MOTOR
TROUBLE
SHOOTING
GUIDES
PROBLEM
CAUSE
REMEDY
Motor
Overheats
(Check
temperature
with
instrumentation)
Motor
not
connected
for
proper
supply
voltage.
Check
connection
diagram
on
conduit
box
cover
and
correct
the
wiring.
Supply
voltage
varies
outside
the
allowable
tolerance
causing
an
undervoltage
or
overvoltage
condition.
Assure
correct
supply
voltage.
Insufficient
cooling
air
volume
due
to:
a.
Low
frequency
operation
on
variable
frequency
drive.
b.
Obstructed
air
flow.
Increase
air
flow:
a.
Continuous
running
auxiliary
fan.
b.
Ensure
unobstructed
air
flow.
Ambient
temperature
is
too
high.
Ensure
cool
air
gets
to
the
motor.
Ducting
may
be
required.
Overload
at
rated
voltage.
Unit
will
draw
current
in
excess
of
nameplate
rating
and
run
below
rated
speed.
Select
a
larger
unit.
Motor’s
allowable
duty
cycle
is
exceeded
(too
many
starts
per
hour
required).
The
problem
may
or
may
not
be
solved
with
a
larger
motor.
Contact
SEW
Eurodrive.
Single
phasing
due
to
break
or
loose
connection
in
supply
line
or
blown
fuse.
Repair
supply
lines.
Replace
fuses.
Motor
does
not
run.
Blown
fuse.
Determine
and
correct
cause
of
failure
and
replace
fuse.
Motor
protection
device
activated.
Reset
protective
device.
Identify
and
correct
cause
for
device
activation.
Motor
protection
device
faulty
or
will
not
reset.
Check
protection
device
for
faults.
Motor
will
not
start
or
starts
sluggishly.
Motor
not
connected
for
proper
voltage.
Check
connection
diagram
in
conduit
box
cover
and
correct
the
wiring.
Large
voltage
and/or
frequency
fluctuation
at
starting.
Ensure
stable
power
supply.
For
reduced
voltage
starting,
motor
will
not
start
in
Star
Connection
but
will
start
in
Delta
Connection.
Insufficient
torque
in
Star
Connection
Start
motor
directly
in
Delta
Connection
if
possible.
Otherwise
use
a
larger
motor.
Faulty
contact
in
Star/Delta
starter.
Correct
fault
condition.
Motor
hums
and
draws
high
current.
Falulty
or
defective
winding.
Have
motor
repaired
by
qualified
service
shop.
Rotor
dragging
Fuses
blow
or
motor
over
Ͳ
current
protection
trips
immediately.
Short
circuit
in
power
supply
conductors
or
in
the
motor.
Correct
the
fault
condition.
Motor
has
ground
fault
or
winding
to
winding
short
circuit.
Have
motor
repaired
by
qualified
service
shop.
Motor
improperly
connected.
Check
connection
diagram
in
conduit
box
cover
and
correct
the
wiring.
Motor
runs
in
the
wrong
direction.
Motor
supply
leads
misconnected.
Switch
two
supply
leads.
Note:
If
after
proceeding
through
the
Troubleshooting
Chart
the
motor
is
found
to
be
defective,
contact
your
nearest
SEW
Eurodrive
Asssembly
Plant
for
warranty
assistance
or
replacement
parts.
9D-20 of 24
Содержание Hycor ThickTech RDT400
Страница 7: ...EXHIBITS ...
Страница 28: ...CYLINDER ROTATION RDT CYLINDER ROTATION AS VIEWED FROM DISCHARGE END 4 1A ...
Страница 42: ...DRIVEN IDLER SPROCKET CHAIN DRIVE SPROCKET CHAIN AND SPROCKET ASSEMBLY SPROCKET TENSIONER 6 1A ...
Страница 63: ...Section Nine A 9A 1of 22 ...
Страница 72: ...9A 10of 22 ...
Страница 80: ...9A 18of 22 ...
Страница 81: ...9A 19of 22 ...
Страница 82: ...9A 20of 22 ...
Страница 83: ...9A 21of 22 ...
Страница 84: ...9A 22of 22 ...
Страница 85: ...Section Nine B 9B 1 of 8 ...
Страница 92: ...9B 8 of 8 ...
Страница 93: ...Section Nine C 9C 1 of 27 ...
Страница 98: ...Page 5 Page 5 9C 6 of 27 ...
Страница 100: ...Page 7 Page 7 9C 8 of 27 ...
Страница 101: ...Page 8 Page 8 9C 9 of 27 ...
Страница 120: ...Section Nine D 9D 1 of 24 ...
Страница 136: ...9D 17 of 24 ...
Страница 144: ...Section Nine E 9E 1 of 5 ...
Страница 149: ...Section Nine F 9F 1 of 23 ...
Страница 172: ...Section Nine G 9G 1 of 6 ...
Страница 178: ...Section Nine H 9H 1 of 2 ...
Страница 181: ...Control Panel BOM Drawings ...
Страница 194: ......
Страница 195: ......
Страница 196: ...Equipment Drawings ...