Control Connections for Local Control
Refer to the Installation Diagram
Control wiring must have a minimum cross-section area of 0.75mm
2
(18AWG)
Use screened control cables to comply with EMC requirements
Current Limit
(fixed)
A6
B3
Connection to allow the MAIN CURR. LIMIT parameter to adjust the current limit.
Program Stop/
Coast Stop
B8
B9
C9
Removing B8 from C9 (24V) causes a Program Stop (regenerative drive only)
Removing B9 from C9 (24V) causes a Coast Stop
The Emergency Stop relay (normally-open, delay on de-energisation) is not sequenced via
the drive. It is a separate control feature.
Enable
C5
C9
The contact between terminals C5 (ENABLE) and C9 must be closed for the drive to run.
External Trip
C1
C2
Terminals C1 and C2 must be linked for the drive to run
(External Trip interlock not required in this simple set-up).
Clean Earth
A1
Via the clean earth rail which originates directly from the main incoming earth rail.