Mechanical Installation 

NOTE 

 

Refer to the Safety and EMC sheets provided with the drive. 

Mount the unit vertically inside a suitable cubicle. Drill mounting holes accurately.  
Check for material that could damage/restrict operation. 

 

  Fit 4 x inserts into the back panel 

  Fit bolts/washers loosely into lower inserts 

  Engage the drive's lower mounting slots onto the bolts 

  Fit the top bolts and tighten - M5 : 2.7Nm (2 ft.lbf), M6 : 4.5Nm (3.3 ft.lbf) 

Ventilation 

The Drive gives off heat during normal operation and requires: 

  Adequate cooling air to enter and exit the cubicle 

  Free flowing air through the drive's ventilation slots and heatsink 

  A normally cool mounting surface 

  Minimum air clearances to be maintained above and below drives and other 

equipment (additive when two units are mounted together)  

Frame 

Current 

Rating 

(A) 

Weight Kg 

(lbs) 

Overall Dimensions 

Fixing Centres 

Fixin

Air Clearance 

(above&below) 

Width 

Height 

Depth 

Width 

Height 

 

20 

5.2 (11.4) 

170(6.69)  415(16.34) 

175(6.9) 

140(5.51)

 

400(15.75)

 

M5 

100(3.94) 

35-45 

7.2

15.8

  170(6.69)  415(16.34) 

202(7.95)  140(5.51)

 

400(15.75)

 

M5 

100(3.94) 

 

75 

8.3

18.2

  170(6.69)  439(17.28) 

202(7.95)  140(5.51) 

400(15.75) 

M5 

100(3.94) 

110-165  10.4

22.8

  170(6.69)  439(17.28) 

240(9.45)  130(5.12) 

400(15.75) 

M5 

100(3.94) 

 

 

Dimensions are in millimetres (inches)

 

 

mm (inches)

 

Keypad 

Speed Feedback Option 

Communications Option 

USB Port 

Control Terminals 

Power Terminals 

Drive Earth/Ground 

(Frame 1 illustrated) 

 

Содержание DC590PR Series

Страница 1: ...ne Provided with every Drive is a QuickStart Safety Information Compact disk containing the Product Manual and Configuration Tool Keypad optional Option cards optional This QuickStart assumes that You...

Страница 2: ...nd heatsink A normally cool mounting surface Minimum air clearances to be maintained above and below drives and other equipment additive when two units are mounted together Frame Current Rating A Weig...

Страница 3: ...ed for all signal and control cabling Motor Earth Ground Connect an earth ground wire to the motor from the dirty earth ground rail Connect shield between the motor and dirty earth ground rail Drive E...

Страница 4: ...Rail A 1 Pole MCB B Control Transformer C 2 Pole MCB D Fan Fuses E Motor Overload Protection F Emergency Stop Relay G Isolated Motor Thermistor M Motor Permanent Earthing The unit must be permanently...

Страница 5: ...C9 24V causes a Program Stop regenerative drive only Removing B9 from C9 24V causes a Coast Stop The Emergency Stop relay normally open delay on de energisation is not sequenced via the drive It is a...

Страница 6: ...Power Connections Refer to the Installation Diagram Minimum rating of 1 1 x full load current Europe Minimum rating of 1 25 x full load current UL...

Страница 7: ...the drive is powered on and the P code may need to be reset Auxiliary Supply AL1 AL2 Single phase 110 240V ac 50 60Hz Match auxiliary supply to the contactor coil voltage Protect with external fuses d...

Страница 8: ...SOLATE THE DRIVE using branch circuit protection or circuit breaker 8 Disconnect the load from the motor shaft if possible If there is any doubt about the integrity of a particular installation insert...

Страница 9: ...plate ARMATURE CURRENT Enter the armature current value IA CAL from the motor rating plate FIELD CURRENT Enter the nominal field current IF CAL from the motor rating plate FLD CTRL MODE Check that th...

Страница 10: ...The main contactor should never be operated by any means other than the drive s internal controls nor should any additional circuitry be placed around the contactor coil circuit Press the Start key o...

Страница 11: ...lied to the power terminals L1 L2 and L3 Check the correct field voltage appears between the field output terminals F and F If the Field Voltage is incorrect do not continue Switch off all supplies an...

Страница 12: ...ne the drive 4 Autotuning This process tunes the drive to the connected motor Initial conditions must be Main contactor open i e Stop key pressed Program Stop terminal B8 and Coast Stop terminal B9 hi...

Страница 13: ...lication specific CHAPTER 3 Connection Diagrams Control Connections Optional Equipment Motor Field current range switch selection SW1 on power board CHAPTER 4 Selecting Speed Feedback Initial Start up...

Страница 14: ...TH 10K SETPOINT RAMPINPUT EMERGENCY STOPRELAY Speed Demand Uni directional A1 A4 B3 The 10K potentiometer adjusts the speed setpoint Zero speed Terminal A1 0V input Maximum forward speed 100 Terminal...

Страница 15: ...To check this 0 5V the Total Speed Setpoint can be measured at terminal A8 Analog Output 2 Start the drive by closing the Start Run contact C3 5 Slowly increase the MAIN CURR LIMIT parameter towards...

Страница 16: ...HP Internal Field Current supply A 1 Total Losses Full Load W Symm etrical Fault Curren t rms kA 45 20 20 7 5 5 102 57 5 45 20 20 10 5 102 57 5 45 35 35 15 5 102 57 5 45 35 35 20 5 102 117 5 45 45 45...

Страница 17: ...LV Build MV Build 220 500V ac 10 50 60Hz 5 line to line ground referenced TN and non ground referenced IT Supply Current Supply current due to armature 0 9 x Idc A ac rms Total ac rms current includin...

Страница 18: ...gle phase Overvoltage Category II 3A ac rms maximum Nominal current used for power supplies 0 5A at 110V ac 0 25A at 240V ac Contactor Output 3A maximum at the auxiliary voltage The drive is powered u...

Отзывы: