background image

 
 

(1) Dew Point Controller and Display.  Directly controls dew point and provides 

consistent digital display of the dew point.  Factory set at 38ºF.  During Actual 

display mode, displays the dew point temperature from 20ºF to 99ºF or -6ºC to 
37ºC.  During DP SET mode, the unit displays dew point set points from 36ºF to 

50ºF in 2º steps or 1ºC to 10ºC in 1/2º steps.  (NOTE – the ones digit decimal 
point is used to indicate 1/2º when displaying set point is used in the Celsius 

scale).  ºC LED indicates the display is in Celsius.  ºF LED- indicates the 
temperature display in Fahrenheit.  ACTUAL LED – shows actual temperature 
being measured by system.  DP SET LED – INDICATES that the display is in 

programming mode during which the set point can be changed and stored.  The 
dew point display also displays the unit error codes when they occur (See 

Diagnostic Codes). 

 

(2)  On / Off Button for Load/No Load mode.   When LED is on, this indicates 

when the unit is in the Load/No Load Mode. 

 

(3)  On / Off Button for Thermal Bank Mode.  Thermal Bank LED indicates when 

the unit is operating the thermal bank mode. 

 

(4) Raise / Lower Buttons.  These are used adjust the set point values.  The set 

point will change once for each time pressed.   If the button is pressed and 

held, the set point will change one step per second. 

 

(5)  Set Button.  Toggles between Actual Display mode and Set Point mode.  

During the Set Point Display mode, the Raise and Lower keys are used to select 

new set points which are stored in non-volatile memory when the mode is set 
back to ACTUAL.  If no keys are pressed within 15 sec., the mode is 
automatically set to ACTUAL.  This switch is also used to select the temperature 

scale that the unit will operate in by pressing and holding for 15 sec.  (The unit 
will toggle between ºF and ºC) 

 
(6)  Hidden Button.  Positioned at the bottom center of the Dew Point window 

between the Mode keys.  When, pressed, the display will show the external 
suction temperature at the expansion bulb.  It has no further effect on 

operation.  It may also be used for other diagnostics and factory test purposes. 

 

(7)  Power Saver Active LED.  Unit in mode of low power consumption.  

Refrigeration system unloaded or in thermal banking condition. 

 
(8)  High Dew Point Alarm LED.  Indicates that the unit is in High Dew Point 

condition.  The high dew point alarm light with remote dry contacts, will 
activate when the actual dew point is 15ºF higher than the dew point set point.   

Any diagnostic code will activate the high dew point alarm immediately. 

 

 
 
 

 
 

 
 

Содержание SC80

Страница 1: ...Airtek Division SMART CYCLE COLD TRAP REFRIGERATED AIR DRYERS OPERATORS MANUAL MODELS SC CT80 SC CT3000 SERVICE DEPARTMENT 1 800 451 6023...

Страница 2: ...ection 5 0 SENSORS CONTROLS RELAYS Section 6 0 START UP PROCEDURE Section 6 0 ROUNTINE MAINTENANCE Section 7 0 DIAGNOSTIC CODES Section 8 0 TROUBLE SHOOTING Section 9 0 MAINTENACE SCHEDULE Section 10...

Страница 3: ...ase Heate r WATTS Crankcase Heater Voltage VOLT Number of Fans Fan Motor Horse Power HP Max Amp Draw AMPS copper THHN Wire Size AWG Fuse Size AMP enter n a if not used Nema Starter Size PART Overload...

Страница 4: ...ure between 50 95 F 10 35 C and free from explosive and corrosive fumes Three 3 feet 92cm of space must be allowed between all open grills walls or other objects Where ambient temperatures may periodi...

Страница 5: ...zed when the refrigeration suction gauge reads between 28 to 35 PSI Plumbing the Air Lines The dryers are shipped ready to run All connections are made to the outside of the cabinet Air piping must be...

Страница 6: ...a bypass line and gate valve to permit isolation of the dryer from the air system This is done to provide easy service and or removal of the dryer without interruption of air to the system Fig 2 Model...

Страница 7: ...c box cover from inside unit 2 Locate the wires 3 Locate hole on side of box place and tighten connector run wires through connector 4 Using wire connectors connect Black to Hot wire White to Neutral...

Страница 8: ...Section 4 0 Controls REFRIGERANT DRYER CONTROLLER FEATURES AND OPERATIONS 5 1 4 8 10 2 6 3 7 9...

Страница 9: ...s The set point will change once for each time pressed If the button is pressed and held the set point will change one step per second 5 Set Button Toggles between Actual Display mode and Set Point mo...

Страница 10: ...every 30 minutes independent to the float signal The 30 minute timed intercal setting can be adjusted down to 1 minute or raised up to 60 minutes if desired To adjust the drain Timed Interval setting...

Страница 11: ...ter cooled units 13 High Inlet Temp Display Should not be above 100 F High inlet air temp can cause overloading of dryer If lit check compressed air after cooler and or oil cooler on air compressor 12...

Страница 12: ...lay and LED alarm turns on when the dew point is 15 F above the set point This is also active during any error conditions Compressor Unloader 1 Relay CU1 FU Panel Only Turns on when the dew point is b...

Страница 13: ...panel from unit 4 Some units are shipped with the refrigeration service valve tagged These tagged service valves must not be opened until the dryer is ready to be started and the main power is perman...

Страница 14: ...ow introduce compressed air to the dryer 11 Check the automatic drain for proper operation Drain should open at regular intervals based on the drain control settings Clean Y Strainer after the first 8...

Страница 15: ...ant charge See tag for correct refrigerant charge Unit needs to be pulled into vacuum 500 micron minimum Unit needs to be pulled into vacuum 500 micron minimum The full charge might not be accepted If...

Страница 16: ...tu ua al l d de ew w p po oi in nt t f fa al ll ls s t to o 2 20 0 F F o or r l lo ow we er r U Un nl lo oa ad de er r v va al lv ve e f fa ai il li in ng g t to o o op pe en n R Re ep pl la ac ce e E...

Страница 17: ...e Contact the factory for verification prior to proceeding with this maintenance item MAINTENANCE PROCEDURES Before performing any maintenance on the machine ensure that air pressure is vented from th...

Страница 18: ...bonnets then need to be removed exposing the tube side of the condenser The tube side should be inspected for any debris and cleaned If soft deposits are found they can be cleaned using a pneumatic t...

Страница 19: ...ated by the On Time dial Removing and reapplying power will again actuate the timing cycle Second pushing the test button will actuate the valve for as long as the button is pressed Third once the tim...

Страница 20: ...Section 11 0 MAINTENANCE CHARTS Maintenance Log Date Service Performed Parts Replaced Initials...

Страница 21: ...Section 11 0 MAINTENANCE CHARTS cont Element Replacement Log Part No Date Initials...

Страница 22: ...Section 12 0 ASSOCIATED DRAWINGS...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ...om FINAL OPERATION CHECK LIST Inlet air temperature is Inlet PSIG is The dew point temperature controller reads between and Air compressor HP or Max SCFM is Is the dryer a minimum of 3 from any struct...

Страница 39: ......

Отзывы: