8.3 TECHNICAL DATA
7
SPS004-SPS100
Model
Weight
Refrigerant
R513A
MIN.- MAX
Ambient Temperature
Amb
Compressed
air inlet
Temperature
F.L.A.[A]
Minimum
section
validated
cable for
electrical
connection
Compressed
air inlet
air outlet
Air
Flow
During
transport
and stockage
After
installation
(Kg)
(Kg)
CO
2
e(t)
In
220/240V
±10%
1ph/50-60Hz
Ø [mm2]
BSPP-F
m
3
/h
SPS 004
24
0.16
0.10
0-50°C
5-50°C
5°- 65°C
1.69
3 G 1.5
1/2”
24
SPS 007
24
0.16
0.10
42
SPS009
25
0.16
0.10
54
SPS 014
35
0.24
0.15
1.76
3/4”
84
SPS 018
36
0.24
0.15
108
SPS 026
46
0.34
0.21
3.18
1”
156
SPS 032
46
0.34
0.21
192
SPS 040
47
0.34
0.21
240
SPS 052
53
0.40
0.25
5.75
1.1/2”
312
SPS 062
55
0.40
0.25
372
SPS 080
80
0.60
0.38
8.59
480
SPS 100
600
Calibration values
Expansion
automatic valve
7-AEV
Fan temperature
Switch
B2
High temperature
safety thermostat
13-HT
Air - Side Max
Working Pressure
High pressure
Switch
14-HP
IP
Sound
pressure level
SPS 004-62
2.6 barg (+ 0.1, - 0)
ON: 30.5 °C
OFF: 30 °C
80°C
16 bar
28 bar
22
52 dB (A)
SPS 080-100
14 bar
Содержание StarlettePlus-E
Страница 2: ......
Страница 98: ...6 6 SPS004 SPS100 7 a Het Het Het a a Het SK HT 50 C a Het Het Het Het Het Het Het Het Het a a a a a a a a a a...
Страница 142: ...8 7 REFRIGERANT CIRCUIT 14 SPS004 SPS100...
Страница 143: ...8 8 WIRING DIAGRAM 15 SPS004 SPS100...
Страница 144: ...8 8 WIRING DIAGRAM 16 SPS004 SPS100 SPS 004 040 SPS 052 062 SPS 080 100...
Страница 145: ...8 8 WIRING DIAGRAM 17 SPS004 SPS100...
Страница 146: ...8 8 WIRING DIAGRAM 18 SPS004 SPS100 Optional Free contact status compressor 018 052 100 108 312 600 026 040 156 240...
Страница 147: ......