OEM6250 Installation Guide
OUTPUT CONNECTIONS (includes OUT-A & OUT-B) —
for electronic devices such as PLCs
Connection to a Sinking Input (active high)
Connection to a Sourcing Input (active low)
Electronic
Device
Output
Connection
Ground
Connection
Input
Ground
OUT-P
+5V
GND
OEM6250
7406
GND
GND
(open collector)
+5VDC
R13
(0 K
W
)
is removed.
4.7 K
W
External Supply
(up to 24VDC)
+
–
Electronic
Device
Output
Connection
Ground
Connection
Input
Ground
OUT-P
+5V
GND
OEM6250
GND
GND
(open collector)
V+
7406
+5VDC
External Supply
(up to 24VDC)
+
–
R13
(0 K
W
)
is removed.
4.7 K
W
Connection to a Combination of Sinking & Sourcing Inputs
Combinations of sourcing
and sinking inputs can be
accommodated at the same
voltage level. Be aware of
the input impedance of the
sourcing input module, and
make sure that there is
enough current flowing
through the input module
while in parallel with the
OUT-P pull-up resistor.
Electronic
Devices
Output 1
Input
Ground
OUT-P
+5V
GND
OEM6250
4.7 K
W
GND
External Supply
(up to 24VDC)
+
–
V+
Output 2
Ground
Connection
Input
Ground
4.7 K
W
GND
Sourcing Input
Sinking Input
(open collector)
7406
(open collector)
7406
R13
(0 K
W
)
is removed.
+5VDC
Connection to an Inductive Load (active low)
Output
Connection
OUT-P
+5V
GND
OEM6250
4.7 K
W
GND
Use an external diode when driving
inductive loads. Connect the diode in
parallel to the inductive load,
attaching the anode to the OEM6250
output and the cathode to the supply
voltage of the inductive load, via an
external resistor. To size the external
resistor, use this formula:
(open collector)
7406
R13
(0 K
W
)
is removed.
+5VDC
External Supply
(up to 24VDC)
+
–
R
EXTERNAL
R
INDUCTANCE
V
CC
R
EXTERNAL
+ R
INDUCTANCE
£
30mA
V
CC
PROGRAMMING TIP
Connecting to an active-
high sinking input? Set
the output’s active level to
high with the
OUTLVL
command
(
1
= active high).
Connecting to an active-
low sourcing input? Set
the output’s active level to low
with the
OUTLVL
command
(
¯
= active low).
Thus, when the OEM6250’s
output is activated, current will
flow through the attached
input and the
TOUT
status
command will report a “
1
”
(indicates that the output is
active), regardless of the type
of input that is connected.
Details on setting the active
level and checking the output
status are provided in the
6000 Series Programmer’s
Guide. Refer also to the
OUTLVL
and
TOUT
command
descriptions in the
6000
Series Software Reference.