS2-V

Страница 1: ...IB FAS2 V April 2014 Type FAS2 V 7 5 THRU 69Kv 600 1200 Amp 61 KA Momentary Center Break Gang Operated Outdoor Air Disconnect Switch ...

Страница 2: ...ase Rods and Offset Crank Rod 3 Step 7 Install Vertical Operating Pipe 4 Step 8 Install Pipe Splice and Guide Plate 4 Step 9 Install Operating Mechanism 5 Step 10 Arcing Horn Instillation 6 Step 11 Final Checks 6 Terminal Connections 6 Maintenance 7 Renewal Parts 8 Lubrication 8 Suggested Tools 15 16 Open End Wrench 15 16 Socket 3 4 Open End Wrench 2 3 4 Socket 1 1 2 Open End Wrench or Adjustable ...

Страница 3: ...or live parts should be avoided because of possible damage to these parts Attachments for hoisting should be made to the switch bases unless otherwise instructed CAUTION When uncrating switches having blade counterbalances open the switch blade to relieve the pressure of the counter balance before removing the live parts from the base INSTALLATION AND ADJUSTMENT Step 1 Switch Blade Adjustment Chec...

Страница 4: ...ral members when the crank crosses the dead center position This serves as a signal to the operator that the switch is fully closed Step 4 Install Interphase Rods With all blades in the closed position install the interphase rods and offset crank rod as follows a Lengthen the interphase rods that are in compression during opening as much as possible yet allowing for the pins to be inserted b On th...

Страница 5: ...6 Install Operating Mechanism Two types of manual operating mechanisms Swing handle operator Worm gear mechanism Swing Handle Operator To install the swing handle operator 1 With ground strap in place on vertical operating pipe slide handle and handle lock plate over the end of the vertical operating pipe 2 Fasten the lock plate at the proper location Recommended height for the lock plate is 3 ft ...

Страница 6: ...e mounted and adjusted The arcing horn should be adjusted to make very light contact when the switch is operated the main switch contacts should separate before the arcing horns disengage Refer to arcing horn assembly drawing supplied with the order for detailed information Step 8 Final Checks The completed 3 pole installation should be checked for the following 1 In the open position the blades s...

Страница 7: ... WARNING Before servicing the switch be sure it is disconnected from all electric power sources and properly grounded A certain amount of care and inspection is recommended The frequency of inspection depends upon atmospheric conditions and frequency of operation The service interval is largely determined by the user Recommended maintenance is similar to that listed in the latest industry standard...

Страница 8: ...oor Switch Components Part Name Type Lubricants Recommended Amount Applied Qty Req d for 6 Three pole Switches Jaw Fingers NO OX ID Grade A Special or Mobil 28 Grease Medium Coat Blade Ends NO OX ID Grade A Special or Mobil 28 Grease Medium Coat 1 Quart Pins On current carrying parts Mobil 28 Grease or DC 4 Pins On control parts Mobil 28 Grease or DC 4 Light Coat 1 Quart Bearing Areas On control p...