![Parker 890CS Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/parker/890cs/890cs_quick-start-manual_3762821007.webp)
Page
7
Installation
A simplified installation is shown below. This installation is
not
EMC compliant. For European
installations and countries with EMC legislation refer to the 890 Engineering Reference Manual,
Appendix C.
KEY
B
Back-plate
C
Cubicle
G
Supply
Protective
Earth/Ground
K
Motor
(M1, M2, M3)
L
3
∅
Power
Supply Cable
(L1, L2, L3)
P
Fuse or circuit
breaker
R
AC Line
Reactor
T
Control Wiring
Terminals
890 Installation Kit
The 890 Installation Kit is shown in the diagram attached to the bottom of
the 890CD units. It can also be fixed to the top of the unit.
The kit provides several options for earth/ground connections. It also
includes the brackets for DIN rail mounting the unit. Refer to the instructions
in the kit and use the appropriate parts.
* Permanent Earthing
The unit must be
permanently earthed
according to EN 50178: A cross-
section conductor of at least 10mm² is required. This can be achieved either
by using a single conductor (PE) or by laying a second conductor though
separate terminals (PE2 where provided) and electrically in parallel.
Содержание 890CS
Страница 9: ...Page 9 Overview...
Страница 27: ...Page 27 890CD Control Terminals...
Страница 28: ...Page 28 890SD Control Terminals...
Страница 29: ...Page 29 890CS Control Terminals...
Страница 30: ...Page 30 Appendix D Electrical Ratings 890CS Common Bus Supply...
Страница 31: ...Page 31 890CD Common Bus Drive...
Страница 32: ...Page 32...