Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Page
D-17
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
COMMS CONTROL
SETUP::SEQ & REF::COMMS CONTROL
This block switches between Remote Terminal and Remote Comms operating modes.
The Drive must be in Remote mode for selection to be made - REMOTE mode is enabled in the LOCAL CONTROL function
block (REF MODES) and selected by the keypad. Refer to the outputs of the LOCAL CONTROL function block for the mode
in use.
Parameter Descriptions
REMOTE COMMS SEL
PREF: 95.01
Default: FALSE
Range: FALSE / TRUE
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is from the terminals.
1 : TRUE, and in REMOTE mode then control is from the communications.
FIREWIRE REF SEL
PREF: 95.10
Default: FALSE
Range:
FALSE / TRUE
This parameter selects Firewire Ref as the active reference.
REMOTE SEQ MODES
PREF: 95.02
Default: 0
Range: Enumerated - see below
Selects the type of remote sequencing mode:
Enumerated Value
:
Mode
0 : TERMINALS/COMMS
1 : TERMINALS ONLY
2 : COMMS ONLY
REMOTE REF MODES
PREF: 95.03
Default:0
Range: See below
Selects the type of remote reference mode:
Enumerated Value
:
Mode
0 : TERMINALS/COMMS
1 : TERMINALS ONLY
2 : COMMS ONLY