TROUBLESHOOTING
Dryer not operating; no lights on
- Blown control fuse: replace fuse.
- No power: apply correct power, verify quality of power source.
- Controller inoperative: replace controller.
- Control transformer defective: replace transformer.
- Program crashes: replace SD card.
Power light on, other lights off, dryer does not operate
- Cycle has not been initiated: press start button.
Dryer not operating; lights on, dryer does not switch
- Control air valve is closed: open control air valve; check condition of control air filter element.
- No air supply to dryer inlet: connect air supply.
- Dryer in Power Saving State: Disable Dewpoint Demand to go back to a standard timing cycle.
No heat in regenerating bed
- Regenerating tower will not blow down: dryer not sequencing or in dewpoint demand mode: see above.
- Bad output, solenoid, or exhaust: replace part or correct issue.
Dryer cycles, no heat
- Dryer in heatless backup mode: switch to heated mode and press start button.
- Overtemp shutdown engaged: Check setting and press reset; if overtemp shuts down dryer again
consult factory.
- Thermocouple disconnected or defective: reconnect or replace.
- Purge flow set to low: adjust purge setting to spec (TWP dryers only).
Insufficient Heat
- Low purge flow: adjust purge setting to spec (TWP dryers only).
- Clogged muffler: clean, replace, or remove.
- Moisture load too high: adjust dryer inlet air flow conditions to within spec.
- Defective thermocouple or controller: replace.
High Outlet Dewpoint or Moisture Downstream
- Dryer not cycling: see dryer not operating.
- Insufficient or no heat: see above.
- Incorrect purge rate: adjust purge setting to value specified on purge tag or manual.
- Capacity of dryer exceeded: adjust inlet flow rate, inlet air temperature, and inlet air pressure to within
specified operating conditions for the model.
- Liquid water present at dryer inlet: check water level in separators, receivers, prefilters, and operation of
associated y-strainers and auto drains. Check condition of filter elements or check differential
pressure gauges.
- Desiccant worn out, contaminated, or insufficient quantity: replace desiccant or add correct amount.
- Reduced regeneration: see
Back Pressure In Regenerating Tower
.
- Leaking bypass valve: replace valve.
- Undried air from another source mixing downstream of dryer: remedy.
Содержание Airtek TWB1000
Страница 1: ...1 Externally Heated Blower Purge Desiccant Dryers User Manual Models TWP TWB200 TWP TWB9000...
Страница 9: ...TWP TWB200 TWP TWB9000 9 TWP Desiccant Dryer Operation TWB Desiccant Dryer Operation...
Страница 10: ...TWP TWB200 TWP TWB9000 10 FLOW SCHEMATIC MODELS TWP200 300 DWG FS11682 Rev...
Страница 11: ...TWP TWB200 TWP TWB9000 11 FLOW SCHEMATIC MODELS TWP400 800 DWG FS11683 Rev...
Страница 12: ...TWP TWB200 TWP TWB9000 12 FLOW SCHEMATIC MODELS TWP1000 1500 DWG FS11684 Rev...
Страница 13: ...TWP TWB200 TWP TWB9000 13 FLOW SCHEMATIC MODELS TWP2000 9000 DWG FS11685 Rev...
Страница 14: ...TWP TWB200 TWP TWB9000 14 FLOW SCHEMATIC MODELS TWB200 800 DWG FS11686 Rev...
Страница 15: ...TWP TWB200 TWP TWB9000 15 FLOW SCHEMATIC MODELS TWB1000 1500 DWG FS11687 Rev...
Страница 16: ...TWP TWB200 TWP TWB9000 16 FLOW SCHEMATIC MODELS TWB2000 9000 DWG FS11688 Rev...
Страница 17: ...TWP TWB200 TWP TWB9000 17 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 18: ...TWP TWB200 TWP TWB9000 18 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 19: ...TWP TWB200 TWP TWB9000 19 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 20: ...TWP TWB200 TWP TWB9000 20 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 21: ...TWP TWB200 TWP TWB9000 21 PANEL LAYOUT STANDARD CONTROLLER...
Страница 38: ...TWP TWB200 TWP TWB9000 38 Service Screen...
Страница 71: ...TWP TWB200 TWP TWB9000 71...