background image

 

 
1. Introduction 
 

The Parmet  Range of Gas Fired Warm Air 
Heaters covers applications with outputs 
from 300,000 to 800,000 Btu/h.  
 
The standard unit is the free-standing unit 
incorporating swivel type distribution heads.  
These units are available with inlet and 
outlets spigots suitable for connection to 
ductwork.  
 

2.Location  

The installation of a warm air heating system 
must conform with any fire regulations or 
insurance requirements especially where 
special risks are involved i.e. where there is 
paint spraying, etc.  Attention must be paid 
where polyurethane based products are 
used in the premises as these can cause 
corrosion to the heat exchanger. 

Installation of free blowing 
PARMET air heaters:- 

Position the air heater taking into regard the 
position of the exhaust flue and avoid the 
heater being obstructed by pillars or 
shelving which could prevent the warm air 
from circulating. 
When more than one air heater is installed 
in the same room it is good practice to 
distribute the air in opposing directions. 
If air is to be ducted from the appliance all 
ducting should be made from non- 
combustible material. 
Where interjoist spaces are used as duct 
routes they should be suitably insulated to 
prevent excessive heat transfering to the 

woodwork.  A full unobstructed return air 
path should be provided to enable the air to 
return to the heater. 
 

3.  Positioning the Unit

 
Free standing air heaters must be positioned 
on a level base that is capable of supporting 
the full weight of the unit. 
 
Ensure that sufficient clearance is allowed 
for, and maintained, around the heater to 
facilitate easy access to the burner, main fan 
assembly and heat exchanger for servicing 
purposes and to allow unrestricted passage 
of the return air unless the system is ducted. 
 

WARNING:- 
 

Clearance should be allowed for the 

pressure relief to operate. 
 

4. Combustion and  
    Ventilation Requirements. 

 
Combustion Air 
 
It is important to ensure that there is 
sufficient air for combustion, especially 
when a heater is positioned in an enclosed 
area i.e.plant room. 
 
The air supply requirements shown relate to 
the total rated input of the heater(s). Size of 
air vent given is for air direct from outside 
and relates to the free area of the grill. 
 

 

 

Отзывы: