P2M2HBVT12400

User Manual

30060921401W05 

February 2018

Pneumatic Division

27031 Evreux - France

Process Data Outputs

The 24 solenoids are represented by one bit each and they are grouped in 3 Bytes. The LSB (Least Significant
Bit) is associated with Solenoid-1 and the MSB (Most Significant Bit) is associated with Solenoid-24.

Byte  

3 (Index 0x2001 | Subindex 0x03)

2

1 (Index 0x2001 | Subindex 0x01)

Bit #  

23 (MSB)

22

21

2

1

0 (LSB)

Example 

Output Data

1

0

1

0

1

0

Controlled 

Output 

Out_23 

HIGH

Out_22

LOW

Out_21 

HIGH 

Out_2

LOW

Out_1

HIGH

Out_0

LOW

Solenoid 

Energized

Solenoid_24 

ON

Solenoid_23 

OFF

Solenoid_22 

ON

Solenoid_3 

OFF

Solenoid_2 

ON

Solenoid_1 

OFF

Index 

Data Type   Subindex

Access  

Name  

Min Value  

Max Value

Default

0x2008  

USINT

0x00

Read / Write 

System Command

0

0xFF

0

Manufacturer Specific Object

“System Command”

The Manufacturing Specific Object

“System Command”

is used for specific functions, such as:

“Leave

Failsafe /

Error

Acknowledgment”

and

“Store

Switching Cycles

Counters”,

as detailed in the table below. In order to

execute the desired function the specific value associated with the command has to be written in the Object.

Command Value

Command Name

Description

0x01

Leave Failsafe State

(Acknowledge Error)

This command allows the module to leave failsafe state*
(acknowledge error). Meaning that, if no error is pending
at the time the Leave Failsafe State command is executed,
then the device returns to normal operation and the
outputs are set according to process data.

* If Failsafe state is reached, then it is not automatically left if the error

conditions are no longer existent.

0X02

Store Switching Cycle Counters

When this command is executed, the current values of
the switching cycle counters are stored into EEPROM. This
command is intended to be used before powering off the
device.

The System Command Byte supports the commands as defined in the table below.

Status / Diagnostic Data and Parameters

Index 

Data Type  

Subindex

Access  

Name  

Min Value  

Max Value

Default

0x2002  

Array of 

UDINT 

0x01 to 0x18

Read

Switching Cycles

0

*

0

Manufacturer Specific Object

“Switching Cycles”

The Manufacturing Specific Object

“Switching Cycles”

contains the 24 switching cycle counters for the valves.

The counters values are automatically stored by the module every 30 minutes.

* Max value for each counter is circa 4,3 billion (UDINT max representable value). Once that the max value is 
reached, this is held in memory and additional cycles are not recorded.

Содержание P2M Node 24 DO

Страница 1: ...USER MANUAL P2M Node 24 DO P2M2HBVT12400 ...

Страница 2: ...e 2 15 P2M2HBVT12400 User Manual 30060921401W05 February 2018 Pneumatic Division 27031 Evreux France EtherCAT is a registered trademark and patented technology licensed by Beckhoff Automation GmbH Germany ...

Страница 3: ... Power Management 09 Power supply diagnostic through LED 09 Power supply diagnostic thought Network 09 Auxiliary voltage reading 09 Auxiliary power supply range adjustment Rotary Switches 10 P2M Node 24 DO Configuration File 10 Mapping of I O Process Data 10 Process Output Data Mapping 10 Process Input Data Mapping 10 Manufacturer Specific Objects 11 Process Data Outputs 11 Manufacturing Specific ...

Страница 4: ...O 15407 2 and 5599 2 Valves Series Depending on the valve series the module is connected to it can control up to 24 pilot solenoid valves as shown on the illustration below For details on appropriate valve adaptor to use please refer to the respective valve series technical catalogue and instruction sheets Module assembly disassembly 2 4 3 5 To disassemble follow steps backward 1 Product general o...

Страница 5: ...o IEC 60068 2 6 2007 EMC According to EN 55011 EN 61000 4 2 up to 4 6 Auxiliary power consumption calculation Depending on the valve range the module is connected to the pilot solenoids differ in power consumption In order to determine the minimum required power to supply the table below may be used Technical Data P2M Node 24DO electrical specifications NOTE it is recommended that the total output...

Страница 6: ...lve Series can handle up to 24 pilot solenoid valves Addressing is as shown below Byte 1 EV08 EV01 PLC Process outputs data mapping Byte 2 EV16 EV09 Byte 3 EV24 EV20 EV19 EV17 Byte 3 Bits 3 to 7 are not connected to valves with Moduflex Valve Range Byte 1 EV08 EV01 0 7 PLC Process outputs data mapping Byte 2 EV16 EV09 Byte 3 EV24 EV17 EV01 EV02 EV03 EV04 EV05 EV06 EV07 EV08 EV09 EV10 EV11 EV12 EV1...

Страница 7: ...dard Female M12 D Coded connectors 4 pins Auxiliary Power Supply Standard Male M12 A Coded connector 4 pins Use of standard manufactured cables available from usual electrical supplier is recommended Out In Power The P2M Node 24DO Auxiliary Power for valves can be supplied from a SAFE 24Vdc auxiliary source in PP or PM mode as well as from Output Switching Signals Device Failsafe Digital Outputs O...

Страница 8: ...l Visual Diagnostic The P2M Node 24DO module offers local diagnostics through 6 LED s status with interpretation described in the table below NOTE Errors caused by solenoid s must be fixed first and then the error must be acknowledged by either one of the following actions switching OFF ON Auxiliary power supply once error is fixed sending the Acknowledge Error command SEE Manufacturing Specific O...

Страница 9: ...ly diagnostic through Network and Process Data mapping Index Data Type Access Name Min Value Max Value Default 0x200B UINT Read Write AUX Voltage Warning Low Limit 18000 24000 20000 0x200C UINT Read Write AUX Voltage Warning High Limit 24000 28500 26400 Auxiliary power supply range adjustment Normal auxiliary power supply voltage range is set by default as 20 0V Aux power supply 26 4V The low and ...

Страница 10: ...ss Output Data Mapping RPDO Byte Mapped Object Index Sub Index Name 0 0x2008 0x00 System Commands 1 0x2001 0x01 Solenoids Channel 1 to 8 2 0x2001 0x02 Solenoids Channel 9 to 16 3 0x2001 0x03 Solenoids Channel 17 to 24 Process Input Data Mapping TPDO Byte Mapped Object Index Sub Index Name 0 0x2009 0x00 Module Error Input LSB 1 Module Error Input MSB 2 0x2006 0x01 Channel Error Channel 1 to 8 4 0x2...

Страница 11: ...RO Module Error 0x2006 0x00 USINT RO Number of Entries 0x03 0x2006 0x01 USINT RO Channel Error Channel 1 to 8 0x2006 0x02 USINT RO Channel Error Channel 9 to 16 0x2006 0x03 USINT RO Channel Error Channel 17 to 24 0x2007 0x00 UINT RO Module Info Flags 0x2008 0x00 USINT RW System Commands 0x2009 0x00 UINT RO Module Error Input 0x200B 0x00 UINT RW AUX Voltage Warning Limit Low 0x200C 0x00 UINT RW AUX...

Страница 12: ...he Object Command Value Command Name Description 0x01 Leave Failsafe State Acknowledge Error This command allows the module to leave failsafe state acknowledge error Meaning that if no error is pending at the time the Leave Failsafe State command is executed then the device returns to normal operation and the outputs are set according to process data If Failsafe state is reached then it is not aut...

Страница 13: ... Specific Object Manufacturer Specific Object AUX Voltage Warning Low Limit This Manufacturing Specific Object contains the value for the AUX Voltage Warning Low Limit in millivolts i e the low AUX Voltage value that will trigger the AUX Voltage Warning diagnostic Values shown in mV Manufacturer Specific Object AUX Voltage Warning High Limit This Manufacturing Specific Object contains the value fo...

Страница 14: ...dule states and faults errors that might affect the module The faults identified in the module error flag are not recoverable therefore a power cycle is required to clear them If the faults are still present following a power cycle the module has to be replaced The message headers and flag definitions associated with each bit in the Manufacturing Specific Object are detailed in the table below Man...

Страница 15: ...range 2 AUX Voltage Error Set if the Auxiliary Voltage is outside Warning and within Error range The outputs are switched off and an acknowledge is required to restart the module 3 Temperature Warning Set if a temperature warning in one of the output driver chips is detected Outputs are switched off and an acknowledge is required to restart the module 4 Output Driver Channel Error Set if an over c...

Страница 16: ...acturing France SAS Pneumatic Division Europe Parc d Activités de la Forêt BP 3124 534 rue Henri Becquerel 27031 EVREUX CEDEX FRANCE P2M Node 24DO User Manual UK30060921401W05 Release February 2019 www parker com pde P2M_IE ...

Отзывы: