TWP/TWB200 – TWP/TWB9000
51
MODBUS REGISTER MAP (CONT’D)
40069
R/W
Control Setting - Variable Cycling Time Enable
1 = Enable dewpoint demand function
40070
R/W
Control Setting - Extended Dry Purge
1 = Enable 2% dry purge feature, Blower model only
40071
R/W
Control Setting - Enable Manual Stepping
1= Enable manual stepping. 0 = Disable manual stepping.
Use with Caution!
40072
R/W
Control Setting - Step to Next State
Set to 1 to step to the next state, 40072 must be set first,
Caution! Do NOT Step out of cooling without considering the
temperature in the regenerating tower. Instead, wait for cooling
cycle to complete
40073
R/W
Control Setting - Remote Shutdown
Set to remotely shutdown the dryer
40074
R/W
Control Setting - Remote Standby
Set to remotely place the dryer in standby.
40075
R/W
Control Setting - Heating Exhaust Limits Enable
Default is 1, Heating Exhaust Limits are active
40076
R/W
Control Setting - Cooling Exhaust Limits Enable
Default is 0, Cooling Exhaust Limits are not active
40077
R/W
Control Setting - Enable Inlet Filter
Display inlet filter pressure and enable alarm
40078
R/W
Control Setting - Store Factory Settings
Store copy of settings in PLC
40079
R/W
Control Setting - Recall Factory Settings
Restore copy of settings in PLC
40080
R/W
Control Setting - Dewpoint Sensor Enable
Dewpoint sensor is installed
40081
R/W
Control Setting - Test Drains
Set to fire drains.
40084
R/W
Control Setting - Enable Dual Acting Valve
Factory Setting - Dryer uses dual acting inlet valves
40085
R/W
Control Setting - Enable Pre-Exhaust Outputs
Factory Setting - Dryer uses pre-exhaust valves
40086
R/W
Alarm Setting - Acknowledge Alarms
Set to silence the alarm display and turn off the alarm relay until
next alarm occurs
40087
R/W
Alarm Setting - Clear all alarms
Reset all alarms, Restarts dryer if it is shutdown.
40088
R/W
Alarm Setting - Blowdown Alarm Enabled
see separate alarm chart for details
40089
R/W
Alarm Setting - Dewpoint Alarm Enabled
see separate alarm chart for details
40090
R/W
Alarm Setting - Low Inlet Pressure Alarm Enable
see separate alarm chart for details
40091
R/W
Alarm Setting - High Inlet Temp Alarm Enabled
see separate alarm chart for details
40092
R/W
Alarm Setting - After-Filter Alarm Enabled
see separate alarm chart for details
40093
R/W
Alarm Setting - Pre-Filter Alarm Enabled
see separate alarm chart for details
40094
R/W
Alarm Setting - Repressurization Alarm Enabled
see separate alarm chart for details
40095
R/W
Alarm Setting - Aux Sensor #1 Low Alarm Enabled
see separate alarm chart for details
40096
R/W
Alarm Setting - Aux Sensor #1 High Alarm Enabled
see separate alarm chart for details
40097
R/W
Alarm Setting - Aux Sensor #2 Low Alarm Enabled
see separate alarm chart for details
40098
R/W
Alarm Setting - Aux Sensor #2 High Alarm Enabled
see separate alarm chart for details
40099
R/W
User Sensor #1 Input Enable
Enables user input # 1
40100
R/W
User Sensor #2 Input Enable
Enables user input # 1
40101
R/W
Control - Reboot HMI Remotely
Remotely reboot the HMI, Useful if VNC server shuts down
unexpectedly due to high network traffic
Содержание Airtek TWB1000
Страница 1: ...1 Externally Heated Blower Purge Desiccant Dryers User Manual Models TWP TWB200 TWP TWB9000...
Страница 9: ...TWP TWB200 TWP TWB9000 9 TWP Desiccant Dryer Operation TWB Desiccant Dryer Operation...
Страница 10: ...TWP TWB200 TWP TWB9000 10 FLOW SCHEMATIC MODELS TWP200 300 DWG FS11682 Rev...
Страница 11: ...TWP TWB200 TWP TWB9000 11 FLOW SCHEMATIC MODELS TWP400 800 DWG FS11683 Rev...
Страница 12: ...TWP TWB200 TWP TWB9000 12 FLOW SCHEMATIC MODELS TWP1000 1500 DWG FS11684 Rev...
Страница 13: ...TWP TWB200 TWP TWB9000 13 FLOW SCHEMATIC MODELS TWP2000 9000 DWG FS11685 Rev...
Страница 14: ...TWP TWB200 TWP TWB9000 14 FLOW SCHEMATIC MODELS TWB200 800 DWG FS11686 Rev...
Страница 15: ...TWP TWB200 TWP TWB9000 15 FLOW SCHEMATIC MODELS TWB1000 1500 DWG FS11687 Rev...
Страница 16: ...TWP TWB200 TWP TWB9000 16 FLOW SCHEMATIC MODELS TWB2000 9000 DWG FS11688 Rev...
Страница 17: ...TWP TWB200 TWP TWB9000 17 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 18: ...TWP TWB200 TWP TWB9000 18 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 19: ...TWP TWB200 TWP TWB9000 19 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 20: ...TWP TWB200 TWP TWB9000 20 WIRING DIAGRAM STANDARD CONTROLLER...
Страница 21: ...TWP TWB200 TWP TWB9000 21 PANEL LAYOUT STANDARD CONTROLLER...
Страница 38: ...TWP TWB200 TWP TWB9000 38 Service Screen...
Страница 71: ...TWP TWB200 TWP TWB9000 71...