Mechanical Installation
NOTE
Refer to the Safety and EMC sheets provided with the drive.
Mount the unit vertically inside a suitable cubicle. Drill mounting holes accurately.
Check for material that could damage/restrict operation.
Fit 4 x inserts into the back panel
Fit bolts/washers loosely into lower inserts
Engage the drive's lower mounting slots onto the bolts
Fit the top bolts and tighten - M5 : 2.7Nm (2 ft.lbf), M6 : 4.5Nm (3.3 ft.lbf)
Ventilation
The Drive gives off heat during normal operation and requires:
Adequate cooling air to enter and exit the cubicle
Free flowing air through the drive's ventilation slots and heatsink
A normally cool mounting surface
Minimum air clearances to be maintained above and below drives and other
equipment (additive when two units are mounted together)
Frame
Current
Rating
(A)
Weight Kg
(lbs)
Overall Dimensions
Fixing Centres
Fixin
g
Air Clearance
(above&below)
Width
Height
Depth
Width
Height
1
20
5.2 (11.4)
170(6.69) 415(16.34)
175(6.9)
140(5.51)
400(15.75)
M5
100(3.94)
35-45
7.2
(
15.8
)
170(6.69) 415(16.34)
202(7.95) 140(5.51)
400(15.75)
M5
100(3.94)
2
75
8.3
(
18.2
)
170(6.69) 439(17.28)
202(7.95) 140(5.51)
400(15.75)
M5
100(3.94)
110-165 10.4
(
22.8
)
170(6.69) 439(17.28)
240(9.45) 130(5.12)
400(15.75)
M5
100(3.94)
Dimensions are in millimetres (inches)
mm (inches)
1
Keypad
2
Speed Feedback Option
3
Communications Option
4
USB Port
5
Control Terminals
6
Power Terminals
7
Drive Earth/Ground
(Frame 1 illustrated)
1
2
3
4
5
6
7