background image

Bulletin TI-NITROFLOW TG2-G 

Installation, Operation and Maintenance Manual

 TI-NITROFLOWTG2 

www.labgasgenerators.com

5

1-800-343-4048

The NitroFlow TG2 generator incorporates a water separator to remove liquid water from the 

compressed air before it reaches the prefilters. The liquids are collected in the supplied disposal 

container.  Refer to the included installation and maintenance instructions.  

Two stages of high efficiency coalescing pre-filters are incorporated into the design of the Nitroflow 

TG2 to remove water and particulate contamination to 0.1 micron.  The generator is equipped with 

float drain valves to automatically discharge any liquids which have accumulated in the filter bowls.  

The liquids are collected in the supplied disposal container.  These filters protect the membrane 

and associated components from contamination.

A 3-way pneumatic valve is located after the prefilters to release any leftover liquid water that may 

be present on startup.
An activated carbon module is located upstream of both the nitrogen module and the dryer module 

to remove any hydrocarbon contaminants that may exist in the room air.  A particulate filter is 

located after this carbon module to remove any carbon particles.

The NitroFlow TG2 generator has a hollow fiber membrane module which converts compressed 

air into high purity nitrogen.  The membrane module has no moving parts assuring years of 

maintenance-free operation. 

There is one activated carbon module and particulate filter after the nitrogen membrane to remove 

any contaminants present in the nitrogen stream. 

The water vapor in the compressed air passes through the hollow fibers of the membrane for 

removal, resulting in dry air.  A small portion of the dry air is redirected along the fibers to sweep out 

additional water vapor laden air and vented to atmosphere in the cabinet.  A dew point of -40°F is 

achieved at a pressure of 100 psig.
An activated carbon module is located downstream of the membrane dryer to remove any volatile 

organic compounds that may be present in the air stream. A filter is located after this carbon 

module to remove any carbon particles.

Prefilters

Water Separator

Hydrocarbon Removal

3-way Pneumatic Valve

3-way Pneumatic Valve

Dryer Membrane

Nitrogen Module

Outlet Carbon
Module & Filter

Outlet Carbon  
Module and Filter

Diagnostics

Figure 3

Figure 4

There are two diagnostic indicator lights on the Parker Balston NitroFlow TG2 System:

High Temperature LED (red):

  The “High Temperature” LED indicator illuminates when the 

compressor pump has reached its maximum temperature.  The compressor will shut down by a 

thermal switch opening, preventing power to the motor.  Compressor restarts automatically as 

soon as the over-temperature condition is corrected.

Power On LED (Green):

  This indicates the compressor is operating.

Installation

All installation, operation, and maintenance activities for the NitroFlowTG2 Generator System 

should be performed by trained personnel using reasonable care to avoid injury or damage.

The NitroFlow TG2 system has casters and is packed in a wooden shipping container.  The 

installation kit, consisting of plastic tubing, tube fittings, and a plug is packed in a box inside 

the wooden container.  Remove the wire L-shaped fasteners from the sides of the container 

(see Figure 3).  Do not attempt to lift the generator from the container.  Remove and locate the 

plywood ramp (see Figure 4).  Release the locked casters.  Move the generator down the ramp.  

Move the generator and installation kit to its installation location.

Unpacking

Содержание A03-0344

Страница 1: ...Bulletin TI NITROFLOW TG2 G Installation Operation and Maintenance Manual TI NITROFLOWTG2 www labgasgenerators com 1 1 800 343 4048 NitroFlow TG2 Installation Operation and Maintenance Manual...

Страница 2: ...2 www labgasgenerators com 2 1 800 343 4048 Symbol Description Caution refer to accompanying documents for explanation Refer to the caution note indicated for explanation Caution risk of electric shoc...

Страница 3: ...eered to produce pure nitrogen gas hydrocarbon free air and clean dry 40 F dew point air delivered by a carefully matched scroll compressor The system is housed in two fully integrated cabinets the lo...

Страница 4: ...where it is discharged from the pump A high output fan cools the compressor cabinet as it blows over a series of fins on the after cooler The compressor operates at a lower temperature thus increasing...

Страница 5: ...r removal resulting in dry air A small portion of the dry air is redirected along the fibers to sweep out additional water vapor laden air and vented to atmosphere in the cabinet A dew point of 40 F i...

Страница 6: ...ld be sized accordingly 3 The service should be protected by up to a minimum 20 Amp circuit breaker The value is based on the application equipment requirements as well as the electrical components to...

Страница 7: ...G2 generator 1 nitrogen outlet gas connection 2 dry air outlet gas connections 4 drain connections Press the tubing into the quick connect fittings Assure tubing is fully inserted about Tubing is prov...

Страница 8: ...and High Temperature The green LED remains illuminated during normal operation The other LED indicator High Temperature remains unlit if the compressor is functioning properly Red illumination of the...

Страница 9: ...e generator after the maintenance or repair is completed Prior to servicing the generator turn off the system and disconnect the cordset from the power supply Allow the system a minimum of 1 hour to d...

Страница 10: ...0 000 hours Filter Silencer P N 75117 1 30 000 hours Filter Element P N BZ100 180 DXE 1 30 000 hours Filter Element P N BZ100 180 BXE 1 30 000 hours Filter Element P N BZ100 090 BXE 4 Filter Silencer...

Страница 11: ...port of the filter housing by pushing the collet of the fitting towards the body of the fitting and pulling on the tube to release it see Figure 12 3 Remove the compressed air inlet tube from the elbo...

Страница 12: ...mount of grease according to the grease delivery Table 1 Figure 16 Note Pump grease gun before feeding to eliminate air from the needle adapter Each pump equals 0 65 grams of grease The volume of grea...

Страница 13: ...re 17 5 Replace fixed scroll and fan duct Torque bolts initially 17 inch lbs then finally 175 inch lbs Grease Pin Crank Bearing Figure 17 Note The grease fitting located in the center of the pin crank...

Страница 14: ...ing Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 8 After installing half of the low pressure seal carefully remove the seal from the channel to make sure the seal is properly locking onto the cha...

Страница 15: ...uses of the size and type specified in the Specifications section of this manual These instructions describe the replacing of the two coalescing pre filters two carbon modules and two particulate filt...

Страница 16: ...a new one see Figure 42 4 Reverse the steps to re assemble Make sure the o ring is sealed in the groove before reinstalling the bowl Hand tighten plus 1 4 turn using the 1 wrench Figure 39 Figure 40 F...

Страница 17: ...Note both the bulkhead and quick disconnect fittings will be reused with the new drain assembly Parker recommends the use of Teflon plumbers tape on the treads of these fittings during reassembly 8 Re...

Страница 18: ...egory II IEC 61010 Pollution Degree 2 Impact Code IK08 EMC Compliance EN61326 1 CISPR 11 Curtain Gas N2 Purity 99 999 Organics 96 93 N2 depending on flow Curtain Gas Max Flow Pressure 30 SLPM 80 PSIG...

Страница 19: ...ould perform any troubleshooting activities Determine whether the trouble is with the compressor or the gas generator Disconnect the plastic tubing from the compressor fitting see Figure 43 Once remov...

Страница 20: ...y and unit power rating Replace contractor assembly Replace motor Compressor is running but will not make pressure Auto drain valve is open continuously Drive belts broke or are too loose Clogged inta...

Страница 21: ...oling air fan Re grease Clean aftercooler Replace tip seals per instructions every 5 000 hrs Check replace filter Clean unit Compressor shuts down on temperature malfunction Temperature switch has unp...

Страница 22: ...arryover due to filter float drain malfunction High relative humidity Total flow demand greater than 68 SPLM for the Gas 1 Gas 2 and source gas outlets Turn on compressor Open pressure regulator Check...

Страница 23: ...the original price for the product This warranty applies only to defects in material or workmanship and does not cover wear components on compressors routine maintenance recommended by the instructio...

Страница 24: ...Bulletin TI NITROFLOW TG2 G Installation Operation and Maintenance Manual TI NITROFLOWTG2 www labgasgenerators com 24 1 800 343 4048 Figure 49...

Страница 25: ...Bulletin TI NITROFLOW TG2 G Installation Operation and Maintenance Manual TI NITROFLOWTG2 www labgasgenerators com 25 1 800 343 4048...

Страница 26: ...Bulletin TI NITROFLOW TG2 G Installation Operation and Maintenance Manual TI NITROFLOWTG2 www labgasgenerators com 26 1 800 343 4048...

Страница 27: ...Bulletin TI NITROFLOW TG2 G Installation Operation and Maintenance Manual TI NITROFLOWTG2 www labgasgenerators com 27 1 800 343 4048...

Страница 28: ...C L A B L E R E C Y C L A BLE 2012 2019 Parker Hannifin Corporation Printed in U S A Bulletin TI NITROFLOWTG2 PKI A 7 2019 Parker Hannifin Manufacturing Limited Gas Separation and Filtration Division...

Отзывы: