![Parker 890CS Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/parker/890cs/890cs_quick-start-manual_3762821013.webp)
Page
13
890CS Control Connections
Sequencing
•
Terminals X02/05 and X02/06
provide an analog output proportional to Input Current or Power.
•
Terminals X04/01 and X04/02
provide a Health warning contact signalling an impending fault.
•
Terminals X04/05 and X04/06
provide a Health Trip contact signalling the drive has faulted.
Indication
Use a small slotted screwdriver to set the rotary
switch S1 to match the voltage of the incoming
3-phase power.
NOTE: This is factory set to 500V. This MUST be
set to the incoming line voltage.
A
Voltage Selection
•
Connect a 24VDC power supply across
terminals X01/01 and X01/04 (mandatory).
24VDC in
terminal X01/01
0VDC in
terminal X01/04
•
Run 24VDC power to supply 890CDs
(optional).
24VDC out
terminal X01/02
0VDC out
terminal X01/03
24V Aux Supply
B
Connect a volt-free
contact
•
RUN (maintained
contact) across
terminals X02/01
and X02/03
Terminals
X04/01 & X04/02
X04/05 & X04/06
If the supply to these
volt-free relays is
>25Vac rms
or
>60V dc
,
you must provide an
appropriate fusing
system of 10A for the
supply to these digital
outputs to comply with
UL Earthing
Requirements.
DIGIN 1
This is for future
use. Leave the
terminal open.
Содержание 890CS
Страница 9: ...Page 9 Overview...
Страница 27: ...Page 27 890CD Control Terminals...
Страница 28: ...Page 28 890SD Control Terminals...
Страница 29: ...Page 29 890CS Control Terminals...
Страница 30: ...Page 30 Appendix D Electrical Ratings 890CS Common Bus Supply...
Страница 31: ...Page 31 890CD Common Bus Drive...
Страница 32: ...Page 32...
Страница 33: ...Page 33...