13
DME012-RX - DME080-RX
The equipment should be connected to the electrical supply through a switch or circuit breaker. This device should be clearly and indelibly
marked as the disconnecting device for the equipment and located in close proximity to the equipment and be easily accessible to the
operator.
Overcurrent protection must be fitted as part of the building installation. This protection should be selected in accordance with local and
national code regulations and based upon the technical data supplied for this equipment.
3.3.2 Hygrometer relay
The dryer is supplied with a 3 core non-detachable hygrometer relay cable as identified below.
Warning
The mains supply cable and hygrometer relay cables are clearly identified at the cable gland. Ensure that
the correct cable is selected prior to continuing the installation
1
2
HYGROMETER
DEWPOINT
RELAY
For correct operation of the DDS system, conductors 1 and 2 should be connected across a set of volt free contacts as shown.
When in operation, the contacts should close when the dewpoint reaches the set point and remain closed until the moisture
content rises above the set point.
Note: The dryer has an internal moisture over-ride which has been factory set at 30 minutes. This means that the dryer will revert
to normal operation after 30 minutes regardless of the dewpoint.