background image

 

subjected to local heat gain e.g.in front of 
windows allowing the sun to act directly on 
the thermostat. 
 
Note: The main electric supply should be 
protected by a fused isolating switch rated 
at:- 
GP-300 

13 Amps 

GP-400 

10 Amps 3 Ph. 

GP-500 

10 Amps.3 Ph 

GP-750 

20 Amps 3 Ph 

GP900  

20 Amps 3 Ph 

 
The wiring to the appliance should be to 
I.E.E. Regulations. An earth wire is 
connected to the main terminal block in the 
heater, as indicated in the wiring diagrams. 
 

 
8. Commissioning  
    Instructions 
 

Ensure that the gas and electricity supplies 
to the appliance are turned off. Set the 
thermostat to a minimum position. 
 
Switch on the main electrical supply. Select 
the ‘manual’ setting on the fan/limit stat, 
which will then start the fan. Now switch to 
automatic. If the fan should fail to start, try 
to establish the cause (e.g. the blowing of a 
fuse or a fault in the wiring). Disconnect the 
main electrical supply. 
 
Refer to the Burner Supplement  supplied 
with the heater  and complete gas 
soundness test on the burner controls 
assembly. 
 
Complete the specified tests in the 
Commissioning  and Testing section of the 
Burner Supplement. The following is a 
description of the sequence of events that 

will occur each time the external control 
circuit is completed. 
 
With all the controls on and the thermostat 
calling for heat, the burner starts up going 
through a pre-purge period before ignition 
takes place. Start gas is released and 
ignited. The flame is sensed by an ionisation 
probe which allows the control box to open 
the main gas valve thus establishing main 
flame. 
 
On loss of flame or breakdown of the 
rectification systems the control box will go 
to lockout, and the rest button located on 
the control box will light up. Press the 
lockout button in order to rest the control 
box. 
 
 
 
 
The burner motor drives a fan which 
provides air for combustion. The air 
pressure that this fan produces is sensed 
and used to operate a pressure switch. This 
in turn signals the control box that air 
circulation is proved. Any loss in air 
pressure will automatically result in the 
burner going to lockout. 
 
Fitted to the burner is the main gas 
electrically operated valves. 
 
 

9. Maintenance  
    Instructions 
 

A maintenance check should be carried out 
annually. The check should be for safe and 
reliable operation of the burner and flue 
system, and any wear likely to take place 
on switches or moving components. 
 

Отзывы: