SD-290-509

© 2009 Sporlan Division, Parker Hannifin Corporation

PROGRAM*

ITEM NUMBER

DESCRIPTION

PROGRAM

DEFAULT SETPOINTS

952971

SUBCOOL -O-MATIC

R-507 small valve

P0033

 

R507  SMAL

 

SHSP=10  LQSP=45

 

GAIN=10  ING=50

DERI=20

952972

SUBCOOL -O-MATIC

R-404A small valve

P0033

 

404A  SMAL

 

SHSP=10  LQSP=45

 

GAIN=10  ING=50

DERI=20

952973

SUBCOOL -O-MATIC

R-22 small valve

P0033

 

R22  SMAL

 

SHSP=10  LQSP=45

 

GAIN=10  ING=50

DERI=20

952974

SUBCOOL -O-MATIC

R-134A small valve

P0033

 

134A  SMAL

 

SHSP=10  LQSP=45

 

GAIN=10  ING=50

DERI=20

953050

SUBCOOL -O-MATIC

R-507 medium valve

P0033

 

R507  MED

 

SHSP=10  LQSP=45

 

GAIN=22  ING=50

DERI=20

953068

SUBCOOL -O-MATIC

R-404 large valve

P0033

 

R404  LRG

 

SHSP=10  LQSP=45

 

GAIN=22  ING=50

DERI=20

ACCESSORIES

PART NUMBER

DESCRIPTION

NOTES

952740

Transducer Kit

1 required per controller

952662

Temperature Sensor Kit

2 required per controller

Can be used as suction or subcooled liquid sensor.

958737

Panel Display

Not required for normal operation. Suggested for 

field troubleshooting or parameter modification.

953276

SMA-12

Not required for normal operation. 

Suggested for valve test & troubleshooting.

*Program number, eg. P0033 will be followed by revision number, eg. -02.

Table 3

Table 4

TROUBLESHOOTING

ALARMS

Subcool-O-Matic  boards  with  production  dates  after  4-16-07  include 

alarms  and  fail  safe  features.  Failed  mis-wired  sensors  will  trigger  an 

alarm. When triggered, an alarm code will be displayed on the 2 digit 

onboard display and on the remote panel display, when used. Each alarm 

indicates that the referenced sensor is mis-wired, disconnected or faulty. 

The alarm will persist until the problem is corrected.

Since the liquid and suction temperature sensors are identical, no alarm 

will be triggered if the sensors are placed in the incorrect location (i.e. 

liquid sensor on the suction line) refer to Figure 4, however, superheat 

readings and control will be inaccurate.

Failed temperature sensors will generally read extremely low resistance 

or infinite resisitance when tested with an ohmmeter. Readings should be 

taken with the sensor disconnected from the board.

Pressure transducers are tested while connected to the board and powered. 

Voltage between 1+ and 1- should be 5.0 volts DC. Voltage between 1- 

and 1S will be between 0.5 and 4.5 volts DC.

Pressure transducers must be installed tight enough to depress the valve 

stem in the fitting. Failure to do so will result in erroneous pressure read-

ings and possibly leaks.

FAILSAFE

If the superheat falls below 2 degrees, the valve will shut within 80 seconds.

ALARM

ONBOARD

DISPLAY

REMOTE

DISPLAY

Liquid temperature sensor

LS

LQSR

Suction (outlet) temp. sensor

OS

SCSR

Pressure transducer alarm

PS

PRSR

No alarm

actual superheat

NOAL

Table 2