The Mechanical Subcooler controller was designed as a simple and eco-

nomical means of controlling an Electric Expansion Valve on almost any 

mechanical subcooling system. True pressure and temperature superheat 

ensures accurate control and safety. All components (valves, controller, 

sensors) must be supplied by Sporlan to assure compatibility and proper 

operation. Please see Tables 3 and 4 on page 4 for correct part numbers. 

Pressure-temperature superheat control for one of four common refriger-

ants  may  be  selected.  Controllers  can  be  ordered  configured  for  R-22, 

R-404A, R-422D, and R-507. The refrigerant type can be changed in the 

field by use of the optional Panel Display, part number 958737. Onboard 

readouts show actual leaving liquid temperature, superheat, suction pres-

sure,  and  liquid  temperature  set  point.  Two  push  buttons  are  provided 

on the board, to change the liquid temperature set point, as well as open, 

close, or position the valve.

As illustrated, the controller is provided with hardware and input/output 

connections for a number of user specified purposes. See below:

• One valve control

• One pressure input (transducer supplied by Sporlan or Customer)

• One digital input (from external switches or relays)

• Two temperature inputs (Sporlan supplied surface or air sensors)

• Optional battery backup for onboard clock and fail-safe valve closure

• Two digit LED readout

• Green & red LED status indicators

• Two push buttons for setting superheat, etc.

• Panel Display jack

INSTALLATION

When  handling  the  boards,  electrostatic  protection  procedures 

should be followed. The person installing the controller should be 

grounded through a ground strap. If ground straps and other ESD 

protection are not available, handle the board only by the edges 

of the board. Another fairly safe place to hold the board is by the 

battery holders. DO NOT TOUCH ANY COMPONENTS ON THE 

BOARD EXCEPT THE BATTERY HOLDER OR RELAYS.

1.

  The board should be mounted in a dry, protected environment using 

the 5 mounting holes. Make sure none of the printed circuit paths or 

components are touching the metal panel or any thing else conductive.

2.

  If only one valve is used, connections are to be made to terminal block 

closest to display readout and push buttons 

PB1

 and 

PB2

.

3. 

Controllers are configured for pressure temperature superheat.

4.

  Connect suction temperature sensor to 

TS2

. The sensor is not polar-

ized. The sensor should be mounted to the suction line after the evapo-

rator using the furnished clamps. 

5.

   Connect leaving liquid temperature sensor to 

TS1

. The sensor is not 

polarized. 

6.

  The pressure transducer should be mounted on the suction line near 

the  temperature  sensor  location.  Sporlan  has  supplied  transducer 

cables with two combinations of wire colors. Connect the wires to the 

terminals on the board in accordance with Table 1 below. If the cable 

is spliced in the field to extend its length, care must be taken to assure 

that the new wire is properly connected to the board.

7.

   DI1 is a digital input used to close the valve. A short or closed contact 

from an external relay will close the valve for pump down. 

8.

   Power is connected to the terminal marked 24VAC. Power requirements 

are  24  volts  AC  at  40  VA.  For  protection  from  electrical  transients, 

connect one MOV varistor between one leg of the input voltage of the 

24 VAC transformer and earth ground. See Figure 4. Connect a second 

MOV varistor between the other leg of the input voltage of the 24 VAC 

transformer to earth ground. Two MOV varistors are included with the 

controller.

OPERATION

When first powered up the numeric display will show actual leaving liquid 

temperature.

1. 

When power is applied, the green LED will be on constantly and the 

2 digit display will show the leaving liquid temperature as read by the 

controller. The red LED is the negative sign. If the red LED is off, the 

2 digit display reading is between 0 to 99°F. If the red LED is on, the 

2 digit display reading is between -50 and 0°F. Pressing button 

PB1

 

at any time will cause the 2 digit display to show the leaving liquid 

temperature as read by the controller.

2.

  Pressing  button 

PB2

  at  any  time  will  cause  the  2  digit  display  to 

show the superheat as read by the controller. The 2 digit display read-

ing is between 0 to 99°F. Pressing button 

PB2

 at any time will cause 

the 2 digit display to show the superheat as read by the controller.

3. 

Pressing buttons 

PB1

 and 

PB2

 simultaneously at any time will cause 

the 2 digit display to show the suction pressure as read by the control-

ler. The red LED is the 100’s digit. If the red LED is off, the 2 digit 

display reading is between 0 to 99 PSIG. If the red LED is on, the 2 

digit display reading is between 100 and 153 PSIG.

4.

   Whenever the controller is in pumpdown or defrost, the 2 digit will 

display 

dF

.

5.

   Pressing and holding buttons 

PB1

 and 

PB2

 simultaneously until the 

green LED starts blinking will cause the 2 digit display to show the 

leaving liquid temperature set point. While the green LED is blink

-

ing,  pressing 

PB1

  will  increment  the  set  point  by  1°F.  While  the 

One Digital Input

One Pressure 

Input

One Valve Input

Two Temperature

Inputs
Two Set Point 

Pushbuttons

Holders for 

Optional Fail

Safe Batteries

Two Digit

LED Display

Green

Status LED

Red Status LED

Panel Display Jack

24 Volt AC

50/60 Hz.

40 VA Input

Figure 1

Terminals for Valve 1 shown.

SUBCOOL-O-MATIC

MECHANICAL SUBCOOLER CONTROLLER 

Installation and Servicing Instructions

CONTROLLER

TERMINAL

OLD PIGTAIL 

LEADS

NEW HERMETIC 

CABLE

1+ or 2+

Red

Black

1- or 2-

Black

Green

1S or 2S

Green

White

Table 1