green LED is blinking, pressing 

PB2

 will decrement the set point 

by 1°F. Do not press any pushbutton for 5 to 10 seconds or until the 

green LED stops blinking. The controller will use the last display 

 

for  the  leaving  liquid  temperature  set  point  and  will  go  back  to 

 

normal operation.

REMOTE PANEL DISPLAY

A remote panel display is available that will allow access to all the param-

eters that the controller uses. The Remote Panel Display can be used as a 

set point tool in production, a diagnostic tool in the field or as a permanent 

readout device on the controller. A five foot cable is included.

Plug the remote display into the telephone jack (J9) on the controller. The 

following is a list of readings available:

POSN 

Number of steps the electric expansion valve is open

SUPH 

Superheat read by controller

LQTP 

Temperature read by the leaving liquid temperature sensor (-50 

to 102°F.)

PRES 

Pressure read by the transducer (0-153 psi absolute or gauge)

TOUT 

Temperature read by the suction temperature sensor

  

(-50 to 102°F.)

TSAT 

Saturated  Temp.  Based  on  suction  pressure  and  refrigerant 

selected

COOL, PMDN
 

COOL when in normal operation, PMDN when in pump down

R22, 404A, R422, R507
 

R22 for refrigerant R22, 404A for refrigerant R404A, R422 for 

refrigerant R422D, and R507 for refrigerant R507.

LARG, SMAL, MEDM 
 

LARG if the EEV used is an SEI-50 or larger. SMAL if the 

EEV used is smaller than an SEI-30. MEDM if the EEV used is 

a SEI-30.

SHSP 

Superheat set point (5 to 30°F.)

LQSP 

Leaving liquid Temperature set point (-40 to 100

°F)

GAIN 

Proportional  gain  set  point.  Number  of  steps  per  degree  that 

liquid temperature is above or below its set point (0 to 255 steps 

per degree). Default is 44 for LARG setting, 22 for MEDM set

-

ting, and 10 for SMAL setting.

INTG 

Integral  set  point.  Number  of  seconds  the  controller  waits  to 

update the reference valve position. (1 to 120 seconds). Default 

is 50 seconds.

DERI 

Derivative set point. Number of steps the controller opens or 

closes the valve based on the rate the leaving liquid temperature 

is changing (0 to 255 seconds). Default is 20.

Pressing 

ENTER

  will  toggle  display  between  one  of  the  displays 

described above and the numeric value read for that particular display.  

Pressing 

UP

  will  scroll  through  the  menu  from 

POSN

  to 

SUPH

,  etc.  

Pressing 

DOWN

 will scroll through the menu the opposite way.

POSN MODE

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds to put the 

valve in manual valve position. The number of steps open will be dis-

played and the 1000’s digit will blink. 

Pressing the 

UP

 button will open the valve 1000 steps.

Pressing the 

DOWN

 button will close the valve 1000 steps.

Pressing the 

ENTER

 button will change the flashing digit from 1000’s 

digit to the 100’s digit.

 

Pressing the 

UP

 button will open the valve 100 steps.

Pressing the 

DOWN

 button will close the valve 100 steps.

Pressing the 

ENTER

 button will change the flashing digit from 100’s digit 

to the 10’s digit.

 

Pressing the 

UP

 button will open the valve 10 steps.

Pressing the 

DOWN

 button will close the valve 10 steps.

Pressing the 

ENTER

 button will change the flashing digit from 10’s digit 

to the 1’s digit.

 

Pressing the 

UP

 button will open the valve 1 step.

Pressing the 

DOWN

 button will close the valve 1 step.

Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 1000’s digit.

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds will put the 

controller in normal control. The digits will stop blinking.

SHSP MODE

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds to enable the 

superheat set point to be changed. The set point is displayed and the 100’s 

digit will blink. 

Pressing the 

ENTER

 button will change the flashing digit from 100’s digit 

to the 10’s digit. 

Pressing the 

UP

 button will increase the set point by 10 degrees.

Pressing the 

DOWN

 button will decrease the set point by 10 degrees.

Pressing the 

ENTER

 button will change the flashing digit from 10’s digit 

to the 1’s digit. 

Pressing the 

UP

 button will increase the set point by 1 degree.

Pressing the 

DOWN

 button will decrease the set point by 1 degree.

Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 100’s digit.

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds will save the 

set point. The digits will stop blinking.

LQSP MODE

Press  and hold 

UP

 button  and 

ENTER

 button for 5  seconds to enable 

the leaving liquid temperature set point to be changed. The set point is 

displayed and the 100’s digit will blink. 

Pressing the 

UP

 button will increase the set point by 100 degrees.

Pressing the 

DOWN

 button will decrease the set point by 100 degrees.

Pressing the 

ENTER

 button will change the flashing digit from 100’s digit 

to the 10’s digit. 

Pressing the 

UP

 button will increase the set point by 10 degrees.

Pressing the 

DOWN

 button will decrease the set point by 10 degrees.

Pressing the 

ENTER

 button will change the flashing digit from 10’s digit 

to the 1’s digit. 

Pressing the 

UP

 button will increase the set point by 1 degree.

Pressing the 

DOWN

 button will decrease the set point by 1 degree.

Page 2

Figure 2