5.4 Cycling menu
Parameter table “CYC”
Code Defi nition
Default
Min
Max.
MOd
ON = energy saving enabled
OFF = energy saving disabled
ON
ON
OFF
For choosing the set proceed as follows (or see the fl ow chart):
Press buttons
set
and
esc
toghether to enter on submenu.
Using buttons
and
select “Par” and press
set
to confi rm.
Using buttons
and
select “CYC” and press
set
to confi rm.
It appears the code “ MOd” press
set
to confi rm.
Using buttons
and
change the value and press
set
to confi rm.
Press
esc
to exit.
5.5 Alarm menu
Parameter table “ALL”
Code Defi nition
Default
Min
Max.
ALC
relay alarm/warning
ON
-
-
OFF = relay energised for alarms/warnings
ON = relay energised only alarms
For choosing the set proceed as follows (or see the fl ow chart):
Press buttons
set
and
esc
toghether to enter on submenu.
Using buttons
and
select “Par” and press
set
to confi rm.
Using buttons
and
select “ALL” and press
set
to confi rm.
It appears the code “ ALC” press
set
to confi rm.
Using buttons
and
change the value and press
set
to confi rm.
Press
esc
to exit.
Flow Chart
set
esc
Par
CF9
VER
CYC
set
dON
esc
CHd
dOFF
ON
120
5
PASS
SOFt
rE
SUP
1
0
OFF
1.0
esc
ALL
ALC
set
esc
esc
set
esc
set
esc
set
esc
set
esc
set
set
esc
ON
set
esc
set
esc
set
esc
set
esc
TIME
esc
MOd
ON
set
esc
set
5.6 Alarms/Warnings
Warnings
When a warning is ON, the “warning code” fl ashing on display.
When the nominal conditions return, automatically the warning code dis-
appears.
Alarms
When an Alarm is ON, the “Alarm code” fl ashing on display together the
alarm symbol
, the block of the machine depending on the severity
fo the alarm.
For multiple alarms only the last condition appears on the display.
Alarms/Warnings Table
Name Code
Description alarm / warning
Reset Dryer
H
-
Warning High Dew point
A
ON
L
-
Warning Low Dew Point
A
ON
P1
ER01
Warning evaporator sensor fault /dis-
connected
A
ON
P3
ER03
Warning pressure transducer fault/
disconnected
A
ON
HdP
ER07
Alarm High Dew point
M
OFF
LdP
ER08
Alarm Low Dew Point
A
OFF
EXT
ER11
Alarm external (remote)
M
OFF
Aldi
-
Alarm High pressure
Alarm High Compressor Discharge
Temperature
M
OFF
A=Automatic; M=Manual.
Press the button
esc
for a few seconds to reset manually, the alarm
code and the alarm symobl
must disappear.
Alarm History
In order to see which and how many alarms have occurred you have to
follow the following sequence (or see the fl ow chart):
In alarm/warning situation.
Press
set
to enter on “ALHi”.
Press
to choose “AL” and press
set
to enter.
Press
and
to see the alarms.
Press
esc
to exit.
Содержание SPE026-ES
Страница 2: ......
Страница 122: ...6 6 SPE026 100 ES 7 SK HT 122 F 50 C PV...
Страница 131: ...8 5 EXPLODED DRAWING 9 6 SPE026 100 ES...
Страница 134: ...8 7 REFRIGERANT CIRCUIT 12 6 SPE026 100 ES 156 192 240 312 372 480 600 26 62 26 62 52 100 52 100 80 100 80 100...
Страница 135: ...8 8 WIRING DIAGRAM 13 6 SPE026 100 ES 70...
Страница 136: ...8 8 WIRING DIAGRAM 14 6 SPE026 100 ES 026 040 156 240 026 040 312 600...
Страница 137: ...8 8 WIRING DIAGRAM 15 6 SPE026 100 ES...
Страница 138: ...8 8 WIRING DIAGRAM 16 6 SPE026 100 ES option...
Страница 139: ......