Parker RAC Europe
PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 32 of 74
According to the factory setting the address of the CAN node of an electronic expansion valve driver has value
11
(therefore operate on the interface to set parameter
NW Node
to
[ 1 ] 11
).
12.
Switch off the power supply of the interface.
13.
Switch on the power supply of the interface.
14.
Keep pressed 2 s buttons LEFT and ENTER: the display will show the following menu.
Network Status
Loc 99 OK > >
1 11
OK
>
>
2 0 - >
>
3 0 - >
>
4 0 - >
>
5 0 - >
>
15.
Press and release button UP or button DOWN to select the device.
16.
Press and release button ENTER: the display will show page 1 of the device.
17.
Operate as shown in paragraph 7.2 “Configuring a built-in version”.
7.4
Configuring the device through the programming key
PSKEY10
The following procedures shows how to upload and download the configuration parameters by using the programming
key PSKEY10.
To copy the parameters from the device to the programming key PSKEY10 operate as follows:
1.
Make sure the power supply is switched on.
2.
Connect the key to the device; look at paragraph 10.1.4 “Connection to the device”.
3.
With reference to step 28 of the paragraph 7.2 "Configuring a built-in version", from page 37 press button UP
or button DOWN to select “
key
” to copy the parameters in PSKEY10 or “
memory
” to copy the parameters in
the internal memory of the device, belonging to the field “
Application param.
” to copy the application
software parameters or belonging to the field “
Drivers param
”. to copy the configuration parameters.
4.
Press and release button ENTER: the parameters will be copied (this operation usually takes a few seconds; the
last line of the page provides information on the status of the process).
5.
Disconnect the programming key.
To copy the parameters from the programming key PSKEY10 to the device operate as follows:
6.
Make sure the power supply is switched on.
7.
Connect the key to the device; look at paragraph 10.1.4 “Connection to the device”.
8.
With reference to step 28 of the paragraph 7.2 "Configuring a built-in version", from page 38 press button UP
or button DOWN to select “
key
” to copy the parameters from PSKEY10 or “
memory
” to copy the parameters
from the internal memory of the device, belonging to the field “
Application param.
” to copy the application
software parameters or belonging to the field “
Drivers param
”. to copy the configuration parameters.
9.
Press and release button ENTER: the parameters will be copied (this operation usually takes a few seconds; the
last line of the page provides information on the status of the process).
10.
Disconnect the programming key.