Parker RAC Europe
PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 35 of 74
7.8
List of configuration parameters
The following is a complete list of parameters managed by the application, each with a short code, the ModBus address
(Adr), brief description, default values and limits, measurement units (U), the menu in which they are accessed (M)
and the notes.
The menus are split into levels: U (User), I (Installer, protected by first-level password), M (Manufacturer, protected
by the second level password.
All the parameters in the User menu are freely modifiable and their modification is immediately applied. The Installer
parameters are usually loaded by the application only when the machine is in the
Stand-by off
(10), and can be
changed only in this state. The Manufacturer parameters are the most low-level and are usually loaded by the
application only at the start-up, can be modified only in the
Stand-by off
(10) and requires a reset to load the new
value.
The variable
Parameters status
(ParS) indicates that the modified parameters have been acquired but are not currently
in use. To finalize the acquisition, it is necessary to reset or disable the valve. If the variable is set to 0, it means that
the new parameters are already active.
The correct procedure for changing Installer and Manufacturer parameters is:
•
disable the valve
•
modify the parameters
•
verify the
Parameters status
(ParS) value
•
reset the board if requested by Parameters status (ParS)
Par.
Min.
Max.
Units
Default
Menu
Control mode choice
Pcty
0
7
- - - -
7
I
main control type
0 = none
1 = analog positioner on AI1 (0-20
mA)
2 = analog positioner on AI2 (4-20
mA)
3 = analog positioner on AI3 (0-5 V)
4 = analog positioner on AI4 (0-10
V)
5 = analog positioner on AI4
6 = SH
control
SetP
1
2
- - - -
1
U
SH parameters set selection
1 = parameters set n. 1
2 = parameters set n. 2
Par.
Min.
Max.
Units
Default
Menu
Parameters set n. 1
Pc01 3.0 25.0
K
6.0
User SH
setpoint
Pc02 1.0 3.0
K
2.0
User LoSH
setpoint
Pc03 10.0 40.0
K
15.0
User HiSH
setpoint
Pc04
-200.0
40.0
°C
40.0
User
Set1 LOP temperature
Pc05 -40.0 40.0
°C
40.0
User MOP
temperature